Form factors of RCDs: Difference between revisions
(updated new image sizes FigF66 - also F64 and F65 for coherence (book 2013)) |
(cleaned up source: table format, etc ...) |
||
Line 13: | Line 13: | ||
== Industrial type circuit-breakers with integrated or adaptable RCD | == Industrial type circuit-breakers with integrated or adaptable RCD module == | ||
(see '''Fig. F64''') | (see '''Fig. F64''') | ||
{| | {{Highlightbox| | ||
Industrial circuit-breakers with an integrated RCD are covered in IEC 60947-2 and its appendix B | |||
}} | |||
[[File:FigF64a_2013.jpg]] [[File:FigF64b_2013.jpg|x200px]][[File:FigF64c_2013.jpg|x220px]] | |||
Industrial type circuit- Acti 9 DIN-rail industrial <br>breaker Vigi Compact Circuit-breaker with adaptable Vigi RCD module | Industrial type circuit- Acti 9 DIN-rail industrial <br>breaker Vigi Compact Circuit-breaker with adaptable Vigi RCD module | ||
Line 35: | Line 34: | ||
(see '''Fig. F65''') | (see '''Fig. F65''') | ||
{| | {{Highlightbox| | ||
Household or domestic circuit-breakers with an integrated RCD are covered in IEC 60898, IEC 61008 and IEC 61009 | |||
}} | |||
[[ | [[File:FigF65a_2013.jpg|x300px]] [[File:FigF65b_2013.jpg|x200px]] | ||
The incoming-supply “Monobloc” Déclic Vigi residual<br>circuit-breaker can current circuit-breakers intended <br>also have time-delayed for protection of terminal socket-outlet<br>characteristics and circuits in domestic and tertiary <br>integrate a RCD sector applications.<br>(type S). | The incoming-supply “Monobloc” Déclic Vigi residual<br>circuit-breaker can current circuit-breakers intended <br>also have time-delayed for protection of terminal socket-outlet<br>characteristics and circuits in domestic and tertiary <br>integrate a RCD sector applications.<br>(type S). | ||
Line 51: | Line 49: | ||
(see '''Fig. F66''') | (see '''Fig. F66''') | ||
{| | {{Highlightbox| | ||
Residual current load break switches are covered by particular national standards.RCDs with separate toroidal current transformers are standardized in IEC 60947-2 appendix M | |||
}} | |||
RCDs with separate toroidal CTs can be used in association with circuit-breakers or contactors. | RCDs with separate toroidal CTs can be used in association with circuit-breakers or contactors. | ||
[[ | [[File:FigF66a_2013.jpg|x100px]] [[File:FigF66b_2013.jpg|x200px]] | ||
'''''Fig. F66:''' RCDs with separate toroidal current transformers (Vigirex)'' | '''''Fig. F66:''' RCDs with separate toroidal current transformers (Vigirex)'' |
Revision as of 13:10, 15 November 2013
Residual current devices (RCD) are commonly incorporated in or associated with the following components:
- Industrial-type moulded-case circuit-breakers (MCCB) and air circuit-breakers (ACB) conforming to IEC 60947-2 and its appendix B and M
- Industrial type miniature circuit-breakers (MCB) conforming to IEC 60947-2 and its appendix B and M
- Household and similar miniature circuit-breakers (MCB) complying with IEC 60898, IEC 61008, IEC 61009
- Residual load switch conforming to particular national standards
- Relays with separate toroidal (ring-type) current transformers, conforming to IEC 60947-2 Appendix M
RCDs are mandatorily used at the origin of TT-earthed installations, where their ability to discriminate with other RCDs allows selective tripping, thereby ensuring the level of service continuity required.
Industrial type circuit-breakers with integrated or adaptable RCD module
(see Fig. F64)
Industrial circuit-breakers with an integrated RCD are covered in IEC 60947-2 and its appendix B
Industrial type circuit- Acti 9 DIN-rail industrial
breaker Vigi Compact Circuit-breaker with adaptable Vigi RCD module
Fig. F64: Industrial-type CB with RCD module
Adaptable residual current circuit-breakers, including DIN-rail mounted units (e.g. Compact or Acti 9), are available, to which may be associated an auxiliary RCD module (e.g. Vigi).
The ensemble provides a comprehensive range of protective functions (isolation, protection against short-circuit, overload, and earth-fault.
Household and similar miniature circuit-breakers with RCD
(see Fig. F65)
Household or domestic circuit-breakers with an integrated RCD are covered in IEC 60898, IEC 61008 and IEC 61009
The incoming-supply “Monobloc” Déclic Vigi residual
circuit-breaker can current circuit-breakers intended
also have time-delayed for protection of terminal socket-outlet
characteristics and circuits in domestic and tertiary
integrate a RCD sector applications.
(type S).
Fig. F65: Domestic residual current circuit-breakers (RCCBs) for earth leakage protection
Residual current circuit-breakers and RCDs with separate toroidal current transformer
(see Fig. F66)
Residual current load break switches are covered by particular national standards.RCDs with separate toroidal current transformers are standardized in IEC 60947-2 appendix M
RCDs with separate toroidal CTs can be used in association with circuit-breakers or contactors.
Fig. F66: RCDs with separate toroidal current transformers (Vigirex)