== Grid connected PV system <= 10kW (Residential) ==
== Grid connected PV system &lt;= 10kW (Residential) ==


===One single phase inverter===
=== One single phase inverter ===


* Typically, a 5kW grid-connected single-phase inverter. with UOC MAX  600V.  
*Typically, a 5kW grid-connected single-phase inverter. with UOC MAX  600V.  
* One or two strings – Isctc < 25A, IAC < 32A.  
*One or two strings – Isctc &lt; 25A, IAC &lt; 32A.  
* In this design there is no string protection.
*In this design there is no string protection.  
* A PV main switch is necessary. When the inverter is indoors, an additional remote controlled switch at the DC cable entry point is recommended for emergencies services.
*A PV main switch is necessary. When the inverter is indoors, an additional remote controlled switch at the DC cable entry point is recommended for emergencies services.


[[File:Fig P22.png|none]]
[[Image:Fig P22.png|none|Fig P22.png]]  


{| width="800" border="1" cellpadding="1" cellspacing="1"
|-
| bgcolor="#D1E9D4" | '''Needs''' || String junction box || PV array main switch || Inverter || AC box (400V)
|-
| bgcolor="#79C68C" colspan="4"| '''Switchgears and control'''
|-
| bgcolor="#79C68C" |
:Isolation || • || • (d) || (a) || • (d)
|-
| bgcolor="#79C68C" |
:Switching<br>(Making & breaking<br>rated current || •<br>DC21B || (a) || • (d) ||
|-
| bgcolor="#79C68C" |
:Control || • (b) || • (d) || (e) || • (d)
|-
| bgcolor="#79C68C" |
:Over-current protection || (c) ||  ||  ||
|-
| bgcolor="#79C68C" |
:Protection against<br>Insulation fault ||  ||  || (h) || (h)<br>RCD type B or A SI
|-
| bgcolor="#A6D6AE" | '''Surge protection''' ||  || • type 2 ||  || • type 1 or 2
|-
| bgcolor="#D1D3D4" | Enclosure || Outdoor IP5x<br>Double insulation || Indoor IP5x<br>Double insulation || || Standard AC requirement +<br>grid code requirement
|}


'''''Fig. P23 :''''' '''10-100kW single multi MPPT inverter'''
<br> '''''Fig. P23&nbsp;:''''' '''10-100kW single multi MPPT inverter'''

Revision as of 14:59, 16 October 2013

Grid connected PV system <= 10kW (Residential)

One single phase inverter

  • Typically, a 5kW grid-connected single-phase inverter. with UOC MAX  600V.
  • One or two strings – Isctc < 25A, IAC < 32A.
  • In this design there is no string protection.
  • A PV main switch is necessary. When the inverter is indoors, an additional remote controlled switch at the DC cable entry point is recommended for emergencies services.
Fig P22.png
Needs String junction box PV array main switch Inverter AC box (400V)
Switchgears and control
Isolation || • || • (d) || (a) || • (d)
Switching
(Making & breaking
rated current || •
DC21B || (a) || • (d) ||
Control || • (b) || • (d) || (e) || • (d)
Over-current protection || (c) || || ||
Protection against
Insulation fault || || || (h) || (h)
RCD type B or A SI
Surge protection • type 2 • type 1 or 2
Enclosure Outdoor IP5x
Double insulation
Indoor IP5x
Double insulation
Standard AC requirement +
grid code requirement


Fig. P23 : 10-100kW single multi MPPT inverter

Share