Coordination between circuit-breakers: Difference between revisions

From Electrical Installation Guide
Home > LV switchgear: functions and selection > Circuit-breaker > Coordination between circuit-breakers
m (r2.7.2) (robot Adding: zh:断路器间的配合)
(updated according to guide 2013 (+ format))
Line 1: Line 1:
{{Menu_LV_switchgear_functions_&_selection}}
{{Menu_LV_switchgear_functions_and_selection}}
__TOC__
__TOC__


Line 11: Line 11:


'''Definition of the cascading technique''' <br>By limiting the peak value of short-circuit current passing through it, a current-limiting CB permits the use, in all circuits downstream of its location, of switchgear and circuit components having much lower short-circuit breaking capacities, and thermal and electromechanical withstand capabilities than would otherwise be necessary. Reduced physical size and lower performance requirements lead to substantial economy and to the simplification of installation work. It may be noted that, while a current-limiting circuit-breaker has the effect on downstream circuits of (apparently) increasing the source impedance during short-circuit conditions, it has no such effect in any other condition; for example, during the starting of a large motor (where a low source impedance is highly desirable). The range of Compact NSX current-limiting circuit-breakers with powerful limiting performances is particularly interesting.
'''Definition of the cascading technique''' <br>By limiting the peak value of short-circuit current passing through it, a current-limiting CB permits the use, in all circuits downstream of its location, of switchgear and circuit components having much lower short-circuit breaking capacities, and thermal and electromechanical withstand capabilities than would otherwise be necessary. Reduced physical size and lower performance requirements lead to substantial economy and to the simplification of installation work. It may be noted that, while a current-limiting circuit-breaker has the effect on downstream circuits of (apparently) increasing the source impedance during short-circuit conditions, it has no such effect in any other condition; for example, during the starting of a large motor (where a low source impedance is highly desirable). The range of Compact NSX current-limiting circuit-breakers with powerful limiting performances is particularly interesting.


== Conditions of implementation  ==
== Conditions of implementation  ==
Line 19: Line 20:
|}
|}


Most national standards admit the cascading technique, on condition that the amount of energy “let through” by the limiting CB is less than the energy all downstream CBs and components are able to withstand without damage.<br>In practice this can only be verified for CBs by tests performed in a laboratory. Such tests are carried out by manufacturers who provide the information in the form of tables, so that users can confidently design a cascading scheme based on the combination of recommended circuit-breaker types. As an example, '''Figure&nbsp;H48 '''indicates the cascading possibilities of circuit-breaker types C60, DT40N, C120 and NG125 when installed downstream of current-limiting CBs Compact NSX 250 N, H or L for a 230/400 V or 240/415 V 3-phase installation.  
Most national standards admit the cascading technique, on condition that the amount of energy “let through” by the limiting CB is less than the energy all downstream CBs and components are able to withstand without damage.<br>In practice this can only be verified for CBs by tests performed in a laboratory. Such tests are carried out by manufacturers who provide the information in the form of tables, so that users can confidently design a cascading scheme based on the combination of recommended circuit-breaker types. As an example, '''Figure&nbsp;H48 '''indicates the cascading possibilities of circuit-breaker types iC60, DT40N, C120 and NG125 when installed downstream of current-limiting CBs Compact NSX 250 N, H or L for a 230/400 V or 240/415 V 3-phase installation.  


----
<br>


{| style="width: 517px; height: 319px" cellspacing="1" cellpadding="1" width="517" border="1"
{| style="width: 517px; height: 319px" cellspacing="1" cellpadding="1" width="517" border="1"
Line 33: Line 31:
| bgcolor="#0099cc" |  
| bgcolor="#0099cc" |  
|-
|-
| valign="top" rowspan="4" | '''Short-circuit&nbsp;breaking capacity of the upstream (limiter) CBs'''  
| valign="top" rowspan="4" | '''Short-circuit breaking capacity of the upstream (limiter) CBs'''  
| 150&nbsp;&nbsp;&nbsp;  
| 150&nbsp;&nbsp;&nbsp;  
| &nbsp;  
| &nbsp;  
Line 77: Line 75:
|-
|-
| 30  
| 30  
| C60N/H&lt;=32A  
| iC60N/H&lt;=32A  
| C60N/H&lt;=32A  
| iC60N/H&lt;=32A  
| C60N/H&lt;=32A
| iC60N/H&lt;=32A
|-
|-
| valign="top" | 30  
| valign="top" | 30  
| valign="top" | C60L&lt;=25A  
| valign="top" | iC60L&lt;=25A  
| C60L&lt;=25A(*)<br>Quick PRD<br>40/20/8  
| iC60L&lt;=25A(*)<br>Quick PRD<br>40/20/8  
| valign="top" | C60L&lt;=25A
| valign="top" | iC60L&lt;=25A
|-
|-
| valign="top" | 25  
| valign="top" | 25  
| C60H&gt;=40A<br>C120N/H  
| iC60H&gt;=40A<br>C120N/H  
| C60H&gt;=40A<br>C120N/H  
| iC60H&gt;=40A<br>C120N/H  
| C60H&gt;=40A<br>C120N/H
| iC60H&gt;=40A<br>C120N/H
|-
|-
| 20  
| 20  
| C60N&gt;=40A  
| iC60N&gt;=40A  
| C60N&gt;=40A  
| iC60N&gt;=40A  
| C60N&gt;=40A
| iC60N&gt;=40A
|}
|}
(*) Quick PRD with integrated circuit-breaker as disconnector see chapter J


'''''Fig. H48: '''Example of cascading possibilities on a 230/400 V or 240/415 V 3-phase installation''  
'''''Fig. H48: '''Example of cascading possibilities on a 230/400 V or 240/415 V 3-phase installation''  


----


== Advantages of cascading  ==
== Advantages of cascading  ==
Line 111: Line 106:
*The use of lighter-duty switchgear and appliances, with consequently lower cost  
*The use of lighter-duty switchgear and appliances, with consequently lower cost  
*Economy of space requirements, since light-duty equipment have generally a smaller volume
*Economy of space requirements, since light-duty equipment have generally a smaller volume


== Principles of discriminative tripping (selectivity)  ==
== Principles of discriminative tripping (selectivity)  ==
Line 119: Line 115:
|}
|}


Discrimination is achieved by automatic protective devices if a fault condition, occurring at any point in the installation, is cleared by the protective device located immediately upstream of the fault, while all other protective devices remain unaffected (see '''Fig. H49''').  
Discrimination (selectivity) is achieved by automatic protective devices if a fault condition, occurring at any point in the installation, is cleared by the protective device located immediately upstream of the fault, while all other protective devices remain unaffected (see '''Fig. H49''').  


----
[[Image:FigH49.jpg|none]]


<br>[[Image:FigH49.jpg|left]] <br><br><br><br><br><br><br><br><br><br><br><br><br><br><br>'''''Fig. H49:''' Total and partial discrimination''  
'''''Fig. H49:''' Total and partial discrimination''  


----


Discrimination between circuit-breakers A and B is total if the maximum value of short-circuit-current on circuit B (Isc B) does not exceed the short-circuit trip setting of circuit-breaker A (Im A). For this condition, B only will trip (see '''Fig. H50''').  
Discrimination between circuit-breakers A and B is total if the maximum value of short-circuit-current on circuit B (Isc B) does not exceed the short-circuit trip setting of circuit-breaker A (Im A). For this condition, B only will trip (see '''Fig. H50''').  


----
[[Image:FigH50.jpg|none]]


<br>[[Image:FigH50.jpg|left]] <br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br>'''''Fig. H50:''' Total discrimination between CBs A and B''  
'''''Fig. H50:''' Total discrimination between CBs A and B''  


----


Discrimination is partial if the maximum possible short-circuit current on circuit B exceeds the short-circuit trip-current setting of circuit-breaker A. For this maximum condition, both A and B will trip (see '''Fig. H51''').  
Discrimination is partial if the maximum possible short-circuit current on circuit B exceeds the short-circuit trip-current setting of circuit-breaker A. For this maximum condition, both A and B will trip (see '''Fig. H51''').  


----
[[Image:FigH51.jpg|none]]
 
'''''Fig. H51:''' Partial discrimination between CBs A and B''


<br>[[Image:FigH51.jpg|left]] <br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br>'''''Fig. H51:''' Partial discrimination between CBs A and B''


----


'''Protection against overload&nbsp;: discrimination based on current levels <br>'''(see '''Fig. H52a''')<br>This method is realized by setting successive tripping thresholds at stepped levels, from downstream relays (lower settings) towards the source (higher settings). Discrimination is total or partial, depending on particular conditions, as noted above.  
'''Protection against overload&nbsp;: discrimination based on current levels <br>'''(see '''Fig. H52a''')<br>This method is realized by setting successive tripping thresholds at stepped levels, from downstream relays (lower settings) towards the source (higher settings). Discrimination is total or partial, depending on particular conditions, as noted above.  


----
[[Image:FigH52a.jpg|none]]


<br><br>[[Image:FigH52a.jpg|left]] <br><br><br><br><br><br><br><br><br><br><br>'''''Fig. H52a:'''''<i>&nbsp;Discrimination</i>  
'''''Fig. H52a:'''''<i>&nbsp;Discrimination</i>  


----


As a rule of thumb, discrimination is achieved when:'''<br>'''
As a rule of thumb, discrimination is achieved when:'''<br>'''
Line 157: Line 150:
'''Protection against low level short-circuit currents&nbsp;: discrimination based on stepped time delays '''(see '''Fig. H52b''')<br>This method is implemented by adjusting the time-delayed tripping units, such that downstream relays have the shortest operating times, with progressively longer delays towards the source.<br>In the two-level arrangement shown, upstream circuit-breaker A is delayed sufficiently to ensure total discrimination with B (for example: Masterpact with electronic trip unit).  
'''Protection against low level short-circuit currents&nbsp;: discrimination based on stepped time delays '''(see '''Fig. H52b''')<br>This method is implemented by adjusting the time-delayed tripping units, such that downstream relays have the shortest operating times, with progressively longer delays towards the source.<br>In the two-level arrangement shown, upstream circuit-breaker A is delayed sufficiently to ensure total discrimination with B (for example: Masterpact with electronic trip unit).  


----


<br>[[Image:FigH52b.jpg|left]] <br><br><br><br><br><br><br><br><br><br><br><br>'''''Fig. H52b:''' Discrimination''  
[[Image:FigH52b.jpg|none]]
 
'''''Fig. H52b:''' Discrimination''  


----


'''Discrimination based on a combination of the two previous methods''' (see '''Fig. H52c''')<br>A time-delay added to a current level scheme can improve the overall discrimination performance.<br>The upstream CB has two high-speed magnetic tripping thresholds:  
'''Discrimination based on a combination of the two previous methods''' (see '''Fig. H52c''')<br>A time-delay added to a current level scheme can improve the overall discrimination performance.<br>The upstream CB has two high-speed magnetic tripping thresholds:  
Line 170: Line 163:
Discrimination is total if Isc B &lt; Ii (instantaneous).  
Discrimination is total if Isc B &lt; Ii (instantaneous).  


----


<br>[[Image:FigH52c.jpg|left]] <br><br><br><br><br><br><br><br><br><br><br>'''''Fig. H52c:''' Discrimination''  
[[Image:FigH52c.jpg|none]]
 
'''''Fig. H52c:''' Discrimination''  


----


'''Protection against high level short-circuit currents: discrimination based on arc-energy levels'''<br>This technology implemented in the Compact NSX range (current limiting circuit- breaker) is extremely effective for achievement of total discrimination.<br>Principle: When a very high level short-circuit current is detected by the two circuits- breaker A and B, their contacts open simultaneously. As a result, the current is highly limited.  
'''Protection against high level short-circuit currents: discrimination based on arc-energy levels'''<br>This technology implemented in the Compact NSX range (current limiting circuit- breaker) is extremely effective for achievement of total discrimination.<br>Principle: When a very high level short-circuit current is detected by the two circuits- breaker A and B, their contacts open simultaneously. As a result, the current is highly limited.  
Line 182: Line 175:


As a rule of thumb, the discrimination between Compact NSX is total if the size ratio between A and B is greater than 2.5.'''<br>'''
As a rule of thumb, the discrimination between Compact NSX is total if the size ratio between A and B is greater than 2.5.'''<br>'''


== Current-level discrimination<br> ==
== Current-level discrimination<br> ==
Line 187: Line 181:
This technique is directly linked to the staging of the Long Time (LT) tripping curves of two serial-connected circuit-breakers.  
This technique is directly linked to the staging of the Long Time (LT) tripping curves of two serial-connected circuit-breakers.  


----


<br>[[Image:FigH53.jpg|left]] <br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br>'''''Fig. H53:''' Current discrimination''  
[[Image:FigH53.jpg|none]]
 
'''''Fig. H53:''' Current discrimination''  


----


The discrimination limit ls is:  
The discrimination limit ls is:  
Line 216: Line 210:


|}
|}


== Time discrimination  ==
== Time discrimination  ==
Line 226: Line 221:
This is the extension of current discrimination and is obtained by staging over time of the tripping curves. This technique consists of giving a time delay of t to the Short Time (ST) tripping of D1.  
This is the extension of current discrimination and is obtained by staging over time of the tripping curves. This technique consists of giving a time delay of t to the Short Time (ST) tripping of D1.  


----


<br>[[Image:FigH54.jpg|left]] <br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br>
[[Image:FigH54.jpg|none]]


'''''Fig. H54: '''Time discrimination''  
'''''Fig. H54: '''Time discrimination''  


----


The thresholds (Ir1, Isd1) of D1 and (Ir2, Isd2) comply with the staging rules of current discrimination. <br>The discrimination limit ls of the association is at least equal to li1, the instantaneous threshold of D1.  
The thresholds (Ir1, Isd1) of D1 and (Ir2, Isd2) comply with the staging rules of current discrimination. <br>The discrimination limit ls of the association is at least equal to li1, the instantaneous threshold of D1.  
Line 241: Line 234:
'''Discrimination quality'''<br>
'''Discrimination quality'''<br>


There are two possible applications:
*'''on final and/or intermediate feeders'''
*'''on final and/or intermediate feeders'''


Line 251: Line 245:
|}
|}


Note: Use of B category circuit-breakers means that the installation must withstand high electrodynamic and thermal stresses.<br>Consequently, these circuit-breakers have a high instantaneous threshold li that can be adjusted and disabled in order to protect the busbars if necessary.  
'''Note:''' Use of B category circuit-breakers means that the installation must withstand high electrodynamic and thermal stresses.<br>Consequently, these circuit-breakers have a high instantaneous threshold li that can be adjusted and disabled in order to protect the busbars if necessary.  


'''Practical example of discrimination at several levels with Schneider Electric circuit-breakers (with electronic trip units)'''<br>"Masterpact NT is totally selective with any moulded-case Compact NSX circuit breaker, i.e., the downstream circuit-breaker will trip for any short-circuit value up to its breaking capacity. Further, all Compact NSX CBs are totally selective, as long as the ration between sizes is greater than 1.6 and the ratio between ratings is greater than 2.5. The same rules apply for the total selectivity with the miniature circuit-breakers Multi9 further downstream (see '''Fig. H55''').  
'''Practical example of discrimination at several levels with Schneider Electric circuit-breakers (with electronic trip units)'''<br>"Masterpact NT is totally selective with any moulded-case Compact NSX circuit breaker, i.e., the downstream circuit-breaker will trip for any short-circuit value up to its breaking capacity. Further, all Compact NSX CBs are totally selective, as long as the ration between sizes is greater than 1.6 and the ratio between ratings is greater than 2.5. The same rules apply for the total selectivity with the miniature circuit-breakers Acti-9 further downstream (see '''Fig. H55''').  


----


<br>[[Image:Schema pH26.jpg|left]]  
[[Image:Schema pH26.jpg]] &nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp; [[Image:FigH55.jpg]]  


<br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br>
'''''Fig. H55: '''4 level discrimination with Schneider Electric circuit breakers : Masterpact NT, Compact NSX and Acti 9''


----
<br>
[[Image:FigH55.jpg|left]]
<br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br>'''''Fig. H55: '''4 level discrimination with Schneider Electric circuit breakers&nbsp;: Masterpact NT Compact NSX and Multi 9''
----


== Energy discrimination with current limitation  ==
== Energy discrimination with current limitation  ==
Line 277: Line 261:
*The downstream limiting circuit-breaker B sees a very high short-circuit current. The tripping is very fast (&lt;1 ms) and then, the current is limited  
*The downstream limiting circuit-breaker B sees a very high short-circuit current. The tripping is very fast (&lt;1 ms) and then, the current is limited  
*The upstream circuit-breaker A sees a limited short-circuit current compared to its breaking capability, but this current induces a repulsion of the contacts. As a result, the arcing voltage increases the current limitation. However, the arc energy is not high enough to induce the tripping of the circuit-breaker. So, the circuit-breaker A helps the circuit-breaker B to trip, without tripping itself. The discrimination limit can be higher than Icu B and the discrimination becomes total with a reduced cost of the devices
*The upstream circuit-breaker A sees a limited short-circuit current compared to its breaking capability, but this current induces a repulsion of the contacts. As a result, the arcing voltage increases the current limitation. However, the arc energy is not high enough to induce the tripping of the circuit-breaker. So, the circuit-breaker A helps the circuit-breaker B to trip, without tripping itself. The discrimination limit can be higher than Icu B and the discrimination becomes total with a reduced cost of the devices


== Natural total discriminitation with Compact NSX  ==
== Natural total discriminitation with Compact NSX  ==
Line 284: Line 269:
*The ratio of the two trip-unit current ratings is &gt; 1.6  
*The ratio of the two trip-unit current ratings is &gt; 1.6  
*The ratio of rated currents of the two circuit-breakers is &gt; 2.5
*The ratio of rated currents of the two circuit-breakers is &gt; 2.5


== Logic discrimination or “Zone Sequence Interlocking – ZSI”  ==
== Logic discrimination or “Zone Sequence Interlocking – ZSI”  ==
Line 297: Line 283:
*thresholds: there are no threshold rules to be applied, but natural staging of the protection device ratings must be complied with (IcrD1 ≥ IcrD2 ≥ IcrD3).
*thresholds: there are no threshold rules to be applied, but natural staging of the protection device ratings must be complied with (IcrD1 ≥ IcrD2 ≥ IcrD3).


Note: This technique ensures discrimination even with circuit-breakers of similar ratings.  
'''Note:''' This technique ensures discrimination even with circuit-breakers of similar ratings.  
 


== Principles  ==
== Principles  ==
Line 310: Line 297:


&nbsp; - low level: the trip unit detects no faults and sends no orders,<br>&nbsp; - high level: the trip unit detects a fault and sends an order.  
&nbsp; - low level: the trip unit detects no faults and sends no orders,<br>&nbsp; - high level: the trip unit detects a fault and sends an order.  


== Operation  ==
== Operation  ==
Line 315: Line 303:
A pilot wire connects in cascading form the protection devices of an installation (see '''Fig. H56'''). '''When a fault occurs, each circuit-breaker '''upstream of the fault (detecting a fault) sends an order (high level output) and moves the upstream circuit-breaker to its natural time delay (high level input). The circuitbreaker placed just above the fault does not receive any orders (low level input) and thus trips almost instantaneously.  
A pilot wire connects in cascading form the protection devices of an installation (see '''Fig. H56'''). '''When a fault occurs, each circuit-breaker '''upstream of the fault (detecting a fault) sends an order (high level output) and moves the upstream circuit-breaker to its natural time delay (high level input). The circuitbreaker placed just above the fault does not receive any orders (low level input) and thus trips almost instantaneously.  


----


<br>[[Image:Fig H56.jpg|left]] <br><br><br><br><br><br><br><br><br><br><br><br><br><br><br>
[[Image:Fig H56.jpg|none]]


'''''Fig. H56:''' Logic discrimination.''  
'''''Fig. H56:''' Logic discrimination.''  


----


{| style="width: 805px; height: 28px" cellspacing="1" cellpadding="1" width="805" border="1"
{| style="width: 805px; height: 28px" cellspacing="1" cellpadding="1" width="805" border="1"
Line 335: Line 321:
|}
|}


<br>


[[ru:Согласование характеристик автоматических выключателей]]
[[ru:Согласование характеристик автоматических выключателей]]
[[zh:断路器间的配合]]
[[zh:断路器间的配合]]

Revision as of 12:14, 20 August 2013


Cascading (or Back-up protection)

The technique of “cascading” uses the properties of current-limiting circuit-breakers to permit the installation of all downstream switchgear, cables and other circuit components of significantly lower performance than would otherwise be necessary, thereby simplifying and reducing the cost of an installation

Definition of the cascading technique
By limiting the peak value of short-circuit current passing through it, a current-limiting CB permits the use, in all circuits downstream of its location, of switchgear and circuit components having much lower short-circuit breaking capacities, and thermal and electromechanical withstand capabilities than would otherwise be necessary. Reduced physical size and lower performance requirements lead to substantial economy and to the simplification of installation work. It may be noted that, while a current-limiting circuit-breaker has the effect on downstream circuits of (apparently) increasing the source impedance during short-circuit conditions, it has no such effect in any other condition; for example, during the starting of a large motor (where a low source impedance is highly desirable). The range of Compact NSX current-limiting circuit-breakers with powerful limiting performances is particularly interesting.


Conditions of implementation

In general, laboratory tests are necessary to ensure that the conditions of implementation required by national standards are met and compatible switchgear combinations must be provided by the manufacturer

Most national standards admit the cascading technique, on condition that the amount of energy “let through” by the limiting CB is less than the energy all downstream CBs and components are able to withstand without damage.
In practice this can only be verified for CBs by tests performed in a laboratory. Such tests are carried out by manufacturers who provide the information in the form of tables, so that users can confidently design a cascading scheme based on the combination of recommended circuit-breaker types. As an example, Figure H48 indicates the cascading possibilities of circuit-breaker types iC60, DT40N, C120 and NG125 when installed downstream of current-limiting CBs Compact NSX 250 N, H or L for a 230/400 V or 240/415 V 3-phase installation.


kArms
Short-circuit breaking capacity of the upstream (limiter) CBs 150        NSX250L
70   NSX250H  
50 NSX250N    
 
Fleche.jpg
Fleche.jpg
Fleche.jpg
                    
Possible short-circuit breaking capacity of the downstream CBs (benefiting from the cascading technique) 150      NG125L
70   NG125L  
36 NG125N NG125N  
30 iC60N/H<=32A iC60N/H<=32A iC60N/H<=32A
30 iC60L<=25A iC60L<=25A(*)
Quick PRD
40/20/8
iC60L<=25A
25 iC60H>=40A
C120N/H
iC60H>=40A
C120N/H
iC60H>=40A
C120N/H
20 iC60N>=40A iC60N>=40A iC60N>=40A

Fig. H48: Example of cascading possibilities on a 230/400 V or 240/415 V 3-phase installation


Advantages of cascading

The current limitation benefits all downstream circuits that are controlled by the current-limiting CB concerned.
The principle is not restrictive, i.e. current-limiting CBs can be installed at any point in an installation where the downstream circuits would otherwise be inadequately rated.
The result is:

  • Simplified short-circuit current calculations
  • Simplification, i.e. a wider choice of downstream switchgear and appliances
  • The use of lighter-duty switchgear and appliances, with consequently lower cost
  • Economy of space requirements, since light-duty equipment have generally a smaller volume


Principles of discriminative tripping (selectivity)

Discrimination may be total or partial, and based on the principles of current levels, or time-delays, or a combination of both. A more recent development is based on the logic techniques.
The Schneider Electric system takes advantages of both current-limitation and discrimination

Discrimination (selectivity) is achieved by automatic protective devices if a fault condition, occurring at any point in the installation, is cleared by the protective device located immediately upstream of the fault, while all other protective devices remain unaffected (see Fig. H49).

FigH49.jpg

Fig. H49: Total and partial discrimination


Discrimination between circuit-breakers A and B is total if the maximum value of short-circuit-current on circuit B (Isc B) does not exceed the short-circuit trip setting of circuit-breaker A (Im A). For this condition, B only will trip (see Fig. H50).

FigH50.jpg

Fig. H50: Total discrimination between CBs A and B


Discrimination is partial if the maximum possible short-circuit current on circuit B exceeds the short-circuit trip-current setting of circuit-breaker A. For this maximum condition, both A and B will trip (see Fig. H51).

FigH51.jpg

Fig. H51: Partial discrimination between CBs A and B


Protection against overload : discrimination based on current levels
(see Fig. H52a)
This method is realized by setting successive tripping thresholds at stepped levels, from downstream relays (lower settings) towards the source (higher settings). Discrimination is total or partial, depending on particular conditions, as noted above.

FigH52a.jpg

Fig. H52a: Discrimination


As a rule of thumb, discrimination is achieved when:

  • IrA/IrB > 2:

Protection against low level short-circuit currents : discrimination based on stepped time delays (see Fig. H52b)
This method is implemented by adjusting the time-delayed tripping units, such that downstream relays have the shortest operating times, with progressively longer delays towards the source.
In the two-level arrangement shown, upstream circuit-breaker A is delayed sufficiently to ensure total discrimination with B (for example: Masterpact with electronic trip unit).


FigH52b.jpg

Fig. H52b: Discrimination


Discrimination based on a combination of the two previous methods (see Fig. H52c)
A time-delay added to a current level scheme can improve the overall discrimination performance.
The upstream CB has two high-speed magnetic tripping thresholds:

  • Im A: delayed magnetic trip or short-delay electronic trip
  • Ii: instantaneous strip

Discrimination is total if Isc B < Ii (instantaneous).


FigH52c.jpg

Fig. H52c: Discrimination


Protection against high level short-circuit currents: discrimination based on arc-energy levels
This technology implemented in the Compact NSX range (current limiting circuit- breaker) is extremely effective for achievement of total discrimination.
Principle: When a very high level short-circuit current is detected by the two circuits- breaker A and B, their contacts open simultaneously. As a result, the current is highly limited.

  • The very high arc-energy at level B induces the tripping of circuit-breaker B
  • Then, the arc-energy is limited at level A and is not sufficient to induce the tripping of A

As a rule of thumb, the discrimination between Compact NSX is total if the size ratio between A and B is greater than 2.5.


Current-level discrimination

This technique is directly linked to the staging of the Long Time (LT) tripping curves of two serial-connected circuit-breakers.


FigH53.jpg

Fig. H53: Current discrimination


The discrimination limit ls is:

  • Is = Isd2 if the thresholds lsd1 and lsd2 are too close or merge,
  • Is = Isd1 if the thresholds lsd1 and lsd2 are sufficiently far apart.

As a rule, current discrimination is achieved when:

  • Ir1 / Ir2 < 2,
  • Isd1 / Isd2 > 2.

The discrimination limit is:

  • Is = Isd1.
Discrimination quality
Discrimination is total if Is > Isc(D2), i.e. Isd1 > Isc(D2).
This normally implies:
  • a relatively low level Isc(D2),
  • a large difference between the ratings of circuit-breakers D1 and D2.

Current discrimination is normally used in final distribution.


Time discrimination

Discrimination based on time-delayed tripping uses CBs referred to as “selective” (in some countries).
Implementation of these CBs is relatively simple and consists in delaying the instant of tripping of the several series-connected circuit-breakers in a stepped time sequence

This is the extension of current discrimination and is obtained by staging over time of the tripping curves. This technique consists of giving a time delay of t to the Short Time (ST) tripping of D1.


FigH54.jpg

Fig. H54: Time discrimination


The thresholds (Ir1, Isd1) of D1 and (Ir2, Isd2) comply with the staging rules of current discrimination.
The discrimination limit ls of the association is at least equal to li1, the instantaneous threshold of D1.

Discrimination quality

There are two possible applications:

  • on final and/or intermediate feeders

A category circuit-breakers can be used with time-delayed tripping of the upstream circuit-breaker. This allows extension of current discrimination up to the instantaneous threshold li1 of the upstream circuit-breaker: Is = li1.
If Isc(D2) is not too high - case of a final feeder - total discrimination can be obtained.

  • on the incomers and feeders of the MSB

At this level, as continuity of supply takes priority, the installation characteristics allow use of B category circuit-breakers designed for time-delayed tripping. These circuit-breakers have a high thermal withstand (Icw ≥ 50% Icn for t = 1s): Is = Icw1.
Even for high lsc(D2), time discrimination normally provides total discrimination: Icw1 > Icc(D2).

Note: Use of B category circuit-breakers means that the installation must withstand high electrodynamic and thermal stresses.
Consequently, these circuit-breakers have a high instantaneous threshold li that can be adjusted and disabled in order to protect the busbars if necessary.

Practical example of discrimination at several levels with Schneider Electric circuit-breakers (with electronic trip units)
"Masterpact NT is totally selective with any moulded-case Compact NSX circuit breaker, i.e., the downstream circuit-breaker will trip for any short-circuit value up to its breaking capacity. Further, all Compact NSX CBs are totally selective, as long as the ration between sizes is greater than 1.6 and the ratio between ratings is greater than 2.5. The same rules apply for the total selectivity with the miniature circuit-breakers Acti-9 further downstream (see Fig. H55).


Schema pH26.jpg               FigH55.jpg

Fig. H55: 4 level discrimination with Schneider Electric circuit breakers : Masterpact NT, Compact NSX and Acti 9


Energy discrimination with current limitation

Cascading between 2 devices is normally achieved by using the tripping of the upstream circuit-breaker A to help the downstream circuit-breaker B to break the current. The discrimination limit Is is consequently equal to the ultimate breaking current Icu B of circuit-breaker B acting alone, as cascading requires the tripping of both devices.
The energy discrimination technology implemented in Compact NSX circuit-breakers allows to improve the discrimination limit to a value higher than the ultimate breaking current Icu B of the downstream circuit-breaker. The principle is as follows:

  • The downstream limiting circuit-breaker B sees a very high short-circuit current. The tripping is very fast (<1 ms) and then, the current is limited
  • The upstream circuit-breaker A sees a limited short-circuit current compared to its breaking capability, but this current induces a repulsion of the contacts. As a result, the arcing voltage increases the current limitation. However, the arc energy is not high enough to induce the tripping of the circuit-breaker. So, the circuit-breaker A helps the circuit-breaker B to trip, without tripping itself. The discrimination limit can be higher than Icu B and the discrimination becomes total with a reduced cost of the devices


Natural total discriminitation with Compact NSX

The major advantage of the Compact NSX range is to provide a natural total discrimination between two series-connected devices if:

  • The ratio of the two trip-unit current ratings is > 1.6
  • The ratio of rated currents of the two circuit-breakers is > 2.5


Logic discrimination or “Zone Sequence Interlocking – ZSI”

Discrimination schemes based on logic techniques are possible, using CBs equipped with electronic tripping units designed for the purpose (Compact, Masterpact) and interconnected with pilot wires

This type of discrimination can be achieved with circuit-breakers equipped with specially designed electronic trip units (Compact, Masterpact): only the Short Time Protection (STP) and Ground Fault Protection (GFP) functions of the controlled devices are managed by Logic Discrimination. In particular, the Instantaneous Protection function - inherent protection function - is not concerned.
Settings of controlled circuit-breakers

  • time delay: there are no rules, but staging (if any)of the time delays of time discrimination must be applied (ΔtD1 ≥ ΔtD2 ≥ ΔtD3),
  • thresholds: there are no threshold rules to be applied, but natural staging of the protection device ratings must be complied with (IcrD1 ≥ IcrD2 ≥ IcrD3).

Note: This technique ensures discrimination even with circuit-breakers of similar ratings.


Principles

Activation of the Logic Discrimination function is via transmission of information on the pilot wire:

  • ZSI input:

  - low level (no downstream faults): the Protection function is on standby with a reduced time delay (y 0,1 s),
  - high level (presence of downstream faults): the relevant Protection function moves to the time delay status set on the device.

  • ZSI output:

  - low level: the trip unit detects no faults and sends no orders,
  - high level: the trip unit detects a fault and sends an order.


Operation

A pilot wire connects in cascading form the protection devices of an installation (see Fig. H56). When a fault occurs, each circuit-breaker upstream of the fault (detecting a fault) sends an order (high level output) and moves the upstream circuit-breaker to its natural time delay (high level input). The circuitbreaker placed just above the fault does not receive any orders (low level input) and thus trips almost instantaneously.


Fig H56.jpg

Fig. H56: Logic discrimination.


Discrimination quality
This technique enables:
  • easy achievement as standard of discrimination on 3 levels or more,
  • elimination of important stresses on the installation, relating to time-delayed tripping of the protection device, in event of a fault directly on the upstream busbars.

All the protection devices are thus virtually instantaneous,

  • easy achievement of downstream discrimination with non-controlled circuit-breakers.


ru:Согласование характеристик автоматических выключателей zh:断路器间的配合