Choice of transformer rating: Difference between revisions

From Electrical Installation Guide
(Created page with '{{Menu_General_rules_of_electrical_installation_design}} <br> When an installation is to be supplied directly from a MV/LV transformer and the maximum apparent-power loading of …')
 
Line 144: Line 144:


<br>
<br>
[[ru:Выбор номинальной мощности трансформатора]]

Revision as of 14:17, 14 September 2012


When an installation is to be supplied directly from a MV/LV transformer and the maximum apparent-power loading of the installation has been determined, a suitable rating for the transformer can be decided, taking into account the following considerations (see Fig. A15):

  • The possibility of improving the power factor of the installation (see chapter L)
  • Anticipated extensions to the installation
  • Installation constraints (e.g. temperature)
  • Standard transformer ratings


Apparent power kVA 

In (A)
237 V 410 V
100 244 141
160 390 225
250 609 352
315 767 444
400 974 563
500 1218 704
630 1535 887
800 1939 1127
1000 2436 1408
1250 3045 1760
1600 3898 2253
2000 4872 2816
2500 6090 3520
3150 7673 4436






















Fig. A15: Standard apparent powers for MV/LV transformers and related nominal output currents


The nominal full-load current In on the LV side of a 3-phase transformer is given by:

[math]\displaystyle{ \mbox{In}=\frac{\mbox{Pa}\times10^3}{\mbox{U}\sqrt3} }[/math]

  • Pa = kVA rating of the transformer
  • U = phase-to-phase voltage at no-load in volts (237 V or 410 V)
  • In is in amperes.

For a single-phase transformer:

[math]\displaystyle{ \mbox{In}=\frac{\mbox{Pa}\times10^3}{\mbox{V}} }[/math]
where

  • V = voltage between LV terminals at no-load (in volts)

Simplified equation for 400 V (3-phase load)

  • In = kVA x 1.4
  • The IEC standard for power transformers is IEC 60076.


ru:Выбор номинальной мощности трансформатора

Share