Building protection system: Difference between revisions
m (r2.7.2) (robot Adding: zh:建筑保护系统) |
m (1 revision imported: Migrated pages - removed CN links) |
||
(10 intermediate revisions by 5 users not shown) | |||
Line 1: | Line 1: | ||
{{ | {{Menu_Overvoltage_protection}}__TOC__ | ||
The role of the building protection system is to protect it against direct lightning strokes. | |||
__TOC__ | |||
The role of the building protection system is to protect it against direct lightning strokes. | |||
The system consists of: | |||
*the capture device: the lightning protection system; | *the capture device: the lightning protection system; | ||
*down-conductors designed to convey the lightning current to earth; | *down-conductors designed to convey the lightning current to earth; | ||
Line 16: | Line 14: | ||
Three types of building protection are used: | Three types of building protection are used: | ||
===The lightning rod (simple rod or with triggering system)=== | |||
The lightning rod is a metallic capture tip placed at the top of the building. It is earthed by one or more conductors (often copper strips) (see {{FigRef|J12}}). | |||
{{FigImage|DB422472_EN|svg|J12|Lightning rod (simple rod or with triggering system)}} | |||
=== The lightning rod with taut wires === | |||
- | These wires are stretched above the structure to be protected. They are used to protect special structures: rocket launching areas, military applications and protection of high-voltage overhead lines (see {{FigRef|J13}}). | ||
{{FigImage|DB422473_EN|svg|J13|Taut wires}} | |||
=== The lightning conductor with meshed cage (Faraday cage) === | |||
This protection involves placing numerous down conductors/tapes symmetrically all around the building. (see {{FigRef|J14}}). | |||
This type of lightning protection system is used for highly exposed buildings housing very sensitive installations such as computer rooms. | |||
{{FigImage|DB422474|svg|J14|Meshed cage (Faraday cage)}} | |||
== Consequences of building protection for the electrical installation's equipment == | == Consequences of building protection for the electrical installation's equipment == | ||
50% of the lightning current discharged by the building protection system rises back into the earthing networks of the electrical installation (see {{FigRef|J15}}): the potential rise of the frames very frequently exceeds the insulation withstand capability of the conductors in the various networks (LV, telecommunications, video cable, etc.). | |||
50% of the lightning current discharged by the building protection system rises back into the earthing networks of the electrical installation (see | |||
Moreover, the flow of current through the down-conductors generates induced overvoltages in the electrical installation. | |||
{{Highlightbox| | |||
As a consequence, the building protection system does not protect the electrical installation: it is therefore compulsory to provide for an electrical installation protection system.}} | |||
{{FigImage|DB422475_EN|svg|J15|Direct lightning back current}} |
Latest revision as of 17:50, 20 December 2019
The role of the building protection system is to protect it against direct lightning strokes.
The system consists of:
- the capture device: the lightning protection system;
- down-conductors designed to convey the lightning current to earth;
- "crow's foot" earth leads connected together;
- links between all metallic frames (equipotential bonding) and the earth leads.
When the lightning current flows in a conductor, if potential differences appear between it and the frames connected to earth that are located in the vicinity, the latter can cause destructive flashovers.
The 3 types of lightning protection system
Three types of building protection are used:
The lightning rod (simple rod or with triggering system)
The lightning rod is a metallic capture tip placed at the top of the building. It is earthed by one or more conductors (often copper strips) (see Fig. J12).
The lightning rod with taut wires
These wires are stretched above the structure to be protected. They are used to protect special structures: rocket launching areas, military applications and protection of high-voltage overhead lines (see Fig. J13).
The lightning conductor with meshed cage (Faraday cage)
This protection involves placing numerous down conductors/tapes symmetrically all around the building. (see Fig. J14).
This type of lightning protection system is used for highly exposed buildings housing very sensitive installations such as computer rooms.
Consequences of building protection for the electrical installation's equipment
50% of the lightning current discharged by the building protection system rises back into the earthing networks of the electrical installation (see Fig. J15): the potential rise of the frames very frequently exceeds the insulation withstand capability of the conductors in the various networks (LV, telecommunications, video cable, etc.).
Moreover, the flow of current through the down-conductors generates induced overvoltages in the electrical installation.
As a consequence, the building protection system does not protect the electrical installation: it is therefore compulsory to provide for an electrical installation protection system.