Average power factor values for the most commonly-used equipment and appliances
(see Fig. L7)
Fig. L7 – Values of cos φ and tan φ for commonly-used equipment
Equipment and appliances | cos φ | tan φ | |||
---|---|---|---|---|---|
Motor | Common induction motor | loaded at | 0 % | 0.17 | 5.80 |
25% | 0.55 | 1.52 | |||
50 % | 0.73 | 0.94 | |||
75 % | 0.80 | 0.75 | |||
100 % | 0.85 | 0.62 | |||
Lamps | Incandescent lamps | 1.0 | 0 | ||
Fluorescent lamps (uncompensated) | 0.5 | 1.73 | |||
Fluorescent lamps (compensated) | 0.93 | 0.39 | |||
Discharge lamps | 0.4 to 0.6 | 2.29 to 1.33 | |||
Ovens | Ovens using resistance elements | 1.0 | 0 | ||
Induction heating ovens (compensated) | 0.85 | 0.62 | |||
Dielectric type heating ovens | 0.85 | 0.62 | |||
Welding | Resistance-type soldering machines | 0.8 to 0.9 | 0.75 to 0.48 | ||
Fixed 1-phase arc-welding set | 0.5 | 1.73 | |||
Arc-welding motor-generating set | 0.7 to 0.9 | 1.02 to 0.48 | |||
Arc-welding transformer-rectifier set | 0.7 to 0.8 | 1.02 to 0.75 | |||
Arc furnace | 0.8 | 0.75 |