The system earthing arrangement must be properly selected to ensure the safety of life and property. The behaviour of the different systems with respect to EMC&nbsp;considerations must be taken into account.'''Figure R1 '''below presents a summary of their main characteristics.<br>European standards (see EN 50174-2 § 6.4 and EN 50310 § 6.3) recommend the TN-S system which causes the fewest EMC problems for installations comprising information-technology equipment (including telecom equipment).  
The system earthing arrangement must be properly selected to ensure the safety of life and property. The behaviour of the different systems with respect to EMC considerations must be taken into account. {{FigureRef|R1}} below presents a summary of their main characteristics.


----
European standards (see EN 50174-2, EN 50310 and HD 60364-4-444) recommend the TN-S eathing system which causes the fewest EMC problems for installations comprising information-technology equipment (including telecom equipment).


<br>
{{tb-start|id=Tab1440|num=R1|title=Main characteristics of the different earthing sytems|cols=5}}
 
{| class="wikitable"
{| style="width: 770px; height: 201px" cellspacing="1" cellpadding="1" width="770" border="1"
|-
|-
| bgcolor="#0099cc" | &nbsp;
!
| bgcolor="#0099cc" | '''TT'''
! TT  
| valign="top" bgcolor="#0099cc" | '''TN-S'''
! TN-S  
| bgcolor="#0099cc" | '''IT'''
! IT  
| bgcolor="#0099cc" | '''TN-C'''
! TN-C
|-
|-
| valign="top" | Safety of persons  
| Safety of persons  
| Good<br>RCD mandatory  
| Correct
| colspan="3" | Good<br>Continuity of the PE conductor must be ensured throughout the installation
Use of residual current devices (circuit breaker)is mandatory
| colspan="3" | Correct
Continuity of the PE conductor must be ensured throughout the installation
|-
|-
| Safety&nbsp;of&nbsp;property&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;
| Safety of property
| Good
| Correct
| Poor  
| Poor  
| Good
| Correct
| Poor
| Poor
|-
|-
| &nbsp;&nbsp;&nbsp;&nbsp;
|  
| valign="top" | Medium fault current<br>(&lt; a few dozen amperes)  
| Medium ground-fault current (< about ten amps)  
| valign="top" | High fault current<br>(around 1 kA)  
| High ground-fault current (about 1 kA)  
| Low current for first fault <br>(&lt; a few dozen mA),<br>but high for second fault  
| Low ground-fault current for first fault (< about ten mA), but high for second fault
| valign="top" | High fault current<br>(around 1 kA)
| High ground-fault current (about 1 kA)
|-
|-
| Availability of energy  
| Availability of energy  
| Good
| Correct
| Good
| Correct
| Excellent  
| Excellent  
| Good
| Correct
|-
|-
| valign="top" | EMC behaviour
| EMC performance
| valign="top" | Good<br>- Risk of overvoltages<br>- Equipotential problems<br>- Need to manage devices with high leakage currents&nbsp;
| Correct 
| valign="top" | Excellent<br>- Few equipotential problems<br>- Need to manage<br>devices with high <br>leakage currents<br>- High fault currents <br>(transient&nbsp;disturbances)  
* Risk of overvoltages
| valign="top" | Poor (to be avoided)<br>- Risk of overvoltages<br>- Common-mode filters and<br>surge arrestors must handle&nbsp;the phase- to-phase voltages<br>- RCDs subject&nbsp;to&nbsp;nuisance tripping if&nbsp;common-mode&nbsp;<br>capacitors are present<br>- Equivalent to TN system for second&nbsp;fault&nbsp;&nbsp;
* Equipotential problems
| valign="top" | Poor <br>(should never be used)<br>- Neutral and PE are the same<br>- Circulation of disturbed currents in exposed conductive parts (high<br>magnetic-field radiation)<br>- High fault currents(transient disturbances)
* Need to manage devices with high leakage currents
| Excellent  
* Good equipotential situation
* Need to manage devices with high leakage currents
* High ground- currents (transient disturbances)  
| Poor (to be avoided)
* Risk of overvoltages
* Common-mode filters and surge arrestors must handle the phase- to-phase voltages
* RCDs subject to nuisance tripping if common-mode capacitors are present
* Equivalent to TN system for second fault
| Poor (not recommended)
* Neutral and PE are combined
* 50/60 Hz and harmonics currents circulate in the earthing and grounding structures
* High ground-fault currents (transient disturbances)
|}
|}


'''''Fig. R1:''' Main characteristics of system earthing''
When an installation includes high-power equipment (motors, air-conditioning, lifts, power electronics, etc.), it is advised to install one or more transformers specifically for these systems. Electrical distribution must be organised in a star system and all outgoing circuits must exit the main low-voltage switchboard (MLVS).
 
----
 
When an installation includes high-power equipment (motors, air-conditioning, lifts, power electronics, etc.), it is advised to install one or more transformers specifically for these systems. Electrical distribution must be organised in a star system and all outgoing circuits must exit the main low-voltage switchboard (MLVS).<br>Electronic systems (control/monitoring, regulation, measurement instruments, etc.) must be supplied by a dedicated transformer in a TN-S system.<br>'''Figure R2 '''below illustrate these recommendations.  


----
Electronic systems (control/monitoring, regulation, measurement instruments, etc.) must be supplied by a dedicated transformer in a TN-S system.


<br>[[Image:Fig R02.jpg|left]]<br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br>'''''Fig. R2:''' Recommendations of separated distributions''
{{FigureRef|R2}} below illustrates these recommendations.


[[ru:ЭМС для различных схем распределения электроэнергии]]
{{FigImage|DB422765_EN|svg|R2|Recommendations of separated distributions}}
[[zh:不同配电系统结构的电磁兼容性能]]

Latest revision as of 09:47, 22 June 2022

The system earthing arrangement must be properly selected to ensure the safety of life and property. The behaviour of the different systems with respect to EMC considerations must be taken into account. Figure R1 below presents a summary of their main characteristics.

European standards (see EN 50174-2, EN 50310 and HD 60364-4-444) recommend the TN-S eathing system which causes the fewest EMC problems for installations comprising information-technology equipment (including telecom equipment).

Fig. R1 – Main characteristics of the different earthing sytems
TT TN-S IT TN-C
Safety of persons Correct

Use of residual current devices (circuit breaker)is mandatory

Correct

Continuity of the PE conductor must be ensured throughout the installation

Safety of property Correct Poor Correct Poor
Medium ground-fault current (< about ten amps) High ground-fault current (about 1 kA) Low ground-fault current for first fault (< about ten mA), but high for second fault High ground-fault current (about 1 kA)
Availability of energy Correct Correct Excellent Correct
EMC performance Correct
  • Risk of overvoltages
  • Equipotential problems
  • Need to manage devices with high leakage currents
Excellent
  • Good equipotential situation
  • Need to manage devices with high leakage currents
  • High ground- currents (transient disturbances)
Poor (to be avoided)
  • Risk of overvoltages
  • Common-mode filters and surge arrestors must handle the phase- to-phase voltages
  • RCDs subject to nuisance tripping if common-mode capacitors are present
  • Equivalent to TN system for second fault
Poor (not recommended)
  • Neutral and PE are combined
  • 50/60 Hz and harmonics currents circulate in the earthing and grounding structures
  • High ground-fault currents (transient disturbances)

When an installation includes high-power equipment (motors, air-conditioning, lifts, power electronics, etc.), it is advised to install one or more transformers specifically for these systems. Electrical distribution must be organised in a star system and all outgoing circuits must exit the main low-voltage switchboard (MLVS).

Electronic systems (control/monitoring, regulation, measurement instruments, etc.) must be supplied by a dedicated transformer in a TN-S system.

Figure R2 below illustrates these recommendations.

Fig. R2 – Recommendations of separated distributions