At the moment of energizing a transformer, high values of transient current (which includes a significant DC component) occur, and must be taken into account when considering protection schemes (see {{FigRef|N31}}).
 
{{FigImage|DB422663_EN|svg|N31|Transformer-energizing inrush current}}
 
The magnitude of the current peak depends on:
*The value of voltage at the instant of energization
*The magnitude and polarity of the residual flux existing in the core of the transformer
*Characteristics of the load connected to the transformer
 
The first current peak can reach a value equal to 10 to 15 times the full-load r.m.s. current, but for small transformers (< 50 kVA) may reach values of 20 to 25 times the nominal full-load current. This transient current decreases rapidly, with a time constant θ of the order of several ms to severals tens of ms.
 