For the best results in electrical installation design it is recommended to read all the chapters of this guide in the order in which they are presented.  
For the best results in electrical installation design it is recommended to read and to use all the chapters of this guide in the order in which they are presented.




== Listing of power demands  ==
== Rules and statutory regulations ==
* cf chapter [[General rules of electrical installation design]]
 
Range of low-voltage extends from 0 V to 1 000 V in a.c. and from 0 V to 1 500V in d.c. One of the first decision id the selection of type of current between the alternative current which corresponds to the most common type of current through out the world and the direct current. Then designers have to select the most appropriate rated voltage within these ranges of voltages. When connected to a LV public network, the type of current and the rated voltage are already selected and imposed by the Utility.
 
Compliance with national regulations is then the second priority of the designers of electrical installation. Regulations may be based on national or international standards such as the IEC 60364 series.
 
Selection of equipment complying with national or international product standards and appropriate verification of the completed installation is a powerful mean for providing a safe installation with the expected quality. Defining and complying with the verification and testing of the electrical installation at its completion as well as periodic time will guarantee the safety and the quality of this installation all along its
life cycle. Conformity of equipment according to the appropriate product standards used within the installation is also of prime importance for the level of safety and quality.
 
Environmental conditions will become more and more stringent and will need to be considered at the design stage of the installation. This may include national or regional regulations considering the material used in the equipment as well as the dismantling of the installation at its end of life
 
 
== Installed power loads - Characteristics ==
* cf pages [[Installed power loads - Characteristics]] and [[Power loading of an installation]]


* cf chapter [[General rules of electrical installation design]]
A review of all applications needing to be supplied with electricity is to be done. Any possible extensions or modifications during the whole life of the electrical installation are to be considered. Such a review aimed to estimate the current flowing in each circuit of the installation and the power supplies needed.
 
The total current or power demand can be calculated from the data relative to the location and power of each load, together with the knowledge of the operating modes(steady state demand, starting conditions, non simultaneous operation, etc.)


The study of a proposed electrical installation requires an adequate understanding of all [[General rules of electrical installation design#Electrical installation rules, standards|governing rules and regulations]]. The total power demand can be calculated from the data relative to the location and power of each load, together with the knowledge of the operating modes (steady state demand, starting conditions, non simultaneous operation, etc.)
Estimation of the maximum power demand may use various factors depending on the type of application; type of equipment and type of circuits used within the electrical installation.


From these data, the power required from the supply source and (where appropriate) the number of sources necessary for an adequate supply to the installation are readily obtained.  
From these data, the power required from the supply source and (where appropriate)the number of sources necessary for an adequate supply to the installation is readily obtained.


Local information regarding tariff structures is also required to allow the best choice of connection arrangement to the power-supply network, e.g. at medium voltage or low voltage level.
Local information regarding tariff structures is also required to allow the best choice of connection arrangement to the power-supply network, e.g. at medium voltage or low voltage level.




== Service connection  ==
== Connection to the MV public distribution network ==
* cf chapter [[Connection to the MV utility distribution network]]
 
Where this connection is made at the Medium Voltage level a consumer-type substation will have to be studied, built and equipped. This substation may be an outdoor or indoor installation conforming to relevant standards and regulations (the low-voltage section may be studied separately if necessary). Metering at mediumvoltage or low-voltage is possible in this case.


This connection can be made at:


* '''Medium Voltage level''' : cf chapter [[Connection to the MV utility distribution network]]
== Connection to the LV utility distribution network ==
A consumer-type substation will then have to be studied, built and equipped. This substation may be an outdoor or indoor installation conforming to relevant standards and regulations (the low-voltage section may be studied separately if necessary). Metering at medium-voltage or low-voltage is possible in this case.
* cf chapter [[Connection to the LV utility distribution network]]


* '''Low Voltage level''' : cf chapter [[Connection to the LV utility distribution network]]
Where the connection is made at the Low Voltage level the installation will be connected to the local power network and will (necessarily) be metered according to LV tariffs.
The installation will be connected to the local power network and will (necessarily) be metered according to LV tariffs.




== Electrical Distribution architecture ==
== MV & LV architecture selection guide ==
* cf chapter [[MV & LV architecture selection guide]]


* cf chapters [[MV & LV architecture selection guide]] and [[LV Distribution]]
The whole electrical system including the MV installation and the LV installation is to be studied as a complete system. The customer expectations and technical parameters will impact the architecture of the system as well as the electrical installation characteristics.


The whole installation distribution network is studied as a complete system.
Determination of the most suitable architecture of the MV/LV main distribution and LV power distribution level is often the result of optimization and compromise.
A selection guide is proposed for determination of the most suitable architecture.
MV/LV main distribution and LV power distribution levels are covered.  


Neutral earthing arrangements are chosen according to local regulations, constraints related to the power-supply, and to the type of loads.
Neutral earthing arrangements are chosen according to local regulations, constraints related to the power-supply, and to the type of loads.
The distribution equipment (panelboards, switchgears, circuit connections, ...) are determined from building plans and from the location and grouping of loads. The type of premises and allocation can influence their immunity to external disturbances.


The distribution equipment (panelboards, switchgears, circuit connections, ...) are determined from building plans and from the location and grouping of loads.


== Protection against electric shocks  ==
The type of premises and allocation can influence their immunity to external disturbances.


* cf chapter [[Protection against electric shocks]]


The earthing system (TT, IT or TN) having been previously determined, then the appropriate protective devices must be implemented in order to achieve protection against hazards of direct or indirect contact.  
== LV distribution ==
* cf chapter [[LV Distribution]]
 
The system earthing is one protective measures commonly used for the protection against electric shocks. These systems earthings have a major impact on the LV electrical installation architecture and they need to be analysed as early as possible. Advantages and drawbacks are to be analysed for a correct selection.


Another aspect needing to be considered at the earlier stage is the external influences. In large electrical installation, different external influences may be encountered and need to be considered independently. As a result of these external influences proper selection of equipment according to their IP or IK codes has to be made.


== Circuits and switchgear  ==


* cf chapters [[Sizing and protection of conductors]] and [[LV switchgear: functions & selection]]
== Protection against electric shocks ==
* cf chapter [[Protection against electric shocks]]


Each circuit is then studied in detail. From the rated currents of the loads, the level of short-circuit current, and the type of protective device, the cross-sectional area of circuit conductors can be determined, taking into account the nature of the cableways and their influence on the current rating of conductors.  
Protection against electric shock consists in providing provision for basic protection (protection against direct contact) with provision for fault protection (protection against indirect contact). Coordinated provisions result in a protective measure.<br>
One of the most common protective measures consists in “automatic disconnection of supply” where the provision for fault protection consists in the implementation of a system earthing. Deep understanding of each standardized system (TT, TN and IT system) is necessary for a correct implementation.


Before adopting the conductor size indicated above, the following requirements must be satisfied:


*The voltage drop complies with the relevant standard
== Sizing and protection of conductors ==
*Motor starting is satisfactory
* cf chapter [[Sizing and protection of conductors]]
*Protection against electric shock is assured


The short-circuit current Isc is then determined, and the thermal and electrodynamic withstand capability of the circuit is checked.
Selection of cross-sectional-areas of cables or isolated conductors for line conductors is certainly one of the most important tasks of the designing process of an electrical installation as this greatly influences the selection of overcurrent protective devices, the voltage drop along these conductors and the estimation of the prospective short-circuits currents: the maximum value relates to the overcurrent protection and the minimum value relates to the fault protection by automatic disconnection of supply. This has to be done for each circuit of the installation.
Similar task is to be done for the neutral conductors and for the Protective Earth (PE) conductor.


These calculations may indicate that it is necessary to use a conductor size larger than the size originally chosen.


The performance required by the switchgear will determine its type and characteristics.
== LV switchgear: functions & selection ==
* cf chapter [[LV switchgear: functions & selection]]


The use of cascading techniques and the discriminative operation of fuses and tripping of circuit breakers are examined.
Once the short-circuit current are estimated, protective devices can be selected for the overcurrent protection. Circuit-breakers have also other possible functions such as switching and isolation. A complete understanding of the functionalities offered by all switchgear and controlgear within the installation is necessary. Correct selection of all devices can now be done.


A comprehensive understanding of all functionalities offered by the circuit-breakers is of prime importance as this is the device offering the largest variety of functions.


== Protection against overvoltages  ==


== Overvoltage protection ==
* cf chapter [[Protection against voltage surges in LV]]
* cf chapter [[Protection against voltage surges in LV]]


Direct or indirect lightning strokes can damage electrical equipment at a distance of several kilometers. Operating voltage surges, transient and industrial frequency over-voltage can also produce the same consequences.The effects are examined and solutions are proposed.  
Direct or indirect lightning strokes can damage electrical equipment at a distance of several kilometres. Operating voltage surges, transient and industrial frequency overvoltage can also produce the same consequences.All protective measures against overvoltage need to be assessed. One of the most used corresponds to the use of Surge Protective Devices (SPD). Their selection; installation and protection within the
electrical installation request some particular attention.




== Energy efficiency in electrical distribution ==
== Energy efficiency in electrical distribution ==
 
* cf chapter [[Energy Efficiency in electrical distribution]]
* cf chapter [[Energy Efficiency in electrical distribution]]


Implementation of measuring devices with an adequate communication system within the electrical installation can produce high benefits for the user or owner: reduced power consumption, reduced cost of energy, better use of electrical equipment.
Implementation of active energy efficiency measures within the electrical installation can produce high benefits for the user or owner: reduced power consumption, reduced cost of energy, better use of electrical equipment. These measures will most of the time request specific design for the installation as measuring electricity consumption either per application (lighting, heating, process…) or per area (floor, workshop) present particular interest for reducing the electricity consumption stillkeeping the same level of service provided to the user.
 


== Reactive energy  ==


== Reactive energy ==
* cf chapter [[Power factor correction and harmonic filtering]]
* cf chapter [[Power factor correction and harmonic filtering]]


The power factor correction within electrical installations is carried out locally, globally or as a combination of both methods.  
The power factor correction within electrical installations is carried out locally, globally or as a combination of both methods. Improving the power factor has a direct impact on the billing of consumed electricity and may also have an impact on the energy efiiciency.
 


== Harmonics  ==


== Harmonics ==
* cf chapter [[Power harmonics management]]
* cf chapter [[Power harmonics management]]


Harmonics in the network affect the quality of energy and are at the origin of many disturbances as overloads, vibrations, ageing of equipment, trouble of sensitive equipment, of local area networks, telephone networks. This chapter deals with the origins and the effects of harmonics and explain how to measure them and present the solutions.
Harmonic currents in the network affect the quality of energy and are at the origin of many disturbances as overloads, vibrations, ageing of equipment, trouble of sensitive equipment, of local area networks, telephone networks. This chapter deals with the origins and the effects of harmonics and explain how to measure them and present the solutions.




== Particular supply sources and loads ==
== Particular supply sources and loads ==
 
* cf chapter [[Characteristics of particular sources and loads]]
* cf chapter [[Characteristics of particular sources and loads]]


Particular items or equipment are studied:
Particular items or equipment are studied:
* Specific sources such as alternators or inverters
* Specific loads with special characteristics, such as induction motors, lighting circuits or LV/LV transformers
* Specific systems, such as direct-current networks


*Specific sources such as [[Characteristics of particular sources and loads#Protection of a LV generator set and the downstream circuits|alternators]] or [[Characteristics of particular sources and loads#Uninterruptible Power Supply units (UPS)|inverters]]
*Specific loads with special characteristics, such as [[Characteristics of particular sources and loads#Asynchronous motors|induction motors]], [[Characteristics of particular sources and loads#Lighting circuits|lighting circuits]] or [[Characteristics of particular sources and loads#Protection of LV/LV transformers|LV/LV transformers]]
*Specific systems, such as direct-current networks
== A green and economical energy  ==


== A green and economical energy ==
* cf chapter [[PhotoVoltaic (PV) installation]]
* cf chapter [[PhotoVoltaic (PV) installation]]


Line 113: Line 128:




== Generic applications ==
== Generic applications ==
* cf chapter [[Residential electrical installations]]


Certain premises and locations are subject to particularly strict regulations: the most common example being residential dwellings.
Certain premises and locations are subject to particularly strict regulations: the most common example being residential dwellings.
* cf chapter [[Residential electrical installations]]


== EMC Guidelines  ==


== EMC Guidelines ==
* cf chapter [[ElectroMagnetic Compatibility (EMC)]]
* cf chapter [[ElectroMagnetic Compatibility (EMC)]]


Some basic rules must be followed in order to ensure Electromagnetic Compatibility. Non observance of these rules may have serious consequences in the operation of the electrical installation: disturbance of communication systems, nuisance tripping of protection devices, and even destruction of sensitive devices.  
Some basic rules must be followed in order to ensure Electromagnetic Compatibility. Non observance of these rules may have serious consequences in the operation of the electrical installation: disturbance of communication systems, nuisance tripping of protection devices, and even destruction of sensitive devices.
 
 


== Ecodial software  ==


Ecodial software<ref name="Ecodial" /> provides a complete design package for LV installations, in accordance with IEC standards and recommendations. <br>The following features are included:
== Ecodial software ==
Ecodial software <ref name="Ecodial" /> provides a complete design package for LV installations, in accordance with IEC standards and recommendations.


*Construction of one-line diagrams  
The following features are included:
*Calculation of short-circuit currents  
* Construction of one-line diagrams
*Calculation of voltage drops  
* Calculation of short-circuit currents according to several operating modes (normal, back-up, load shedding)
*Optimization of cable sizes  
* Calculation of voltage drops
*Required ratings of switchgear and fusegear  
* Optimization of cable sizes
*Discrimination of protective devices  
* Required ratings and settings of switchgear and fusegear
*Recommendations for cascading schemes
* Discrimination of protective devices
*Verification of the protection of people  
* Optimization ofswitchgear using cascading
*Comprehensive print-out of the foregoing calculated design data
* Verification of the protection of people and circuits
* Comprehensive print-out of the foregoing calculated design data




== References ==
== References ==
<references>
<references>
<ref name="Ecodial">Ecodial is a Schneider Electric software and is available in French and English versions.</ref>
<ref name="Ecodial">Ecodial is a Schneider Electric software available in several languages and standard version.</ref>
</references>
</references>


[[ru:Методология]]
[[ru:Методология]]
[[zh:电气装置设计方法]]
[[zh:电气装置设计方法]]

Revision as of 10:13, 19 August 2013


For the best results in electrical installation design it is recommended to read and to use all the chapters of this guide in the order in which they are presented.


Rules and statutory regulations

Range of low-voltage extends from 0 V to 1 000 V in a.c. and from 0 V to 1 500V in d.c. One of the first decision id the selection of type of current between the alternative current which corresponds to the most common type of current through out the world and the direct current. Then designers have to select the most appropriate rated voltage within these ranges of voltages. When connected to a LV public network, the type of current and the rated voltage are already selected and imposed by the Utility.

Compliance with national regulations is then the second priority of the designers of electrical installation. Regulations may be based on national or international standards such as the IEC 60364 series.

Selection of equipment complying with national or international product standards and appropriate verification of the completed installation is a powerful mean for providing a safe installation with the expected quality. Defining and complying with the verification and testing of the electrical installation at its completion as well as periodic time will guarantee the safety and the quality of this installation all along its life cycle. Conformity of equipment according to the appropriate product standards used within the installation is also of prime importance for the level of safety and quality.

Environmental conditions will become more and more stringent and will need to be considered at the design stage of the installation. This may include national or regional regulations considering the material used in the equipment as well as the dismantling of the installation at its end of life


Installed power loads - Characteristics

A review of all applications needing to be supplied with electricity is to be done. Any possible extensions or modifications during the whole life of the electrical installation are to be considered. Such a review aimed to estimate the current flowing in each circuit of the installation and the power supplies needed.

The total current or power demand can be calculated from the data relative to the location and power of each load, together with the knowledge of the operating modes(steady state demand, starting conditions, non simultaneous operation, etc.)

Estimation of the maximum power demand may use various factors depending on the type of application; type of equipment and type of circuits used within the electrical installation.

From these data, the power required from the supply source and (where appropriate)the number of sources necessary for an adequate supply to the installation is readily obtained.

Local information regarding tariff structures is also required to allow the best choice of connection arrangement to the power-supply network, e.g. at medium voltage or low voltage level.


Connection to the MV public distribution network

Where this connection is made at the Medium Voltage level a consumer-type substation will have to be studied, built and equipped. This substation may be an outdoor or indoor installation conforming to relevant standards and regulations (the low-voltage section may be studied separately if necessary). Metering at mediumvoltage or low-voltage is possible in this case.


Connection to the LV utility distribution network

Where the connection is made at the Low Voltage level the installation will be connected to the local power network and will (necessarily) be metered according to LV tariffs.


MV & LV architecture selection guide

The whole electrical system including the MV installation and the LV installation is to be studied as a complete system. The customer expectations and technical parameters will impact the architecture of the system as well as the electrical installation characteristics.

Determination of the most suitable architecture of the MV/LV main distribution and LV power distribution level is often the result of optimization and compromise.

Neutral earthing arrangements are chosen according to local regulations, constraints related to the power-supply, and to the type of loads.

The distribution equipment (panelboards, switchgears, circuit connections, ...) are determined from building plans and from the location and grouping of loads.

The type of premises and allocation can influence their immunity to external disturbances.


LV distribution

The system earthing is one protective measures commonly used for the protection against electric shocks. These systems earthings have a major impact on the LV electrical installation architecture and they need to be analysed as early as possible. Advantages and drawbacks are to be analysed for a correct selection.

Another aspect needing to be considered at the earlier stage is the external influences. In large electrical installation, different external influences may be encountered and need to be considered independently. As a result of these external influences proper selection of equipment according to their IP or IK codes has to be made.


Protection against electric shocks

Protection against electric shock consists in providing provision for basic protection (protection against direct contact) with provision for fault protection (protection against indirect contact). Coordinated provisions result in a protective measure.
One of the most common protective measures consists in “automatic disconnection of supply” where the provision for fault protection consists in the implementation of a system earthing. Deep understanding of each standardized system (TT, TN and IT system) is necessary for a correct implementation.


Sizing and protection of conductors

Selection of cross-sectional-areas of cables or isolated conductors for line conductors is certainly one of the most important tasks of the designing process of an electrical installation as this greatly influences the selection of overcurrent protective devices, the voltage drop along these conductors and the estimation of the prospective short-circuits currents: the maximum value relates to the overcurrent protection and the minimum value relates to the fault protection by automatic disconnection of supply. This has to be done for each circuit of the installation. Similar task is to be done for the neutral conductors and for the Protective Earth (PE) conductor.


LV switchgear: functions & selection

Once the short-circuit current are estimated, protective devices can be selected for the overcurrent protection. Circuit-breakers have also other possible functions such as switching and isolation. A complete understanding of the functionalities offered by all switchgear and controlgear within the installation is necessary. Correct selection of all devices can now be done.

A comprehensive understanding of all functionalities offered by the circuit-breakers is of prime importance as this is the device offering the largest variety of functions.


Overvoltage protection

Direct or indirect lightning strokes can damage electrical equipment at a distance of several kilometres. Operating voltage surges, transient and industrial frequency overvoltage can also produce the same consequences.All protective measures against overvoltage need to be assessed. One of the most used corresponds to the use of Surge Protective Devices (SPD). Their selection; installation and protection within the electrical installation request some particular attention.


Energy efficiency in electrical distribution

Implementation of active energy efficiency measures within the electrical installation can produce high benefits for the user or owner: reduced power consumption, reduced cost of energy, better use of electrical equipment. These measures will most of the time request specific design for the installation as measuring electricity consumption either per application (lighting, heating, process…) or per area (floor, workshop) present particular interest for reducing the electricity consumption stillkeeping the same level of service provided to the user.


Reactive energy

The power factor correction within electrical installations is carried out locally, globally or as a combination of both methods. Improving the power factor has a direct impact on the billing of consumed electricity and may also have an impact on the energy efiiciency.


Harmonics

Harmonic currents in the network affect the quality of energy and are at the origin of many disturbances as overloads, vibrations, ageing of equipment, trouble of sensitive equipment, of local area networks, telephone networks. This chapter deals with the origins and the effects of harmonics and explain how to measure them and present the solutions.


Particular supply sources and loads

Particular items or equipment are studied:

  • Specific sources such as alternators or inverters
  • Specific loads with special characteristics, such as induction motors, lighting circuits or LV/LV transformers
  • Specific systems, such as direct-current networks


A green and economical energy

The solar energy development has to respect specific installation rules.


Generic applications

Certain premises and locations are subject to particularly strict regulations: the most common example being residential dwellings.


EMC Guidelines

Some basic rules must be followed in order to ensure Electromagnetic Compatibility. Non observance of these rules may have serious consequences in the operation of the electrical installation: disturbance of communication systems, nuisance tripping of protection devices, and even destruction of sensitive devices.


Ecodial software

Ecodial software [1] provides a complete design package for LV installations, in accordance with IEC standards and recommendations.

The following features are included:

  • Construction of one-line diagrams
  • Calculation of short-circuit currents according to several operating modes (normal, back-up, load shedding)
  • Calculation of voltage drops
  • Optimization of cable sizes
  • Required ratings and settings of switchgear and fusegear
  • Discrimination of protective devices
  • Optimization ofswitchgear using cascading
  • Verification of the protection of people and circuits
  • Comprehensive print-out of the foregoing calculated design data