Topic on Talk:TN system - Earth-fault current calculation
From Electrical Installation Guide
- (cur prev topic) 10:41, 23 July 2024 . . LMischler (talk | contribs) created topic summary on resistivity used en the Convencional method . . +195
- (cur prev topic) 10:38, 23 July 2024 . . LMischler (talk | contribs) marked the topic "resistivity used en the Convencional method" as resolved (marked as resolved) . . 0
- (cur prev topic) 14:18, 12 July 2024 . . Mathieu GUILLOT (talk | contribs) commented on "resistivity used en the Convencional method" (@Alberto together with our expert @Mathieu GUILLOT, we have now prepared and implemented some changes to this page, for clarification on...) . . +526
- (cur prev topic) 14:28, 12 June 2024 . . LMischler (talk | contribs) edited a post on "resistivity used en the Convencional method" . . +1
- (cur prev topic) 14:27, 12 June 2024 . . LMischler (talk | contribs) commented on "resistivity used en the Convencional method" (@Mathieu GUILLOT I believe the values of ρ shown in this wiki page are for a temperature of 90°C. Taking as reference the IEC 60909 (valu...) . . +719
- (cur prev topic) 10:49, 12 June 2024 . . Mathieu GUILLOT (talk | contribs) commented on "resistivity used en the Convencional method" (Hello, I agree, The values of resistivity given (23.7 10-3) is valid for 115°C (Rho 20°C Cu = 1.72 10-8 Ohm.m Cu T° Factor / 20°C : 3.93...) . . +324
- (cur prev topic) 23:11, 6 June 2024 . . Alberto (talk | contribs) commented on "resistivity used en the Convencional method" (Hi: I think there is an error in the following sentence: "ρ = resistivity at normal working temperature in ohm-mm2/meter (= 23.7 10-3 for...) . . +460