| == Different type of ground fault protections ==
| |
| | |
| (see {{FigRef|F27}})<br>
| |
| | |
| Three types of GFP are possible dependind on the measuring device installed :
| |
| | |
| *“Residual Sensing” RS
| |
| | |
| The “insulation fault” current is calculated using the vectorial sum of currents of current transformers secondaries. The current transformer on the neutral conductor is often outside the circuit-breaker.
| |
| | |
| *“Source Ground Return” SGR
| |
| | |
| The « insulation fault current » is measured in the neutral – earth link of the LV transformer. The current transformer is outside the circuit-breaker.
| |
| | |
| *“Zero Sequence” ZS
| |
| | |
| The « insulation fault » is directly measured at the secondary of the current transformer using the sum of currents in live conductors. This type of GFP is only used with low fault current values.
| |
| | |
| [[File:FigF27.jpg|500px|none]]
| |
| '''''Fig. F27:'''''<i> Different types of ground fault protections</i>
| |
| | |
| == Positioning GFP devices in the installation ==
| |
| | |
| {| class="wikitable"
| |
| |-
| |
| ! Type / installation level
| |
| ! Main-distribution
| |
| ! Sub-distribution
| |
| ! Comments
| |
| |-
| |
| | Source Ground Return (SGR)
| |
| | {{EmptyBlueSquare}}
| |
| |
| |
| | Used
| |
| |-
| |
| | Residual Sensing (RS) (SGR)
| |
| | {{EmptyBlueSquare}}
| |
| | {{BlueSquare}}
| |
| | Often used
| |
| |-
| |
| | Zero Sequence (SGR)
| |
| | {{EmptyBlueSquare}}
| |
| | {{BlueSquare}}
| |
| | Rarely used
| |
| |}
| |
| | |
| <math>\color{RoyalBlue}\Box</math> Possible<br><math>\color{RoyalBlue}\blacksquare</math> Recommended or required
| |
| | |