PV array with a single string of modules
This is the simplest configuration (see Fig. P17). It is used for small PV arrays with peak power of up to 3 kWp depending on the modules deployed. In most cases, it is used for residential PV operations.
Modules are connected in series, supplying direct current of between 200 and 500 VDC in this instance. Optimal efficiency is obtained from the inverter within this voltage range.
A single DC line is fed through to the inverter. The PV array can be isolated from the inverter by means of a load break switch near the inverter.
PV array with several module strings in parallel
This configuration (see Fig. P18), mainly deployed on buildings or in small PV power plants on the ground, is used for PV installations of up to thirty strings in parallel with power output of some 100 kWp.
The strings are paralleled in a PV string combiner box. This box includes the safety devices required for paralleling the strings and appliances used to measure the strings’ current. A single DC cable connects these boxes to the inverter.The PV array can be isolated from the inverter by means a load break switch near the inverter.
As a variation on this diagram, several single-phase inverters can be installed in a three-phase arrangement (see Fig. P19).
PV array with several strings divided into several groups
When power levels exceed 50 or 100 kW, photovoltaic arrays are split into subgroups (see Fig. P20) to make it easier to connect the various components. Strings are paralleled on two levels.
- Strings in each subgroup are paralleled in subgroup PV string combiner boxes. These boxes are fitted with safety devices, the necessary measuring equipment and monitoring devices.
- The outputs of these boxes are paralleled in a PV array combiner box near the inverter. This box is also fitted with the required safety devices as well as the measuring and monitoring equipment necessary for paralleling the subgroups.
The array can be isolated from the inverter using a load block switch which may or may not be fitted in the PV array box. The array’s direct current is approximately 1000 VDC.
PV AC Module or "String inverter"
An alternate solution to DC system is to closely link the inverter to the PV module, in that case the PV module become an AC power source. This solution, called PV AC Module, or "String inverter" is comon for small installation but can be used also for larger system. In that case all the paralleling and wiring is done in AC. General rules for AC system apply.