Bathrooms and showers rooms are areas of high risk, because of the very low resistance of the human body when wet or immersed in water.<br>Precaution to be taken are therefore correspondingly rigorous, and the regulations are more severe than those for most other locations.<br>The relevant standard is IEC 60364-7-701.  
Bathrooms and shower rooms are areas of high risk, because of the very low resistance of the human body when wet or immersed in water.


Precautions to observe are based on three aspects:
Precaution to be taken are therefore correspondingly rigorous, and the regulations are more severe than those for most other locations.


*The definition of zones, numbered 0,1, 2, 3 in which the placement (or exclusion) of any electrical device is strictly limited or forbidden and, where permitted, the electrical and mechanical protection is prescribed
The relevant international standard is IEC 60364-7-701, applicable to the electrical installations in locations containing a fixed bath (bath tub) or shower and to the surrounding zones. Refer to country specific standards (or deviations from the IEC requirements) whenever they exist.
*The establishment of an equipotential bond between all exposed and extraneous metal parts in the zones concerned
*The strict adherence to the requirements prescribed for each particular zones.


Precautions to observe are based on three aspects:
* The [[#Classification of zones|'''definition of zones''']], numbered 0, 1 and 2 in which the placement (or exclusion) of any electrical device is strictly limited or forbidden and, where permitted, the electrical and mechanical protection is prescribed
* The strict adherence to the [[#Requirements prescribed for each zone|'''requirements prescribed for each zone''']]
* The establishment of an [[#Equipotential bonding|'''equipotential bond''']] between all exposed and extraneous metal parts in the zones concerned.


==== Classification of zones ====
== Classification of zones ==
Sub-clause 701.30 of IEC 60364-7-701 defines the zones 0, 1 and 2, illustrated by the following figures for most common examples.


Sub-clause 701.32 of IEC 60364-7-701 defines the zones 0, 1, 2, 3 as shown in the following diagrams (see '''Fig. Q12 '''below to'''&nbsp;Fig. Q18''')
Refer to the standard for a more complete view.


[[File:FigQn12.jpg|none]]
{{FigImage|DB431086_EN|svg|Q15|Definition of zones 0, 1 and 2 (global view)}}
'''''Fig. Q12:'''''<i>&nbsp;Zones 0, 1, 2 and 3 in proximity to a bath-tub</i>


[[File:FigQn13.jpg|none]]
{{FigImage|DB431088_EN|svg|Q16|Definition of zones 0, 1, and 2 – Bath tub complementary examples}}
'''''Fig. Q13:'''''<i>&nbsp;Zones 0, 1, 2 and 3 in proximity of a shower with basin</i>


[[File:FigQn14.jpg|none]]
{{FigImage|DB431089_EN|svg|Q17|Definition of zones 0, 1, and 2 - shower without basin complementary examples}}
'''''Fig. Q14:'''''<i>&nbsp;Zones 0, 1, 2 and 3 in proximity of a shower without basin</i>


[[File:FigQn15.jpg|none]]
== Requirements prescribed for each zone ==
'''''Fig. Q15:'''''<i>&nbsp;No switch or socket-outlet is permitted within 60 cm of the door opening of a shower cabinet</i>
The IEC 60364-7-701 provides the specific requirements for the different zones defined in [[#Classification of zones|classification of zones]], applicable to the equipments, circuits ...  


[[File:FigQn16.jpg|none]]
It is an international standard that has been achieved as a compromise between countries, considering their existing national standards and regulations, thus it includes a significant number of notes providing country specific requirements. It is thus difficult to share a simplified view of these requirements.
'''''Fig. QP16:'''''<i>&nbsp;Individual showers with dressing cubicles</i>


[[File:FigQn17.jpg|none]]
Therefore, what you see below is an overview of the requirements for each zone, based on French standard (NFC 15-100). Always refer to your national standards for the applicable local requirements.  
'''''Fig. Q17:'''''<i>&nbsp;Individual showers with separate individual dressing cubicles</i>


[[File:FigQn18.jpg|none]]
{{tb-start|id=Tab1428|num=Q18|title=Equipment IP required for each zone|cols=2}}
'''''Fig. Q18:'''''<i>&nbsp;Communal showers and common dressing room</i>
{| class="wikitable"
|-
! Zone || Equipment IP required
|-
| Zone 0 || IPX7
|-
| Zone 1 || IPX4{{tn|A}}
|-
| Zone 2 || IPX4
|}
{{tb-notes
|A= IPX5 for showers with horizontal water jets}}


Note: Classes of external influences (see Fig.Q46).
{{FigImage|DB431092|svg|Q19|Overview of the specific requirements for bathrooms and shower rooms (based on French NFC 15-100 standard) - refer to your local standard for actual and complete requirements|
Cells with a grey background indicate that such equipment is forbidden in this zone.<br>
'''[a]''' IPX5 for showers with horizontal water jets<br>
'''[b]''' Separation transformer of the circuit shall be installed outside zones 0..2<br>
'''[c]''' Outside zones 0..2, all circuits shall be protected by 30mA RCDs (or separation transformer, SELV or PELV)}}


== Equipotential bonding ==
see {{FigRef|Q20}}


==== Equipotential bonding  ====
{{FigImage|DB422880_EN|svg|Q20|Supplementary equipotential bonding in a bathroom}}
 
(see {{FigRef|Q19}})
 
[[File:FigQn19.jpg|none]]
'''''Fig. Q19:'''''<i>&nbsp;Supplementary equipotential bonding in a bathroom</i>
 
==== Requirements prescribed for each zone  ====
 
The table&nbsp; describes the application of the principles mentioned in the foregoing text and in other similar or related cases
 
[[ru:Элекстроустановка в ванных и душевых комнатах]]
[[zh:浴室电气安装]]

Latest revision as of 09:48, 22 June 2022

Bathrooms and shower rooms are areas of high risk, because of the very low resistance of the human body when wet or immersed in water.

Precaution to be taken are therefore correspondingly rigorous, and the regulations are more severe than those for most other locations.

The relevant international standard is IEC 60364-7-701, applicable to the electrical installations in locations containing a fixed bath (bath tub) or shower and to the surrounding zones. Refer to country specific standards (or deviations from the IEC requirements) whenever they exist.

Precautions to observe are based on three aspects:

  • The definition of zones, numbered 0, 1 and 2 in which the placement (or exclusion) of any electrical device is strictly limited or forbidden and, where permitted, the electrical and mechanical protection is prescribed
  • The strict adherence to the requirements prescribed for each zone
  • The establishment of an equipotential bond between all exposed and extraneous metal parts in the zones concerned.

Classification of zones

Sub-clause 701.30 of IEC 60364-7-701 defines the zones 0, 1 and 2, illustrated by the following figures for most common examples.

Refer to the standard for a more complete view.

Fig. Q15 – Definition of zones 0, 1 and 2 (global view)
Fig. Q16 – Definition of zones 0, 1, and 2 – Bath tub complementary examples
Fig. Q17 – Definition of zones 0, 1, and 2 - shower without basin complementary examples

Requirements prescribed for each zone

The IEC 60364-7-701 provides the specific requirements for the different zones defined in classification of zones, applicable to the equipments, circuits ...

It is an international standard that has been achieved as a compromise between countries, considering their existing national standards and regulations, thus it includes a significant number of notes providing country specific requirements. It is thus difficult to share a simplified view of these requirements.

Therefore, what you see below is an overview of the requirements for each zone, based on French standard (NFC 15-100). Always refer to your national standards for the applicable local requirements.

Fig. Q18 – Equipment IP required for each zone
Zone Equipment IP required
Zone 0 IPX7
Zone 1 IPX4[a]
Zone 2 IPX4
  1. ^ IPX5 for showers with horizontal water jets
Cells with a grey background indicate that such equipment is forbidden in this zone.
[a] IPX5 for showers with horizontal water jets
[b] Separation transformer of the circuit shall be installed outside zones 0..2
[c] Outside zones 0..2, all circuits shall be protected by 30mA RCDs (or separation transformer, SELV or PELV)
Fig. Q19 – Overview of the specific requirements for bathrooms and shower rooms (based on French NFC 15-100 standard) - refer to your local standard for actual and complete requirements

Equipotential bonding

see Fig. Q20

Fig. Q20 – Supplementary equipotential bonding in a bathroom