Transformer-energizing inrush current: Difference between revisions

From Electrical Installation Guide
(Cleanup_2016)
(update_2018)
Line 3: Line 3:
__TOC__
__TOC__


At the moment of energizing a transformer, high values of transient current (which includes a significant DC component) occur, and must be taken into account when considering protection schemes (see {{FigRef|N31}}).
At the moment of energizing a transformer, high values of transient current (which includes a significant DC component) occur, and must be taken into account when considering protection schemes (see {{FigRef|N32}}).


{{FigImage|DB422663_EN|svg|N31|Transformer-energizing inrush current}}
{{FigImage|DB422663_EN|svg|N32|Transformer-energizing inrush current}}


The magnitude of the current peak depends on:  
The magnitude of the current peak depends on:  

Revision as of 03:47, 14 June 2018


At the moment of energizing a transformer, high values of transient current (which includes a significant DC component) occur, and must be taken into account when considering protection schemes (see Fig. N32).

Fig. N32 – Transformer-energizing inrush current

The magnitude of the current peak depends on:

  • The value of voltage at the instant of energization
  • The magnitude and polarity of the residual flux existing in the core of the transformer
  • Characteristics of the load connected to the transformer

The first current peak can reach a value equal to 10 to 15 times the full-load r.m.s. current, but for small transformers (< 50 kVA) may reach values of 20 to 25 times the nominal full-load current. This transient current decreases rapidly, with a time constant θ of the order of several ms to severals tens of ms.

ru:Ток намагничивания трансформатора при включении zh:变压器励磁涌流

Share