Coordination of residual current protective devices: Difference between revisions

From Electrical Installation Guide
Home > Protection against electric shocks and electrical fires > Residual Current Devices (RCDs) > Coordination of residual current protective devices
(Cleanup_2016)
(No difference)

Revision as of 20:30, 10 April 2018


Discriminative-tripping coordination is achieved either by time-delay or by subdivision of circuits, which are then protected individually or by groups, or by a combination of both methods.

Such discrimination avoids the tripping of any RCD, other than that immediately upstream of a fault position:

  • With equipment currently available, discrimination is possible at three or four different levels of distribution :
    • At the main general distribution board
    • At local general distribution boards
    • At sub-distribution boards
    • At socket outlets for individual appliance protection
  • In general, at distribution boards (and sub-distribution boards, if existing) and on individual-appliance protection, devices for automatic disconnection in the event of an indirect-contact hazard occurring are installed together with additional protection against direct-contact hazards.

Discrimination between RCDs

The general specification for achieving total discrimination between two RCDs is as follow:

  • The ratio between the rated residual operating currents must be > 2
  • Time delaying the upstream RCD

Discrimination is achieved by exploiting the several levels of standardized sensitivity: 30 mA, 100 mA, 300 mA and 1 A and the corresponding tripping times, as shown in Figure F34.

Fig. F34 – Total discrimination at 2 levels

Discrimination at 2 levels

(see Fig. F35)

Protection

  • Level A: RCD time-delayed setting I (for industrial device) or type S (for domestic device) for protection against indirect contacts
  • Level B: RCD instantaneous, with high sensitivity on circuits supplying socket-outlets or appliances at high risk (washing machines, etc.)

Schneider Electric solutions

  • Level A: Compact or Acti 9 circuit-breaker with adaptable RCD module (Vigicompact NSX160), setting I or S type
  • Level B: Circuit-breaker with integrated RCD module (DPN Vigi) or adaptable RCD module (e.g. Vigi iC60) or Vigicompact NSX

Note: The setting of upstream RCCB must comply with selectivity rules and take into account all the downstream earth leakage currents.

Fig. F35 – Total discrimination at 2 levels

Discrimination at 3 or 4 levels

(see Fig. F36)

Protection

  • Level A: RCD time-delayed (setting III)
  • Level B: RCD time-delayed (setting II)
  • Level C: RCD time-delayed (setting I) or type S
  • Level D: RCD instantaneous

Schneider Electric solutions

  • Level A: Circuit-breaker associated with RCD and separate toroidal transformer (Vigirex RH)
  • Level B: Vigicompact NSX or Vigirex
  • Level C: Vigirex, Vigicompact NSX or Vigi iC60
  • Level D:
    • Vigicompact NSX or
    • Vigirex or
    • Acti 9 with integrated or adaptable RCD module: Vigi iC60 or DPN Vigi

Note: The setting of upstream RCCB must comply with selectivity rules and take into account all the downstream earth leakage currents

Fig. F36 – Total discrimination at 3 or 4 levels

Discriminative protection at three levels

(see Fig. F37)

Fig. F37 – Typical 3-level installation, showing the protection of distribution circuits in a TT-earthed system. One motor is provided with specific protection

ru:Система TT: координация устройств защиты от замыканий на землю zh:TT系统剩余电流保护装置间的配合

Share