MV/LV transformer protection with circuit breaker: Difference between revisions

From Electrical Installation Guide
(creation (guide 2015))
 
(uploaded better version of bitmap images (guide 2015))
Line 14: Line 14:




[[File:Fig_B23_2015.png|none]]
[[File:Fig_B23_2015.png|none|180px]]
'''''Fig. B23:''''' ''VIP 30 self powered relay for basic transformer protection''
'''''Fig. B23:''''' ''VIP 30 self powered relay for basic transformer protection''




[[File:Fig_B24_2015.png|none]]
[[File:Fig_B24_2015.png|none|180px]]
'''''Fig. B24:''''' ''VIP 300 self powered IDMT overcurrent and earth-fault relay''
'''''Fig. B24:''''' ''VIP 300 self powered IDMT overcurrent and earth-fault relay''




[[File:Fig_B25_2015.png|none|800px]]
[[File:Fig_B25_2015.png|none|820px]]
'''''Fig. B25:''''' ''SM6 and Premset switchboards including MV/LV transformer protection with circuit breaker associated to self powered relay''
'''''Fig. B25:''''' ''SM6 and Premset switchboards including MV/LV transformer protection with circuit breaker associated to self powered relay''



Revision as of 07:23, 24 December 2014


MV/LV transformer protection with circuit-breaker is usually used in large Commercial, Industrial and Building applications and especially when the transformer power exceeds 800 kVA. In these applications, switchboards made of modular units provide high flexibility.

The protection chain of each unit may include self powered relays (see Fig. B23 and Fig. B24) bringing a high level of safety and optimized CTs (See Fig. B25).

This solution provides interesting benefits concerning:

  • The maintenance
  • The improvement of protection of the transformer
  • The improvement of the discrimination with the LV installation
  • The insensitivity to the inrush currents
  • The detection of low earth fault currents.


Fig B23 2015.png

Fig. B23: VIP 30 self powered relay for basic transformer protection


Fig B24 2015.png

Fig. B24: VIP 300 self powered IDMT overcurrent and earth-fault relay


Fig B25 2015.png

Fig. B25: SM6 and Premset switchboards including MV/LV transformer protection with circuit breaker associated to self powered relay


Maintenance

Modern protective relays are now almost maintenance free, as they include self testing features. However it remains necessary to check the protection chain at commissioning stage and periodically (every 5 or 10 years).

Protection performance

Circuit breakers combined with electronic protection relays bring many protection selectivity benefits, including:

  • coordination with upstream and downstream devices;
  • discrimination of inrush currents;
  • detection of low level of phase to phase and phase to earth fault currents.

Discrimination with LV installation

In cases where the LV installation includes an incoming LV Air circuit breaker, discrimination with the MV circuit-breaker is easy, as it is possible to choose the right curve in the electronic relay to ensure discrimination between MV and LV protection.

Inrush current

Transformer energizing produces very high transient inrush current that can reach peak values, up to ten times the peak rated current. This is a natural phenomenon and the protection should not operate. The circuit breaker allows high flexibility to avoid tripping current while still maintaining a good level of protection due to the electronic relay time/current characteristic.

Low magnitude phase fault current

MV/LV transformer has usually a very low failure rate. Most of the faults are interturn faults or phase to earth faults. Generally an interturn fault is not cleared early enough. Phase-to-phase faults between MV bushing are of more seldom occurrences (see Fig. B26).

Fig B26 2015.svg

Fig. B26: Localization of a fault

Most common faults are short-circuit inside a turn of the MV winding where the fault level is of low magnitude (1 to 6 times the rated current) (see Fig. B26). In case of circuit breaker, as soon as the fault reaches the setting, the relay will detect it and trip safely the circuit breaker, disconnecting the MV/LV transformer circuit.

High magnitude fault currents

In the rare event of a short-circuit between MV bushings, the protection must act quickly. In that case the circuit breaker is slower than the MV fuse that has current limiting capabilities. However, the circuit breaker will clear the fault in less than 100 ms, and this is effective enough to avoid any serious damages.

Low level MV earth-faults

In case of either high impedance earth fault on MV winding or solid earth-faults in impedance earthed neutral system, the earth fault magnitude is below the rated current of the transformer. Modern self powered relays integrate sensitive earth fault protection and then provide effective coverage on these conditions.

Case of public distribution

In public distribution applications, such as MV ring network configurations, utilities look for the simplest repetitive MV/LV substations that are dispersed in a large geographical area. The power of MV/LV transformer is generally limited to 630 kVA or less. Compact and often non extensible 3 function switchgear are specified by the utilities. In these cases, protection of MV/LV transformers by MV fuses offers an optimized solution (see Fig. B27).

Fig B27 2015.png

Fig. B27: Compact 3 function switchgear