== Outdoor substation with prefabricated enclosures ==
A prefabricated MV/LV substation complying with IEC 62271-202 standard includes&nbsp;:
*equipment in accordance with IEC standards
*a type tested enclosure, which means during its design, it has undergone a battery of tests (see '''Fig. B24'''):
&nbsp; - Degree of protection<br>&nbsp; -&nbsp;Functional tests<br>&nbsp; - Temperature class&nbsp;<br>&nbsp; - Non-flammable materials<br>&nbsp; - Mechanical resistance of the enclosure<br>&nbsp; - Sound level<br>&nbsp; - Insulation level<br>&nbsp; - Internal arc withstand<br>&nbsp; - Earthing circuit test<br>&nbsp; - Oil retention,… <br>
[[File:FigB24.jpg|none|500px]]
'''''Fig. B24:'''''<i>&nbsp;Type tested substation according to IEC&nbsp;62271-202 standard</i> <br><br>
'''Main benefits are&nbsp;:<br>'''


*Safety:
== Outdoor substations with prefabricated enclosures ==


&nbsp; - For public and operators thanks to a high reproducible quality level


*Cost effective:
The prefabricated outdoor MV/LV substations (see '''Fig. B55)''' comply with IEC 62271-202 standard.


&nbsp; - Manufactured, equipped and tested in the factory
* A type tested prefabricated outdoor substation is subjected to tests and verifications dedicated to:
** The degree of protection
** The temperature class
** The non-flammable materials
** The mechanical resistance of the enclosure
** The sound level
** The insulation level
** The internal arc withstand
** The earthing circuit
** The retention of oil
** The operation of the substation.


*Delivery time
'''Main benefits:'''


&nbsp; - Delivered ready to be connected.<br>
The prefabricated substations provide a particularly interesting and optimized solution regarding:
<br>


'''IEC 62271-202 standard includes four main designs '''(see '''Fig. B25''')
* The delivery time
* The construction works
* The erection works
* The commissioning
* The total cost.


*Walk-in type substation&nbsp;:


&nbsp; - Operation protected from bad weather conditions
'''''Fig. B55:''''' ''Type tested substation according to IEC 62271-202''


*Non walk-in substation
IEC 62271-202 standard defines requirements for two types of outdoor prefabricated substations (see '''Fig. B56):'''


&nbsp; - Ground space savings, and outdoors operations
* Walk-in type substation
* Non walk-in type substation.


*Half buried substation
'''''Fig. B56:''''' ''Walk in and non-walk in type substations''


&nbsp; - Limited visual impact
The substations may be situated at ground level, half buried or completely buried (underground substation), resulting in three types of design (see '''Fig. B57''' and '''Fig. B58''').


*Underground substation
'''''Fig. B57:''''' ''Outdoor substations. The three type of design''


&nbsp; - Blends completely into the environment.<br>
'''''Fig. B58:''''' ''Outdoor substations '''[a]''' Ground level walk in type substation; '''[b]''' Half buried non walk in type substation''


== Outdoor substation without enclosure ==


<br>
(see '''Fig. B59)'''
[[File:FigB25a.jpg|none]]<br>


&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;'''[a]'''&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp; '''[b]'''
This kind of outdoor substations based on weatherproof equipment is commonly used in countries such as UK and India for example.
[[File:FigB25b.jpg|left]]
[[File:FigB25c.jpg|none]]


<br>
These substations are generally included in MV rings and include:
'''''Fig. B25:'''''<i>&nbsp;The four designs according to IEC&nbsp;62271-202 standard and two pictures [a] walk-in type MV/LV substation; [b] half buried type MV/LV substation</i> <br>
<br>


== Outdoor substations without enclosures  ==
* Two functional units dedicated to the connection of the substation to the ring
* One functional unit for the supply and the protection of the MV/LV power transformer generally done by a circuit breaker unit
* One single MV/LV Power transformer
* One LV distribution panel.


(see '''Fig. B26''')<br>
The transformer and the LV panel can be installed in dedicated outdoor type housing.
These kinds of outdoor substation are common in some countries, based on weatherproof equipment exposed to the elements.<br>These substations comprise a fenced area in which three or more concrete plinths are installed for:


*A ring-main unit, or one or more switch-fuse or circuit-breaker unit(s)
'''''Fig. B59:''''' ''Outdoor substation without enclosure''
*One or more transformer(s), and
*One or more LV distribution panel(s).


[[File:FigB26.jpg|none]]
== Pole mounted substation ==


'''''Fig. B26:'''''<i>&nbsp;Outdoor substations without enclosures</i> <br>
'''Application'''


== Pole mounted substations ==
These substations are mainly used for the supply of isolated rural consumers from MV overhead lines.


'''Constitution'''


'''Field of application'''<br>These substations are mainly used to supply isolated rural consumers from MV overhead line distribution systems.<br>
This type of substation includes (see '''Fig. B60):'''


'''Constitution<br>'''In this type of substation, most often, the MV transformer protection is provided by fuses.<br>Lightning arresters are provided, however, to protect the transformer and consumers as shown in '''Figure B27'''.<br>
* A single pole mounted MV/LV power transformer that is, according to the local rules associated or not with:
** A load break switch
** A set of three fuses
** A set of three surge arrestors
* A low voltage circuit breaker
* An earthing electrode realized at the bottom of the pole supporting the equipment.


'''General arrangement of equipment'''<br>As previously noted the location of the substation must allow easy access, not only for personnel but for equipment handling (raising the transformer, for example) and the manœuvring of heavy vehicles. <br>
The location of the substation must allow easy access of the personnel and handling equipment.


[[File:FigB27.jpg|none]]
'''''Fig. B60:''''' ''Pole mounted MV/LV substation''
'''''Fig. B27:'''&nbsp;Pole-mounted ransformer substation''


[[ru:Подстанция наружной установки]]
[[ru:Подстанция наружной установки]]
[[zh:户外型变电站]]
[[zh:户外型变电站]]

Revision as of 10:47, 10 December 2014


Outdoor substations with prefabricated enclosures

The prefabricated outdoor MV/LV substations (see Fig. B55) comply with IEC 62271-202 standard.

  • A type tested prefabricated outdoor substation is subjected to tests and verifications dedicated to:
    • The degree of protection
    • The temperature class
    • The non-flammable materials
    • The mechanical resistance of the enclosure
    • The sound level
    • The insulation level
    • The internal arc withstand
    • The earthing circuit
    • The retention of oil
    • The operation of the substation.

Main benefits:

The prefabricated substations provide a particularly interesting and optimized solution regarding:

  • The delivery time
  • The construction works
  • The erection works
  • The commissioning
  • The total cost.


Fig. B55: Type tested substation according to IEC 62271-202

IEC 62271-202 standard defines requirements for two types of outdoor prefabricated substations (see Fig. B56):

  • Walk-in type substation
  • Non walk-in type substation.

Fig. B56: Walk in and non-walk in type substations

The substations may be situated at ground level, half buried or completely buried (underground substation), resulting in three types of design (see Fig. B57 and Fig. B58).

Fig. B57: Outdoor substations. The three type of design

Fig. B58: Outdoor substations [a] Ground level walk in type substation; [b] Half buried non walk in type substation

Outdoor substation without enclosure

(see Fig. B59)

This kind of outdoor substations based on weatherproof equipment is commonly used in countries such as UK and India for example.

These substations are generally included in MV rings and include:

  • Two functional units dedicated to the connection of the substation to the ring
  • One functional unit for the supply and the protection of the MV/LV power transformer generally done by a circuit breaker unit
  • One single MV/LV Power transformer
  • One LV distribution panel.

The transformer and the LV panel can be installed in dedicated outdoor type housing.

Fig. B59: Outdoor substation without enclosure

Pole mounted substation

Application

These substations are mainly used for the supply of isolated rural consumers from MV overhead lines.

Constitution

This type of substation includes (see Fig. B60):

  • A single pole mounted MV/LV power transformer that is, according to the local rules associated or not with:
    • A load break switch
    • A set of three fuses
    • A set of three surge arrestors
  • A low voltage circuit breaker
  • An earthing electrode realized at the bottom of the pole supporting the equipment.

The location of the substation must allow easy access of the personnel and handling equipment.

Fig. B60: Pole mounted MV/LV substation