Motor protection coordination: Difference between revisions
From Electrical Installation Guide
m (r2.7.2) (robot Adding: zh:电动机保护配合) |
m (cleaned up source: table format, etc ...) |
||
Line 9: | Line 9: | ||
<br> | <br> | ||
{| | {| class="wikitable" width="65%" | ||
|- | |- | ||
! Coordination | |||
! Consequence of a short circuit | |||
! Application field | |||
|- | |- | ||
| Type 1 | |||
| The contactor or starter shall cause no danger to persons and installation and may not be suitable for further service without repair and replacement of parts. | |||
| General purpose application. <br>Basic machines. | | General purpose application. <br>Basic machines. | ||
|- | |- | ||
| Type 2 | |||
| The contactor or starter shall cause no danger to persons or installation and shall be suitable for further use. The risk of contact welding is recognized, in which case the manufacturer shall indicate the measures to be taken as regards the maintenance of the equipment. | | The contactor or starter shall cause no danger to persons or installation and shall be suitable for further use. The risk of contact welding is recognized, in which case the manufacturer shall indicate the measures to be taken as regards the maintenance of the equipment. | ||
| valign="middle" rowspan="2" | Process with availability constraints, e.g.: continuous process, critical industrial machines. | | valign="middle" rowspan="2" | Process with availability constraints, e.g.: continuous process, critical industrial machines. | ||
|- | |- | ||
| Continuity of service(total coordination) | |||
| No damage or maladjustment is permissible.<br>Must be able to restart immediately after fault is corrected No special precaution is required. | | No damage or maladjustment is permissible.<br>Must be able to restart immediately after fault is corrected No special precaution is required. | ||
|} | |} |
Revision as of 13:10, 15 November 2013
Type 1 and Type 2 coordination are defined in IEC 60947-4-1.
Total coordination is offered by some manufacturers.
Coordination | Consequence of a short circuit | Application field |
---|---|---|
Type 1 | The contactor or starter shall cause no danger to persons and installation and may not be suitable for further service without repair and replacement of parts. | General purpose application. Basic machines. |
Type 2 | The contactor or starter shall cause no danger to persons or installation and shall be suitable for further use. The risk of contact welding is recognized, in which case the manufacturer shall indicate the measures to be taken as regards the maintenance of the equipment. | Process with availability constraints, e.g.: continuous process, critical industrial machines. |
Continuity of service(total coordination) | No damage or maladjustment is permissible. Must be able to restart immediately after fault is corrected No special precaution is required. |
Fig. N69: Level of acceptable destruction according to the coordination types