Internal MV circuits: Difference between revisions

From Electrical Installation Guide
(Text updated (guide 2015))
m (Text replacement - "\[\[ru:[^]]*\]\][ \r\n]*" to "")
 
(12 intermediate revisions by 5 users not shown)
Line 1: Line 1:
{{Menu_MV_and_LV_architecture_selection_guide}}
{{Menu_MV_and_LV_architecture_selection_guide}}
 
Internal MV circuits are dedicated to the supply of the secondary MV/LV substations dispersed in the installation. They are three typical principles commonly used for this purpose {{FigRef|D11}}:
Internal MV circuits are dedicated to the supply of the secondary MV/LV substations dispersed in the installation. They are three typical principles commonly used for this purpose '''(Fig. D11):'''
 
* Single feeder
* Single feeder
* Dual feeder
* Dual feeder
* Open ring
* Open ring


{{FigImage|DB422127_EN|svg|D11|Single feeder, Dual feeder, Open ring}}


Comparison of these three typical principles of internal distribution is given {{FigRef|D12}}.


'''Fig. D11:''' Single feeder, Dual feeder, Open ring
{{tb-start|id=Tab1084|num=D12|title=Comparison of the typical internal circuits|cols=3}}
 
{| class="wikitable"
Comparison of these three typical principles of internal distribution is given '''Fig D12.'''
 
{| class="wikitable" style="width: 65%; height: 122px"  
|-
|-
|  
|  
! colspan="3" | MV circuit configuration
! colspan="3" | MV circuit configuration
|-
|-
Line 38: Line 35:
| Short interruption not acceptable
| Short interruption not acceptable
|}
|}
'''Fig. D12:''' Comparison of the typical internal circuits
[[ru:Конфигурация схемы высокого напряжения]]
[[zh:中压回路的配置]]

Latest revision as of 09:48, 22 June 2022

Internal MV circuits are dedicated to the supply of the secondary MV/LV substations dispersed in the installation. They are three typical principles commonly used for this purpose Fig. D11:

  • Single feeder
  • Dual feeder
  • Open ring
Fig. D11 – Single feeder, Dual feeder, Open ring

Comparison of these three typical principles of internal distribution is given Fig. D12.

Fig. D12 – Comparison of the typical internal circuits
MV circuit configuration
Characteristic to consider Single feeder Open ring Dual feeder
Site topology Any Single or several buildings Single or several buildings
Power demand Any > 1250kVA > 2500kVA
Disturbance sensitivity Long interruption acceptable Short interruption acceptable Short interruption not acceptable