|
|
Line 10: |
Line 10: |
| * A PV main switch is necessary. When the inverter is indoors, an additional remote controlled switch at the DC cable entry point is recommended for emergencies services. | | * A PV main switch is necessary. When the inverter is indoors, an additional remote controlled switch at the DC cable entry point is recommended for emergencies services. |
|
| |
|
| {{TableStart|Tab1405|5col}} | | {{FigImage|DB422723_EN|svg|P22|Grid connected <{{=}} 10kW}} |
| |-
| |
| |colspan="5" | [[File:DB422723_EN.svg|830px]]
| |
| |-
| |
| ! width="180px" | Needs
| |
| ! align="center" width="110px" | String junction box
| |
| ! align="center" width="180px" | PV array main switch
| |
| ! align="center" width="160px" | Inverter
| |
| ! align="center" width="170px" | AC box (400V)
| |
| |- {{PV_HC1}} align="center"
| |
| | colspan="5" | '''Switchgears and control (Q)'''
| |
| |- {{PV_HC1}} align="center"
| |
| | Isolation || • || •{{TabRef|Tab1405|d}} || {{TabRef|Tab1405|a}} || •{{TabRef|Tab1405|d}}
| |
| |- {{PV_HC1}} align="center"
| |
| | Switching
| |
| (Making & breaking rated current
| |
| | •<br>DC21B || •{{TabRef|Tab1405|d}}<br>DC21B || {{TabRef|Tab1405|a}} || •{{TabRef|Tab1405|d}}
| |
| |- {{PV_HC1}} align="center"
| |
| | Control || •{{TabRef|Tab1405|b}} || •{{TabRef|Tab1405|d}} || {{TabRef|Tab1405|e}} || •{{TabRef|Tab1405|d}}
| |
| |- {{PV_HC1}} align="center"
| |
| | Over-current protection || {{TabRef|Tab1405|c}} || || || •{{TabRef|Tab1405|f}}
| |
| |- {{PV_HC1}} align="center"
| |
| | Protection against<br>Insulation fault || || || {{TabRef|Tab1405|g}} || {{TabRef|Tab1405|g}} <br>RCD type B or A SI
| |
| |- {{PV_HC2}} align="center"
| |
| | '''Surge protection (SPD)''' || || • type 2 || || • type 1 or 2
| |
| |- {{PV_HC3}} align="center"
| |
| | '''Enclosure (E)''' || Outdoor<br>Double insulation || Indoor<br>Double insulation || || Standard AC requirement +<br>grid code requirement
| |
| |- {{PV_HC4}} align="center"
| |
| | '''Metering''' || || || Inverter relevant parameters || Energy
| |
| |-
| |
| {{TableEnd|Tab1405|P22|Grid connected <{{=}} 10kW
| |
| |a| PV array main switch could be included in the inverter. This solution makes inverter service or replacement more difficult.
| |
| |b| Remote switching for emergency services located as closely as possible to the PV modules or to the point of entry of DC cables in the building.
| |
| |c| No protection is required when the number of string does not exceed 2.
| |
| |d| Service and emergency switching
| |
| |e| Inverter shall include a protection for anti-islanding (in accordance with VDE 0126 for example)
| |
| |f| Overload and short-circuit protection B curve recommended.
| |
| |g| If the inverter provides no galvanic separation a RCD protection is necessary on AC side. IEC 60364-712 specifies RCD type B. Some local regulations require RCD type A SI}}
| |
|
| |
|
| == 10 to 100kW grid connected PV system (Small building)==
| | === One three phase inverter with one string combiner box === |
| | |
| === One three phase multi input inverter without array box === | |
| | |
| * Typically, 10kW to 36kW grid-connected inverters, U<sub>OC MAX</sub> probably higher than 600V (i.e. 800V or 1000V), Isctc < 125A, Iac < 63A.
| |
| * In this range of power, inverters usually have between 2 and 4 maximum power point tracking (MPPT) inputs, so the number of strings in the same DC sub-network is equal to one or two.
| |
| * There is no need for string protection. A PV main switch for each MPPT input is necessary.
| |
| * When an inverter is indoors, additional remote-controlled switches at DC cable entry point are recommended for emergencies services.
| |
| | |
| {{TableStart|Tab1406|5col}}
| |
| |-
| |
| | colspan="5" | [[File:DB422724_EN.svg|900px]]
| |
| |-
| |
| ! width="170px" | Needs
| |
| ! align="center" width="145px" | String junction box
| |
| ! align="center" width="165px" | PV array main switch
| |
| ! align="center" width="135px" | Inverter
| |
| ! align="center" width="185px" | AC box (400V)
| |
| |- {{PV_HC1}} align="center"
| |
| | colspan="5" | '''Switchgears and control (Q)'''
| |
| |- {{PV_HC1}} align="center"
| |
| | Isolation || • || •{{TabRef|Tab1406|d}} || {{TabRef|Tab1406|a}} || •{{TabRef|Tab1406|d}}
| |
| |- {{PV_HC1}} align="center"
| |
| | Switching<br>(Making & breaking rated current || •<br>DC21B || • {{TabRef|Tab1406|d}}<br>DC21B || {{TabRef|Tab1406|a}} || •{{TabRef|Tab1406|d}}
| |
| |- {{PV_HC1}} align="center"
| |
| | Control || •{{TabRef|Tab1406|b}} || •{{TabRef|Tab1406|d}} || {{TabRef|Tab1406|e}} || •{{TabRef|Tab1406|d}}
| |
| |- {{PV_HC1}} align="center"
| |
| | Over-current protection || {{TabRef|Tab1406|c}} || || || •{{TabRef|Tab1406|f}}
| |
| |- {{PV_HC1}} align="center"
| |
| | Protection against<br>Insulation fault || || || {{TabRef|Tab1406|h}} || {{TabRef|Tab1406|h}}<br>RCD type B or A SI
| |
| |- {{PV_HC2}} align="center"
| |
| | '''Surge protection (SPD)''' || {{TabRef|Tab1406|g}} || • type 2 || || • type 1 or 2
| |
| |- {{PV_HC3}} align="center"
| |
| | '''Enclosure (E)''' || Outdoor IP5x<br>Double insulation || Indoor IP5x<br>Double insulation || || Standard AC requirement +<br>grid code requirement
| |
| |- {{PV_HC4}} align="center"
| |
| | '''Metering''' || || || || Energy
| |
| |-
| |
| {{TableEnd|Tab1406|P23|10-100kW single multi MPPT inverter
| |
| |a| PV array main switch could be included in the inverter. This solution makes inverter service or replacement difficult.
| |
| |b| Remote switching for emergency services located as closely as possible to the PV modules or to the point of entry of DC cables in the building.
| |
| |c| No protection is required when the number of string does not exceed 2.
| |
| |d| Service and emergency switching
| |
| |e| Inverter shall include a protection for anti-islanding (in accordance with VDE 0126 for example)
| |
| |f| Overload and short-circuit protection (B curve recommended).
| |
| |g| If there is no SPD in the inverter or if the distance between String junction box and inverter exceeds 10m a SPD is necessary in this box.
| |
| |h|
| |
| || * If the inverter provides no galvanic separation a RCD protection is necessary on AC side. IEC 60364-712 specifies RCD type B. Some local regulations require RCD type A SI
| |
| || * If the inverter provides at least simple separation
| |
| || - Without functional earthing: insulation monitoring is necessary, it's usually done by the inverter in this range of power.
| |
| || - With functional earthing: the earthing shall be done with a DC MCB breaker (C60PV 4P series 2 – 10A) or a fuse.}}
| |
| | |
| === One three phase inverter with One Array box ===
| |
|
| |
|
| * Typically, 30kW to 60kW grid-connected inverters. U<sub>OC max</sub> is generally higher than 600V (up to 1000V), Isctc does not exceed 200A, Iac does not exceed 100A. | | * Typically, 30kW to 60kW grid-connected inverters. U<sub>OC max</sub> is generally higher than 600V (up to 1000V), Isctc does not exceed 200A, Iac does not exceed 100A. |
Line 107: |
Line 19: |
| * A main PV switch is required. When an inverter is inside, additional remote-controlled switch at DC cable entry point is recommended for emergencies. | | * A main PV switch is required. When an inverter is inside, additional remote-controlled switch at DC cable entry point is recommended for emergencies. |
|
| |
|
| {{TableStart|Tab1407|5col}} | | {{FigImage|DB422725_EN|svg|P23|10-100kW single MPPT inverter}} |
| |-
| |
| | colspan="5" | [[File:DB422725_EN.svg|830px]] | |
| |-
| |
| ! width="160px" | Needs
| |
| ! align="center" width="135px" | String / Array junction box
| |
| ! align="center" width="160px" | PV array main switch
| |
| ! align="center" width="145px" | Inverter
| |
| ! align="center" width="200px" | AC box (400V)
| |
| |- {{PV_HC1}} align="center"
| |
| | colspan="5" | '''Switchgears and control (Q)'''
| |
| |- {{PV_HC1}} align="center"
| |
| | Isolation || • || •{{TabRef|Tab1407|d}} || {{TabRef|Tab1407|a}} || •{{TabRef|Tab1407|d}}
| |
| |- {{PV_HC1}} align="center"
| |
| | Switching<br>(Making & breaking rated current || •<br>DC21B || •{{TabRef|Tab1407|d}}<br>DC21B || {{TabRef|Tab1407|a}} || •{{TabRef|Tab1407|d}}
| |
| |- {{PV_HC1}} align="center"
| |
| | Control || •{{TabRef|Tab1407|b}} || •{{TabRef|Tab1407|d}} || {{TabRef|Tab1407|e}} || •{{TabRef|Tab1407|d}}
| |
| |- {{PV_HC1}} align="center"
| |
| | Over-current protection || • || || || •{{TabRef|Tab1407|f}}
| |
| |- {{PV_HC1}} align="center"
| |
| | Protection against<br>Insulation fault || || || {{TabRef|Tab1407|h}} || {{TabRef|Tab1407|h}}<br>RCD type B or A SI
| |
| |- {{PV_HC2}} align="center"
| |
| | '''Surge protection (SPD)''' || {{TabRef|Tab1407|g}} || • type 2 || || • type 1 or 2
| |
| |- {{PV_HC3}} align="center"
| |
| | '''Enclosure (E)''' || Outdoor IP5x<br>Double insulation || Indoor IP5x<br>Double insulation || || Standard AC requirement +<br>grid code requirement
| |
| |- {{PV_HC4}} align="center"
| |
| | '''Metering''' || || || || P, Q, PF, Energy
| |
| |-
| |
| {{TableEnd|Tab1407|P24|10-100kW single MPPT inverter
| |
| |a| PV array main switch could be included in the inverter. This solution makes inverter service or replacement difficult.
| |
| |b| Remote switching for emergency services located as closely as possible to the PV modules or to the point of entry of DC cables in the building. The main switch in array box can be equipped with tripping coil and motor mechanism for remote reclosing for that purpose.
| |
| |d| Service and emergency switching
| |
| |e| Inverter shall include a protection for anti-islanding (in accordance with VDE 0126 for example)
| |
| |f| Overload and short-circuit protection (B curve recommended).
| |
| |g| If there is no SPD in the inverter or if the distance between String / Array junction box and inverter exceeds 10m a SPD is necessary in this box.
| |
| |h| If the inverter provides no galvanic separation a RCD protection is necessary on AC side. IEC 60364-712 specifies RCD type B. Some local regulations require RCD type A SI.
| |
| || If the inverter provides at least simple separation
| |
| || - Without functional earthing: insulation monitoring is necessary
| |
| || - With functional earthing: the earthing shall be done with a DC MCB breaker (C60PV 4P series 2 – 10A) or a fuse.}}
| |
|
| |
|
| === Multi single phase inverters design === | | === Multi single phase inverters design === |
Line 153: |
Line 27: |
| * In that case, the DC system is very simple and the AC system is very similar to usual AC systems. | | * In that case, the DC system is very simple and the AC system is very similar to usual AC systems. |
|
| |
|
| {{TableStart|Tab1408|5col}} | | {{FigImage|DB422726_EN|svg|P24|10-100kW multi single MPPT inverter}} |
| |-
| |
| | colspan="5" | [[File:DB422726_EN.svg|820px]]
| |
| |-
| |
| ! width="170px" | Needs
| |
| ! align="center" width="120px" | PV arraymain switch
| |
| ! align="center" width="140px" | Inverter
| |
| ! align="center" width="180px" |
| |
| ! align="center" width="190px" | AC box (400V)
| |
| |- {{PV_HC1}} align="center"
| |
| | '''Switchgears and control (Q)''' || colspan="4" | See [[#Grid connected PV system ≤ 10kW (Residential)|≤10kW design]]
| |
| |- {{PV_HC1}} align="center"
| |
| | '''Surge protection (SPD)''' || • type 2 || || || • type 1 or 2
| |
| |- {{PV_HC3}} align="center"
| |
| | '''Enclosure (E)''' || Outdoor IP5x<br>Double insulation || || || Standard AC requirement +<br>grid code requirement
| |
| |- {{PV_HC4}} align="center"
| |
| | '''Metering''' || || || Energy || P,Q, PF, Energy, unbalance
| |
| |-
| |
| {{TableEnd|Tab1408|P25|10-100kW multi single MPPT inverter}}
| |
| | |
| === Three phase inverter with two Array boxes (Na ≤ 2) ===
| |
| | |
| * Typically, 60kW to 100kW grid-connected inverters with 2 arrays. Array cable protection is not necessary for 2 or 3 arrays.
| |
| * The I<sub>sctc</sub> array ≤ 200A, I<sub>sctc</sub> ≤ 400A, and I<sub>max</sub> AC ≤ 200A. A PV main switch is required close to the inverter. Remotely operated switches in array boxes allow disconnects to be located close to the PV modules in the event of emergencies.
| |
| | |
| {{TableStart|Tab1409|5col}}
| |
| |-
| |
| | colspan="5" | [[File:DB422727_EN.svg|810px]]
| |
| |-
| |
| ! width="160px" | Needs
| |
| ! align="center" width="135px" | String / Array junction box
| |
| ! align="center" width="170px" | PV array main switch
| |
| ! align="center" width="160px" | Inverter
| |
| ! align="center" width="175px" | AC box (400V)
| |
| |- {{PV_HC1}} align="center"
| |
| | colspan="5" | '''Switchgears and control (Q)'''
| |
| |- {{PV_HC1}} align="center"
| |
| | Isolation || • || •{{TabRef|Tab1409|d}} || {{TabRef|Tab1409|a}} || •{{TabRef|Tab1409|d}}
| |
| |- {{PV_HC1}} align="center"
| |
| | Switching<br>(Making & breaking<br>rated current || •<br>DC21B || •{{TabRef|Tab1409|d}}<br>DC21B || {{TabRef|Tab1409|a}} || •{{TabRef|Tab1409|d}}
| |
| |- {{PV_HC1}} align="center"
| |
| | Control || • {{TabRef|Tab1409|b}} || •{{TabRef|Tab1409|d}} || {{TabRef|Tab1409|e}} || •{{TabRef|Tab1409|d}}
| |
| |- {{PV_HC1}} align="center"
| |
| | Over-current protection || • || {{TabRef|Tab1409|c}}|| || •{{TabRef|Tab1409|f}}
| |
| |- {{PV_HC1}} align="center"
| |
| | Protection against<br>Insulation fault || || || {{TabRef|Tab1409|h}} || {{TabRef|Tab1409|h}}<br>RCD type B or A SI
| |
| |- {{PV_HC2}} align="center"
| |
| | '''Surge protection (SPD)''' || {{TabRef|Tab1409|g}} || • type 2 || || • type 1 or 2
| |
| |- {{PV_HC3}} align="center"
| |
| | '''Enclosure (E)''' || Outdoor IP5x<br>Double insulation || Indoor IP5x<br>Double insulation || || Standard AC requirement +<br>grid code requirement
| |
| |- {{PV_HC4}} align="center"
| |
| | '''Metering''' || || || || P, Q, PF, Energy
| |
| |-
| |
| {{TableEnd|Tab1409|P26|10-100kW single MPPT inverter with 2 arrays
| |
| |a| PV array main switch could be included in the inverter. This solution makes inverter service or replacement difficult.
| |
| |b| If switching for emergency services is required, the main switch in array box can be equipped with tripping coil and motor mechanism for remote reclosing.
| |
| |c| No protection is required when the number of arrays ≤ 3 (No cable sizing benefit)
| |
| |d| Service and emergency switching
| |
| |e| Inverter shall include a protection for anti-islanding (in accordance with VDE 0126 for example)
| |
| |f| Overload and short-circuit protection.
| |
| |g| If there is no SPD in the inverter or if the distance between DC box and inverter exceeds 10m a SPD is necessary in this box.
| |
| |h| If the inverter provides no galvanic separation a RCD protection is necessary on AC side. IEC 60364-712 specifies RCD type B. Some local regulations require RCD type A SI
| |
| || If the inverter provides at least simple separation
| |
| || - Without functional earthing: insulation monitoring is necessary
| |
| || - With functional earthing: the earthing shall be done with a DC MCB breaker (iC60PV 4P series 2 – 10A) or a fuse.}}
| |
|
| |
|
| == 150kW to 500kW Grid connected PV system (Large building and farm) == | | == 150kW to 500kW Grid connected PV system (Large building and farm) == |
Line 224: |
Line 34: |
|
| |
|
| * Typically, 150kW to 500kW single inverter. | | * Typically, 150kW to 500kW single inverter. |
| * This design is very similar to the previous one except that it has more arrays, which requires array cable protection. | | * This design is very similar to the three phase inverter with one string combiner box except that it has more arrays, which requires array cable protection. |
| * Istc <= 400A, IAC <= 600A. | | * Istc <= 400A, IAC <= 600A. |
|
| |
|
| {{TableStart|Tab1410|5col}} | | {{FigImage|DB422728_EN|svg|P25|150-500kW single MPPT inverter with N arrays > 2}} |
| |-
| |
| | colspan="6" | [[File:DB422728_EN.svg|820px]] | |
| |-
| |
| ! width="150px" | Needs
| |
| ! align="center" width="70px" | String
| |
| ! align="center" width="130px" | Array junction box
| |
| ! align="center" width="140px" | Generator junction box
| |
| ! align="center" width="140px" | Inverter
| |
| ! align="center" width="170px" | AC box 400V or other voltage (Transfoless inverter)
| |
| |- {{PV_HC1}} align="center"
| |
| | colspan="6" | '''Switchgears and control (Q)'''
| |
| |- {{PV_HC1}} align="center"
| |
| | Isolation || • || • || • || {{TabRef|Tab1410|a}} || •{{TabRef|Tab1410|d}}
| |
| |- {{PV_HC1}} align="center"
| |
| | Switching<br>(Making & breaking<br>rated current || || •<br>DC22A || • <br>DC22A || •{{TabRef|Tab1410|a}} || •{{TabRef|Tab1410|d}}
| |
| |- {{PV_HC1}} align="center"
| |
| | Control || || •{{TabRef|Tab1410|b}} || || •{{TabRef|Tab1410|a}}{{TabRef|Tab1410|e}} || •{{TabRef|Tab1410|d}}
| |
| |- {{PV_HC1}} align="center"
| |
| | Over-current protection || • || || •{{TabRef|Tab1410|c}} || || •{{TabRef|Tab1410|f}}
| |
| |- {{PV_HC1}} align="center"
| |
| | Protection against<br>Insulation fault || || || || •{{TabRef|Tab1410|h}} || •{{TabRef|Tab1410|h}}
| |
| |- {{PV_HC2}} align="center"
| |
| | '''Surge protection (SPD)''' || || {{TabRef|Tab1410|g}} || • type 2 || || • type 1 or 2
| |
| |- {{PV_HC3}} align="center"
| |
| | '''Enclosure (E)''' || || Outdoor IP5x<br>Double insulation || Indoor<br>Double insulation || || Standard AC requirement +<br>grid code requirement
| |
| |- {{PV_HC4}} align="center"
| |
| | '''Metering''' || || || || || P, Q, PF, Energy, Alarm, THD, individual harmonics
| |
| |-
| |
| {{TableEnd|Tab1410|P27|150-500kW single MPPT inverter with N arrays > 2
| |
| |a| PV array main switch could be included in the inverter. This solution makes inverter service or replacement more difficult.
| |
| |b| If switching for emergency services is required, the main switch in array box can be equipped with tripping coil and motor mechanism for remote reclosing.
| |
| |c| Array cable protection is recommended to prevent cable oversizing. To ensure fast trip of protections 6 to 8 arrays are recommended.
| |
| |d| Service and emergency switching
| |
| |e| Inverter shall include a protection for anti-islanding (in accordance with VDE 0126 for example)
| |
| |f| Overload and short-circuit protection.
| |
| |g| If there is no SPD in the inverter or if the distance between DC box and inverter exceeds 10m a SPD is necessary in this box.
| |
| |h| Galvanic insulation is provided by LV/MV transformer,
| |
| || - PV system without functional earthing: insulation monitoring is necessary: IMD - IM20 and accessory IMD-IM20-1700
| |
| || - PV system with functional earthing: the earthing shall be done with a DC MCB breaker (C60PV 4P series 2 – 10A) or a fuse.}}
| |
|
| |
|
| === Multi three phases inverters design without array box === | | == Connection of PV system to the grid or to the private low voltage installation == |
|
| |
|
| * Typically 10x20 to 20x30kW grid connected inverters
| | === Direct connection of PV system to the grid === |
| * U<sub>oc</sub> max ≤ 1000V one or two string per inverter. IAC max 50A for one inverter.
| | When PV system is installed for "grid feeding", Utility that operates the grid will provide requirements for protection, disconnection, and metering function. |
|
| |
|
| {{TableStart|Tab1411|5col}}
| | Each utility may have specific requirements according to local habits and grid specificity. |
| |-
| |
| | colspan="5" | [[File:DB422729_EN.svg|820px]]
| |
| |-
| |
| ! width="200px" | Needs
| |
| ! align="center" width="150px" | String junction box
| |
| ! align="center" width="130px" |
| |
| ! align="center" width="130px" |
| |
| ! align="center" width="190px" | AC Combiner box
| |
| |- {{PV_HC1}} align="center"
| |
| | '''Switchgears and control (Q)''' || See 10 to 36kW design || || ||
| |
| |- {{PV_HC1}} align="center"
| |
| | '''Surge protection (SPD)''' ||• type 2 || || || • type 1 or 2
| |
| |- {{PV_HC3}} align="center"
| |
| | '''Enclosure (E)''' || Outdoor IP5x<br>Double insulation || || || Standard AC requirement +<br>grid code requirement
| |
| |- {{PV_HC4}} align="center"
| |
| | '''Metering''' || || || Energy || P, Q, PF, Energy, Alarm
| |
| |-
| |
| {{TableEnd|Tab1411|P28|150-500kW multi 3-phases inverters}}
| |
|
| |
|
| === Multi MW Grid connected PV system (Large building and farm)===
| | As a general rules the following functions are required : |
| | * Energy meter (both direction) |
| | * Disconnecting device (some countries require visual break) |
| | * Over-current and earth fault protection according to earthing system |
| | * Anti-islanding protection like VDE0126. |
|
| |
|
| * Typically 500kW-630kW inverters with LV/MV transformers and MV substation.
| | === Connection of PV system to the private low voltage installation === |
|
| |
|
| {{TableStart|Tab1412|5col}}
| | See [[Photovoltaic architectures for self-consumption]]. |
| |-
| |
| | colspan="7" | [[File:DB422730_EN.svg|830x830px]]
| |
| |-
| |
| ! width="150" | Needs
| |
| ! width="70" align="center" | String
| |
| ! width="130" align="center" | Array junction box
| |
| ! width="120" align="center" | Generator junction box
| |
| ! colspan="2" |Inverter
| |
| ! width="170" align="center" | AC box 400V or other voltage (Transfoless inverter)
| |
| |-
| |
| | colspan="4" | '''Switchgears and control (Q)'''
| |
| | DC side
| |
| | AC side
| |
| |- align="center"
| |
| | Isolation
| |
| | •
| |
| | •
| |
| | •{{TabRef|Tab1412|a}}
| |
| |•
| |
| |•
| |
| | •
| |
| |- align="center"
| |
| | Switching
| |
| (Making & breaking<br>
| |
| rated current
| |
| |
| |
| | •<br>
| |
| DC22A
| |
| | •{{TabRef|Tab1412|a}}
| |
| |•
| |
| DC22A or
| |
| 23A
| |
| |•
| |
| AC1
| |
| | •
| |
| |- align="center"
| |
| | Control
| |
| |
| |
| | •{{TabRef|Tab1412|b}}
| |
| |
| |
| |•
| |
| |•
| |
| | •
| |
| |- align="center"
| |
| | Over-current protection
| |
| | •
| |
| |
| |
| | •{{TabRef|Tab1412|c}}
| |
| |No
| |
| |•
| |
| | •{{TabRef|Tab1412|f}}
| |
| |- align="center"
| |
| | Protection against
| |
| Insulation fault
| |
| |
| |
| |
| |
| |•{{TabRef|Tab1412|h}}
| |
| |•
| |
| |
| |
| | •{{TabRef|Tab1412|h}}
| |
| |- align="center"
| |
| | '''Surge protection (SPD)'''
| |
| |
| |
| | {{TabRef|Tab1412|g}}
| |
| | • type 2
| |
| | colspan="2" | {{TabRef|Tab1412|g}}
| |
| | • type 1 or 2
| |
| |- align="center"
| |
| | '''Enclosure (E)'''
| |
| |
| |
| | Outdoor IP5x
| |
| Double insulation
| |
| | Indoor
| |
| Double insulation
| |
| | colspan="2" |
| |
| |
| |
| |- align="center"
| |
| | '''Metering'''
| |
| |
| |
| | Energy
| |
| |
| |
| | colspan="2" |
| |
| | P, Q, PF, Energy, Alarm, Power quality
| |
| |-
| |
| {{TableEnd|Tab1412|P29|500-630kW inverters with LV/MV transformers
| |
| |a| PV array main switch is usually included in the inverter panel.
| |
| |b| If switching for emergency services is required, the main switch in array box can be equipped with tripping coil and motor mechanism for remote reclosing.
| |
| |c| Array cable protection is recommended to prevent cable oversizing. To ensure fast trip of protections 6 to 8 arrays are recommended.
| |
| |f| Overload and short-circuit protection.
| |
| |g| If there is no SPD in the inverter or if the between DC box and inverter >10m a SPD is necessary in this box.
| |
| |h| Galvanic insulation is provided by LV/MV transformer,
| |
| || - PV system without functional earthing: insulation monitoring is necessary: IMD - IM20 and accessory IMD-IM20-1700
| |
| || - PV system with functional earthing: the earthing shall be done with a DC MCB breaker (C60PV 4P series 2 – 10A) or a fuse.}}
| |