Main characteristics to consider to determine the transformation substations:  
Main characteristics to consider to determine the transformation substations:  
Line 18: Line 18:
<br>
<br>


{| style="width: 65%; height: 93px" cellspacing="1" cellpadding="1" border="1"
{| class="wikitable" style="width: 65%; height: 93px"
|-
|-
| &nbsp;  
| &nbsp;  
| bgcolor="#0099cc" colspan="3" | '''Configuration'''
! colspan="3" | Configuration
|-
|-
| valign="top" bgcolor="#0099cc" | '''Characteristic to consider'''
! Characteristic to consider  
| bgcolor="#0099cc" | '''1 substation with<br>N transformers'''
! 1 substation with<br>N transformers  
| bgcolor="#0099cc" | '''N substations<br>N transformers (identical substations)'''
! N substations<br>N transformers (identical substations)  
| bgcolor="#0099cc" | '''N substations<br>M transformers (different powers)'''
! N substations<br>M transformers (different powers)
|-
|-
| valign="top" | Building configuration  
| Building configuration  
| valign="top" | &lt; 25000m²  
| &lt; 25000m²  
| valign="top" | ≥ 25000m²<br>1 building with several floors  
| ≥ 25000m²<br>1 building with several floors  
| valign="top" | ≥ 25000m²<br>several buildings
| ≥ 25000m²<br>several buildings
|-
|-
| Power demand  
| Power demand  

Revision as of 13:10, 15 November 2013


Main characteristics to consider to determine the transformation substations:

  • Surface area of building or site
  • Power demand, (to be compared with standardized transformer power),
  • Load distribution

The preferred basic configuration comprises one single substation.Certain factors contribute to increasing the number of substations (>1):

  • A large surface area (> 25000m²),
  • The site configuration: several buildings,
  • Total power > 2500kVA,
  • Sensitivity to interruption: need for redundancy in the case of a fire.


  Configuration
Characteristic to consider 1 substation with
N transformers
N substations
N transformers (identical substations)
N substations
M transformers (different powers)
Building configuration < 25000m² ≥ 25000m²
1 building with several floors
≥ 25000m²
several buildings
Power demand < 2500kVA ≥ 2500kVA ≥ 2500kVA
Load distribution Localized loads Uniform distribution Medium density

Fig. D11: Typical characteristics of the different configurations