Detailed characteristics of the external SCPD: Difference between revisions

From Electrical Installation Guide
Home > Overvoltage protection > Surge protection technical supplements > Detailed characteristics of the external SCPD
m (1 revision: no page modification, previous revision = imported ch.J pages cleaned-up)
(Cleanup_2016)
Line 2: Line 2:


__TOC__
__TOC__
== Current wave withstand  ==
== Current wave withstand  ==


The current wave withstand tests on external SCPDs show as follows:  
The current wave withstand tests on external SCPDs show as follows:  
*For a given rating and technology (NH or cylindrical fuse), the current wave withstand capability is better with an aM type fuse (motor protection) than with a gG type fuse (general use).  
*For a given rating and technology (NH or cylindrical fuse), the current wave withstand capability is better with an aM type fuse (motor protection) than with a gG type fuse (general use).  
*For a given rating, the current wave withstand capability is better with a circuit breaker than with a fuse device.
*For a given rating, the current wave withstand capability is better with a circuit breaker than with a fuse device.


{{FigureRef|J53}} below shows the results of the voltage wave withstand tests:  
{{FigureRef|J53}} below shows the results of the voltage wave withstand tests:  
*to protect a SPD defined for Imax = 20 kA, the external SCPD to be chosen is either a MCB 16 A or a Fuse aM 63 A,
*to protect a SPD defined for Imax = 20 kA, the external SCPD to be chosen is either a MCB 16 A or a Fuse aM 63 A,
 
:'''Note:''' in this case, a Fuse gG 63 A is not suitable.  
Note: in this case, a Fuse gG 63 A is not suitable.  
 
*to protect a SPD defined for Imax = 40 kA, the external SCPD to be chosen is either a MCB 40 A or a Fuse aM 125 A,
*to protect a SPD defined for Imax = 40 kA, the external SCPD to be chosen is either a MCB 40 A or a Fuse aM 125 A,


[[File:DB422521_EN.svg|none]]
{{FigImage|DB422521_EN|svg|J53|Comparison of SCPDs voltage wave withstand capabilities for Imax {{=}} 20 kA and Imax {{=}} 40 kA}}
 
'''''Fig. J53:''' Comparison of SCPDs voltage wave withstand capabilities for Imax = 20 kA and Imax = 40 kA''


== Installed Up voltage protection level ==
== Installed Up voltage protection level ==


In general:  
In general:  
*The voltage drop across the terminals of a circuit breaker is higher than that across the terminals of a fuse device. This is because the impedance of the circuit-breaker components (thermal and magnetic tripping devices) is higher than that of a fuse.However:
*The voltage drop across the terminals of a circuit breaker is higher than that across the terminals of a fuse device. This is because the impedance of the circuit-breaker components (thermal and magnetic tripping devices) is higher than that of a fuse.However:
*The difference between the voltage drops remains slight for current waves not exceeding 10 kA (95% of cases);  
*The difference between the voltage drops remains slight for current waves not exceeding 10 kA (95% of cases);  
*The installed Up voltage protection level also takes into account the cabling impedance. This can be high in the case of a fuse technology (protection device remote from the SPD) and low in the case of a circuit-breaker technology (circuit breaker close to, and even integrated into the SPD).
*The installed Up voltage protection level also takes into account the cabling impedance. This can be high in the case of a fuse technology (protection device remote from the SPD) and low in the case of a circuit-breaker technology (circuit breaker close to, and even integrated into the SPD).
: '''Note''': The installed Up voltage protection level is the sum of the voltage drops:
:* in the SPD;
:* in the external SCPD;
:* in the equipment cabling


Note: The installed Up voltage protection level is the sum of the voltage drops:<br>&nbsp; - in the SPD;<br>&nbsp; - in the external SCPD;<br>&nbsp; - in the equipment cabling
== Protection from impedant short circuits  ==


== Protection from impedant short circuits  ==
An impedant short circuit dissipates a lot of energy and should be eliminated very quickly to prevent damage to the installation and to the SPD.
 
{{FigureRef|J54}} compares the response time and the energy limitation of a protection system by a 63 A aM fuse and a 25 A circuit breaker.


An impedant short circuit dissipates a lot of energy and should be eliminated very quickly to prevent damage to the installation and to the SPD.<br>{{FigureRef|J54}} compares the response time and the energy limitation of a protection system by a 63 A aM fuse and a 25 A circuit breaker.<br>These two protection systems have the same 8/20 µs current wave withstand capability (27 kA and 30 kA respectively).
These two protection systems have the same 8/20 µs current wave withstand capability (27 kA and 30 kA respectively).


[[File:Fig J51.jpg|none]]
{{FigImage|DB422522_EN|svg|J54|Comparison of time/current and energy limitations curves for a circuit breaker and a fuse having the same 8/20 µs current wave withstand capability}}
'''''Fig. J54:''' Comparison of time/current and energy limitations curves for a circuit breaker and a fuse having the same 8/20 µs current wave withstand capability''


[[zh:外部短路保护器的详细特征]]
[[zh:外部短路保护器的详细特征]]

Revision as of 00:54, 5 December 2016


Current wave withstand

The current wave withstand tests on external SCPDs show as follows:

  • For a given rating and technology (NH or cylindrical fuse), the current wave withstand capability is better with an aM type fuse (motor protection) than with a gG type fuse (general use).
  • For a given rating, the current wave withstand capability is better with a circuit breaker than with a fuse device.

Figure J53 below shows the results of the voltage wave withstand tests:

  • to protect a SPD defined for Imax = 20 kA, the external SCPD to be chosen is either a MCB 16 A or a Fuse aM 63 A,
Note: in this case, a Fuse gG 63 A is not suitable.
  • to protect a SPD defined for Imax = 40 kA, the external SCPD to be chosen is either a MCB 40 A or a Fuse aM 125 A,
Fig. J53 – Comparison of SCPDs voltage wave withstand capabilities for Imax = 20 kA and Imax = 40 kA

Installed Up voltage protection level

In general:

  • The voltage drop across the terminals of a circuit breaker is higher than that across the terminals of a fuse device. This is because the impedance of the circuit-breaker components (thermal and magnetic tripping devices) is higher than that of a fuse.However:
  • The difference between the voltage drops remains slight for current waves not exceeding 10 kA (95% of cases);
  • The installed Up voltage protection level also takes into account the cabling impedance. This can be high in the case of a fuse technology (protection device remote from the SPD) and low in the case of a circuit-breaker technology (circuit breaker close to, and even integrated into the SPD).
Note: The installed Up voltage protection level is the sum of the voltage drops:
  • in the SPD;
  • in the external SCPD;
  • in the equipment cabling

Protection from impedant short circuits

An impedant short circuit dissipates a lot of energy and should be eliminated very quickly to prevent damage to the installation and to the SPD.

Figure J54 compares the response time and the energy limitation of a protection system by a 63 A aM fuse and a 25 A circuit breaker.

These two protection systems have the same 8/20 µs current wave withstand capability (27 kA and 30 kA respectively).

Fig. J54 – Comparison of time/current and energy limitations curves for a circuit breaker and a fuse having the same 8/20 µs current wave withstand capability

zh:外部短路保护器的详细特征

Share