The Surge Protection Device (SPD): Difference between revisions

From Electrical Installation Guide
Home > Overvoltage protection > Principle of lightning protection > The Surge Protection Device (SPD)
(improved format + re-positioned new grey boxes)
*>CleanUpAuto
(clean-up 2016 - imported revision step 20)
Line 7: Line 7:
}}
}}


The Surge Protection Device (SPD) is a component of the electrical installation protection system.<br>This device is connected in parallel on the power supply circuit of the loads that it has to protect (see '''Fig. J17'''). It can also be used at all levels of the power supply network. <br>This is the most commonly used and most efficient type of overvoltage protection.  
The Surge Protection Device (SPD) is a component of the electrical installation protection system.<br>This device is connected in parallel on the power supply circuit of the loads that it has to protect (see {{FigRef|J17}}). It can also be used at all levels of the power supply network. <br>This is the most commonly used and most efficient type of overvoltage protection.  




Line 46: Line 46:
*'''SPD normative definition'''
*'''SPD normative definition'''


{| class="wikitable" style="width: 743px; height: 54px" width="743"
{| class="wikitable"
|-
|-
! &nbsp;
!  
! Direct lightning stroke  
! Direct lightning stroke  
! colspan="2" | Indirect lightning stroke
! colspan="2" | Indirect lightning stroke
Line 85: Line 85:
== Characteristics of SPD  ==
== Characteristics of SPD  ==


International standard IEC 61643-1 Edition 2.0 (03/2005) defines the characteristics and tests for SPD connected to low voltage distribution systems (see '''Fig. J19''').  
International standard IEC 61643-1 Edition 2.0 (03/2005) defines the characteristics and tests for SPD connected to low voltage distribution systems (see {{FigRef|J19}}).  


[[File:Fig J19.jpg|none]]
[[File:Fig J19.jpg|none]]

Revision as of 09:55, 2 December 2016


Surge Protection Devices (SPD) are used for electric power supply networks, telephone networks, and communication and automatic control buses.

The Surge Protection Device (SPD) is a component of the electrical installation protection system.
This device is connected in parallel on the power supply circuit of the loads that it has to protect (see Fig. J17). It can also be used at all levels of the power supply network.
This is the most commonly used and most efficient type of overvoltage protection.


Fig J17 EN.jpg

Fig. J17: Principle of protection system in parallel

SPD connected in parallel has a high impedance. Once the transient overvoltage appears in the system, the impedance of the device decreases so surge current is driven through the SPD, bypassing the sensitive equipment.

Principle
SPD is designed to limit transient overvoltages of atmospheric origin and divert current waves to earth, so as to limit the amplitude of this overvoltage to a value that is not hazardous for the electrical installation and electric switchgear and controlgear.

SPD eliminates overvoltages:

  • in common mode, between phase and neutral or earth;
  • in differential mode, between phase and neutral.

In the event of an overvoltage exceeding the operating threshold, the SPD

  • conducts the energy to earth, in common mode;
  • distributes the energy to the other live conductors, in differential mode.

The three types of SPD:

  • Type 1 SPD

The Type 1 SPD is recommended in the specific case of service-sector and industrial buildings, protected by a lightning protection system or a meshed cage.
It protects electrical installations against direct lightning strokes. It can discharge the back-current from lightning spreading from the earth conductor to the network conductors.
Type 1 SPD is characterized by a 10/350 µs current wave.

  • Type 2 SPD

The Type 2 SPD is the main protection system for all low voltage electrical installations. Installed in each electrical switchboard, it prevents the spread of overvoltages in the electrical installations and protects the loads.
Type 2 SPD is characterized by an 8/20 µs current wave.

  • Type 3 SPD

These SPDs have a low discharge capacity. They must therefore mandatorily be installed as a supplement to Type 2 SPD and in the vicinity of sensitive loads.Type 3 SPD is characterized by a combination of voltage waves (1.2/50 μs) and current waves (8/20 μs).

  • SPD normative definition
Direct lightning stroke Indirect lightning stroke
IEC 61643-1 Class I test Class II test Class III test
IEC 61643-11/2011 Type 1 : Fig J T1.jpg Type 2 :  Fig J T2.jpg Type 3 :  Fig J T3.jpg
EN/IEC 61643-11 Type 1 Type 2 Type 3
Former VDE 0675v B C D
Type of test wave 10/350 8/20 1.2/50 + 8/20

Note 1: There exist Fig J T1.jpg   +  Fig J T2.jpg SPD (or Type 1 + 2 SPD) combining protection of loads against direct and indirect lightning strokes.
Note 2: some Fig J T2.jpg SPD can also be declared as Fig J T3.jpg.

Fig. J18: SPD standard definition


Characteristics of SPD

International standard IEC 61643-1 Edition 2.0 (03/2005) defines the characteristics and tests for SPD connected to low voltage distribution systems (see Fig. J19).

Fig J19.jpg

    In green, the guaranteed
    operating range of the SPD.

Fig. J19: Time/current characteristic of a SPD with varistor


Common characteristics

  • Uc: Maximum continuous operating voltage

This is the A.C. or D.C. voltage above which the SPD becomes active. This value is chosen according to the rated voltage and the system earthing arrangement.

  • Up: Voltage protection level (at In)

This is the maximum voltage across the terminals of the SPD when it is active. This voltage is reached when the current flowing in the SPD is equal to In. The voltage protection level chosen must be below the overvoltage withstand capability of the loads. In the event of lightning strokes, the voltage across the terminals of the SPD generally remains less than Up.

  • In: Nominal discharge current

This is the peak value of a current of 8/20 µs waveform that the SPD is capable of discharging minimum 20 times.

Why is In important?
In corresponds to a nominal discharge current that a SPD can withstand at least 20 times: a higher value of In means a longer life for the SPD, so it is strongly recommended to chose higher values than the minimum imposed value of 5 kA.

Type 1 SPD

  • Iimp: Impulse current

This is the peak value of a current of 10/350 µs waveform that the SPD is capable of discharging 5 times.

Why is Iimp important?
IEC 62305 standard requires a maximum impulse current value of 25 kA per pole for three-phase system. This means that for a 3P+N network the SPD should be able to withstand a total maximum impulse current of 100kA coming from the earth bonding.

  • Ifi: Autoextinguish follow current

Applicable only to the spark gap technology. This is the current (50 Hz) that the SPD is capable of interrupting by itself after flashover. This current must always be greater than the prospective short-circuit current at the point of installation.

Type 2 SPD

  • Imax: Maximum discharge current

This is the peak value of a current of 8/20 µs waveform that the SPD is capable of discharging once.

Why is Imax important?
If you compare 2 SPDs with the same In, but with different Imax: the SPD with higher Imax value has a higher "safety margin" and can withstand higher surge current without being damaged.

Type 3 SPD

  • Uoc: Open-circuit voltage applied during class III (Type 3) tests.


Main applications

  • Low Voltage SPD

Very different devices, from both a technological and usage viewpoint, are designated by this term. Low voltage SPDs are modular to be easily installed inside LV switchboards.
There are also SPDs adaptable to power sockets, but these devices have a low discharge capacity.

  • SPD for communication networks

These devices protect telephon networks, switched networks and automatic control networks (bus) against overvoltages coming from outside (lightning) and those internal to the power supply network (polluting equipment, switchgear operation, etc.).
Such SPDs are also installed in RJ11, RJ45, ... connectors or integrated into loads.