Protection of transformer and circuits: Difference between revisions

From Electrical Installation Guide
(Created page with '{{Menu_Connection_to_the_MV_utility_distribution_network}} <br> ===== General ===== The electrical equipment and circuits in a substation must be protected in order to avoid o…')
 
m (Text replacement - "\[\[ru:[^]]*\]\][ \r\n]*" to "")
 
(33 intermediate revisions by 11 users not shown)
Line 1: Line 1:
{{Menu_Connection_to_the_MV_utility_distribution_network}}
{{Menu_Connection_to_the_MV_utility_distribution_network}}__TOC__
<br>
The electrical equipment and circuits in a substation must be protected in order to limit the damages due to abnormal currents and over voltages.


===== General  =====
All equipment installed in a power electrical system have standardized ratings for short-time withstand current and short duration power frequency voltage. The role of the protections is to ensure that these withstand limits can never be exceeded, therefore clearing the faults as fast as possible.


The electrical equipment and circuits in a substation must be protected in order to avoid or to control damage due to abnormal currents and/or voltages. All equipment normally used in power system installations have standardized short-time withstand ratings for overcurrent and overvoltage. The role of protective scheme is to ensure that this withstand limits can never be exceeded. In general, this means that fault conditions must be cleared as fast as possible without missing to ensure coordination between protective devices upstream and downstream the equipement to be protected. This means, when there is a fault in a network, generally several protective devices see the fault at the same time but only one must act.<br>These devices may be:
In addition to this first requirement a system of protection must be selective. Selectivity means that any fault must be cleared by the device of current interruption (circuit breaker or fuses) being the nearest to the fault, even if the fault is detected by other protections associated with other interruption devices.


*Fuses which clear the faulty circuit directly or together with a mechanical tripping attachment, which opens an associated three-phase load-break switch
As an example for a short circuit occurring on the secondary side of a power transformer, only the circuit breaker installed on the secondary must trip. The circuit breaker installed on the primary side must remain closed. For a transformer protected with MV fuses, the fuses must not blow.
*Relays which act indirectly on the circuit-breaker coil


=====Transformer protection=====
They are typically two main devices able to interrupt fault currents, circuit breakers and fuses :
* The circuit breakers must be associated with a protection relay having three main functions:
**Measurement of the currents
**Detection of the faults
**Emission of a tripping order to the breaker
* The fuses blow under certain fault conditions.


'''Stresses due to the supply network'''<br>Some voltage surges can occur on the network such as&nbsp;:
== Transformer protection ==


*Atmospheric voltage surges
=== Stresses generated by the supply ===


Atmospheric voltage surges are caused by a stroke of lightning falling on or near an overhead line.  
Two types of over voltages may stress and even destroy a transformer:
* The lightning over voltages due to lightning stroke falling on or near an overhead line supplying the installation where the transformer is installed
* The switching over voltages generated by the opening of a circuit breaker or a load break switch for instance.


*Operating voltage surges
Depending of the application, protection against these two types of voltage surges may be necessary and are often ensured by means of Z<sub>n</sub>O surge arrestors preferably connected on the MV bushing of the transformer.


A sudden change in the established operating conditions in an electrical network causes transient phenomena to occur. This is generally a high frequency or damped oscillation voltage surge wave.<br>For both voltage surges, the overvoltage protection device generally used is a varistor (Zinc Oxide).<br>In most cases, voltage surges protection has no action on switchgear.
=== Stresses due to the load ===


'''Stresses due to the load''' <br>Overloading is frequently due to the coincidental demand of a number of small loads, or to an increase in the apparent power (kVA) demand of the installation, due to expansion in a factory, with consequent building extensions, and so on. Load increases raise the temperature of the wirings and of the insulation material. As a result, temperature increases involve a reduction of the equipment working life. Overload protection devices can be located on primary or secondary side of the transformer. The protection against overloading of a transformer is now provided by a digital relay which acts to trip the circuit-breaker on the secondary side of the transformer. Such relay, generally called thermal overload relay, artificially simulates the temperature, taking into account the time constant of the transformer. Some of them are able to take into account the effect of harmonic currents due to non linear loads (rectifiers, computer equipment, variable speed drives…).This type of relay is also able to predict the time before overload tripping and the waiting time after tripping. So, this information is very helpful to control load shedding operation.<br>In addition, larger oil-immersed transformers frequently have thermostats with two settings, one for alarm purposes and the other for tripping.<br>Dry-type transformers use heat sensors embedded in the hottest part of the windings insulation for alarm and tripping. <br>
A transformer overload is always due to an increase of the apparent power demand (kVA) of the installation. This increase of the demand can be the consequence of either a progressive adjunction of loads or an extension of the installation itself. The effect of any overload is an increase of the temperature of oil and windings of the transformer with a reduction of its life time.


'''Internal faults''' <br>The protection of transformers by transformer-mounted devices, against the effects of internal faults, is provided on transformers which are fitted with airbreathing conservator tanks by the classical Buchholz mechanical relay (see '''Fig. B4'''). These relays can detect a slow accumulation of gases which results from the arcing of incipient faults in the winding insulation or from the ingress of air due to an oil leak. This first level of detection generally gives an alarm, but if the condition deteriorates further, a second level of detection will trip the upstream circuit-breaker. <br>
The protection of a transformer against the overloads is performed by a dedicated protection usually called thermal overload relay. This type of protection simulates the temperature of the transformer’s windings. The simulation is based on the measure of the current and on the thermal time constant of the transformer. Some relays are able to take into account the effect of harmonics of the current due to non-linear loads such as rectifiers, computers, variable speed drives etc. This type of relay is also able to evaluate the remaining time before the emission of the tripping order and the time delay before re-energizing the transformer.


----
In addition, oil-filled transformers are equipped with thermostats controlling the temperature of the oil.


<br>[[Image:FigB4.jpg|left]]
Dry-type transformers use heat sensors embedded in the hottest part of the windings insulation.


<br>
Each of these devices (thermal relay, thermostat, heat sensors) generally provides two levels of detection:
* A low level used to generate an alarm to advise the maintenance staff,
* A high level to de-energize the transformer.


<br>
=== Internal faults in oil filled transformers ===


<br>
In oil filled transformers, internal faults may be classified as follow:
* Faults generating production of gases, mainly:
**Micro arcs resulting from incipient faults in the winding insulation
**Slow degradation of insulation materials
**Inter turns short circuit
* Faults generating internal over pressures with simultaneously high level of line over currents:
**Phase to earth short circuit
**Phase to Phase short circuit.


<br>
These faults may be the consequence of external lightning or switching over voltage.


<br>
Depending on the type of the transformer, there are two kinds of devices able to detect internal faults affecting an oil filled transformer.
* The '''Buchholz''' dedicated to the transformers equipped with an air breathing conservator (see {{FigRef|B16a}}).
: The buchholz is installed on the pipe connecting the tank of the transformer to the conservator (see {{FigRef|B16b}}). It traps the slow emissions of gasses and detect the flow back of oil due to the internal over pressures


<br>
{{Gallery|B16|Breathing transformer protected by buchholz||
|DB422024_EN.svg|a|Functioning principle
|PB116686.jpg|b|Transformer with conservator
}}


<br>
* The '''DGPT''' (Detection of Gas, Pressure and Temperature, see {{FigRef|B18}}) for the integral filled transformers (see {{FigRef|B17}}). This type of transformer is manufactured up to around10 MVA. The DGPT as the buchholz detects the emissions of gasses and the internal over pressures. In addition it monitors the temperature of the oil.


<br>


<br>
{{FigImage|PB116687|jpg|B17|Integral filled transformer}}


<br>
{{Gallery|B18|DGPT (Detection of Gas, Pressure and Temperature) protection relay for integral filled transformers||
|DGPT(b).jpg|a|Transformer protection relay (DGPT)
|DGPT(a).jpg|b|Contacts of the DGPT (cover removed)
}}


<br>
Concerning the monitoring of gas and temperature the buchholz and the DGPT provide two levels of detection:
* A low level used to generate an alarm to advise the maintenance staff,
* A high level to trip the switching device installed on the primary side of the transformer (circuit breaker or load break switch associated with fuses).


<br>
In addition, both the buchholz and the DGPT are suitable for oil leakages detection.


<br>
=== Overloads and internal faults in dry type transformers ===


<br>
(see {{FigRef|B19}} and {{FigRef|B20}})


'''''Fig. B4:'''&nbsp;Transformer with conservator tank''<br>
The dry type transformers are protected against over-heating due to possible downstream overloads by a dedicated relay monitoring thermal sensors embedded in the windings of the transformer (see {{FigRef|B20}}).


----
The internal faults, mainly inter turns and phase to earth short circuits occurring inside a dry type transformers are cleared either by the circuit breaker or the fuses installed on the primary side of the transformer. The tripping of the circuit breakers when used is ordered by the phase to phase and phase to earth over current protections.


An oil-surge detection feature of the Buchholz relay will trip the upstream circuit-breaker “instantaneously” if a surge of oil occurs in the pipe connecting the main tank with the conservator tank.<br>Such a surge can only occur due to the displacement of oil caused by a rapidly formed bubble of gas, generated by an arc of short-circuit current in the oil.<br>By specially designing the cooling-oil radiator elements to perform a concerting action, “totally filled” types of transformer as large as 10 MVA are now currently available.<br>Expansion of the oil is accommodated without an excessive rise in pressure by the “bellows” effect of the radiator elements. A full description of these transformers is given in Sub-clause "Choice of MV/LV transformer"&nbsp;(see '''Fig. B5'''). <br>
Inter turns faults need a dedicated attention:
* They generally generate moderate line over currents. As an example when 5 % of a HV winding are short circuited the line current of the transformer does not exceed 2 In, for a short circuit affecting 10 % of the winding the line current is limited around 3 In.
* Fuses are not appropriate to clear properly such currents
* Dry type transformers are not equipped with additional protection devices such as DGPT dedicated to internal faults detection.
: Hence, internal faults generating low level of line over current may not be safely cleared by fuses. Protection by means of over current relay with adequate characteristic and settings is preferred (Schneider Electric VIP relay range for example).


----
{{FigImage|PB116688|jpg|B19|Dry type transformer}}


<br>[[Image:FigB5.jpg|left]]
{{FigImage|Thermal_relay_(Ziehl)|jpg|B20|Thermal relay for protection of dry type transformer (Ziehl)}}


<br>
=== Selectivity between the protective devices upstream and downstream of the transformer ===


<br>
It is a common practice to ensure the selectivity between the MV circuit breaker or fuses installed on the primary side of a transformer and the LV circuit breaker.


<br>
The characteristics of the protection ordering the tripping or the MV circuit breaker or the operating curves of the fuses when used must be such as in case of downstream fault the LV circuit breaker only trips. The MV circuit breaker must remain closed or the fuse must not blow.


<br>
The tripping curves of MV fuses, MV protection and LV circuit breakers are given by graphs giving the operating time as a function of the current.


<br>
The curves are in general inverse-time type. LV circuit breakers have an abrupt discontinuity which defines the limit of the instantaneous action.


<br>
Typical curves are shown in {{FigRef|B21}}.


<br>
=== Selectivity between LV circuit breaker and MV fuses ===


<br>
(see {{FigRef|B21}} and {{FigRef|B22}})


<br>
* All parts of the MV fuse curve must be above and to the right of the LV CB curve.
* In order to leave the fuses unaffected (i.e. undamaged), the two following conditions must be satisfied:
**All parts of the minimum pre-arcing fuse curve must be shifted to the right of the LV CB curve by a factor of 1.35 or more.<br>Example: where, at time T, the CB curve passes through a point corresponding to 100 A, the fuse curve at the same time T must pass through a point corresponding to 135 A, or more, and so on.
**All parts of the fuse curve must be above the CB curve by a factor of 2 or more<br>Example: where, at a current level I the CB curve passes through a point corresponding to 1.5 seconds, the fuse curve at the same current level I must pass through a point corresponding to 3 seconds, or more, etc.


<br>
The factors 1.35 and 2 are based on the maximum manufacturing tolerances given for MV fuses and LV circuit breakers.


<br>
In order to compare the two curves, the MV currents must be converted to the equivalent LV currents, or vice-versa.


<br>
{{FigImage|DB422028_EN|svg|B21|Selectivity between MV fuse operation and  LV circuit breaker tripping, for transformer protection}}


<br><br>'''''Fig. B5:''' Totally filled transformer'' <br>
{{FigImage|DB422029_EN|svg|B22|MV fuse and LV circuit breaker configuration}}


----
=== Selectivity between LV circuit breaker and MV circuit breaker ===


Evidently the Buchholz devices mentioned above cannot be applied to this design; a modern counterpart has been developed however, which measures:
* All parts of the minimum MV circuit breaker curve must be shifted to the right of the LV CB curve by a factor of 1.35 or more:
** Example: where, at time T, the LV CB curve passes through a point corresponding to 100 A, the MV CB curve at the same time T must pass through a point corresponding to 135 A, or more, and so on.
* All parts of the MV CB curve must be above the LV CB curve. The time difference between the two curves must be 0.3 s at least for any value of the current.


*The accumulation of gas
The factors 1.35 and 0.3 s are based on the maximum manufacturing tolerances given for MV current transformers, MV protection relay and LV circuit breakers.
*Overpressure
*Overtemperature
 
The first two conditions trip the upstream circuit-breaker, and the third condition trips the downstream circuit-breaker of the transformer.
 
'''Internal phase-to-phase short-circuit<br>'''Internal phase-to-phase short-circuit must be detected and cleared by:
 
*3 fuses on the primary side of the tranformer or
*An overcurrent relay that trips a circuit-breaker upstream of the transformer
 
'''Internal phase-to-earth short-circuit''' <br>This is the most common type of internal fault. It must be detected by an earth fault relay. Earth fault current can be calculated with the sum of the 3 primary phase currents (if 3 current transformers are used) or by a specific core current transformer.<br>If a great sensitivity is needed, specific core current transformer will be prefered. In such a case, a two current transformers set is sufficient (see '''Fig. B6''').<br>
 
----
 
<br>[[Image:FigB6.jpg|left]]
 
<br>
 
<br>
 
<br>
 
<br>
 
<br>
 
<br>
 
<br>
 
<br><br><br><br><br><br><br>'''''Fig. B6:''' Protection against earth fault on the MV winding'' <br>
 
----
 
===== Protection of circuits  =====
 
The protection of the circuits downstream of the transformer must comply with the IEC 60364 requirements.<br>
 
===== Discrimination between the protective devices upstream and downstream of the transformer  =====
 
The consumer-type substation with LV metering requires discriminative operation between the MV fuses or MV circuit-breaker and the LV circuit-breaker or fuses. The rating of the MV fuses will be chosen according to the characteristics of the transformer.<br>The tripping characteristics of the LV circuit-breaker must be such that, for an overload or short-circuit condition downstream of its location, the breaker will trip sufficiently quickly to ensure that the MV fuses or the MV circuit-breaker will not be adversely affected by the passage of overcurrent through them.<br>The tripping performance curves for MV fuses or MV circuit-breaker and LV circuit-breakers are given by graphs of time-to-operate against current passing through them. Both curves have the general inverse-time/current form (with an abrupt discontinuity in the CB curve at the current value above which “instantaneous” tripping occurs).<br>These curves are shown typically in '''Figure B7'''.<br>
 
----
 
<br>[[Image:FigB7.jpg|left]]<br>
 
<br>
 
<br>
 
<br>
 
<br>
 
<br>
 
<br>
 
<br><br>
 
<br>
 
<br>
 
<br>
 
<br>
 
<br>
 
<br><br><br>'''''Fig. B7:&nbsp;'''Discrimination between MV fuse operation and LV circuit-breaker tripping, for transformer protection'' <br>
 
----
 
*In order to achieve discrimination (see '''Fig. B8'''):
 
All parts of the fuse or MV circuit-breaker curve must be above and to the right of the CB curve.
 
----
 
<br>[[Image:FigB8.jpg|left]]<br>
 
<br>
 
<br>
 
'''''Fig. B8:&nbsp;'''MV fuse and LV circuit-breaker configuration'' <br>
 
----
 
*In order to leave the fuses unaffected (i.e. undamaged):
 
All parts of the minimum pre-arcing fuse curve must be located to the right of the CB curve by a factor of 1.35 or more (e.g. where, at time T, the CB curve passes through a point corresponding to 100 A, the fuse curve at the same time T must pass through a point corresponding to 135 A, or more, and so on...) and, all parts of the fuse curve must be above the CB curve by a factor of 2 or more (e.g. where, at a current level I the CB curve passes through a point corresponding to 1.5 seconds, the fuse curve at the same current level I must pass through a point corresponding to 3 seconds, or more, etc.).<br>The factors 1.35 and 2 are based on standard maximum manufacturing tolerances for MV fuses and LV circuit-breakers.<br>In order to compare the two curves, the MV currents must be converted to the equivalent LV currents, or vice-versa.<br>Where a LV fuse-switch is used, similar separation of the characteristic curves of the MV and LV fuses must be respected.
 
*In order to leave the MV circuit-breaker protection untripped:
 
All parts of the minimum MV CB curve must be located to the right of the LV CB curve by a factor of 1.35 or more (e.g. where, at time T, the LV CB curve passes through a point corresponding to 100 A, the MV CB curve at the same time T must pass through a point corresponding to 135 A, or more, and so on...) and, all parts of the MV CB curve must be above the LV CB curve (time of LV CB curve must be less or equal than MV&nbsp;CB curves minus 0.3 s)<br>The factors 1.35 and 0.3 s are based on standard maximum manufacturing tolerances for MV current transformers, MV protection relay and LV circuit-breakers.<br>In order to compare the two curves, the MV currents must be converted to the equivalent LV currents, or vice-versa.<br>
 
===== Choice of protective device on the primary side of the transformer  =====
 
As explained before, for low reference current, the protection may be by fuses or by circuit-breaker.<br>When the reference current is high, the protection will be achieved by circuit-breaker.<br>Protection by circuit-breaker provides a more sensitive transformer protection compared with fuses. The implementation of additional protections (earth fault protection, thermal overload protection) is easier with circuit-breakers. <br><br>

Latest revision as of 09:48, 22 June 2022

The electrical equipment and circuits in a substation must be protected in order to limit the damages due to abnormal currents and over voltages.

All equipment installed in a power electrical system have standardized ratings for short-time withstand current and short duration power frequency voltage. The role of the protections is to ensure that these withstand limits can never be exceeded, therefore clearing the faults as fast as possible.

In addition to this first requirement a system of protection must be selective. Selectivity means that any fault must be cleared by the device of current interruption (circuit breaker or fuses) being the nearest to the fault, even if the fault is detected by other protections associated with other interruption devices.

As an example for a short circuit occurring on the secondary side of a power transformer, only the circuit breaker installed on the secondary must trip. The circuit breaker installed on the primary side must remain closed. For a transformer protected with MV fuses, the fuses must not blow.

They are typically two main devices able to interrupt fault currents, circuit breakers and fuses :

  • The circuit breakers must be associated with a protection relay having three main functions:
    • Measurement of the currents
    • Detection of the faults
    • Emission of a tripping order to the breaker
  • The fuses blow under certain fault conditions.

Transformer protection

Stresses generated by the supply

Two types of over voltages may stress and even destroy a transformer:

  • The lightning over voltages due to lightning stroke falling on or near an overhead line supplying the installation where the transformer is installed
  • The switching over voltages generated by the opening of a circuit breaker or a load break switch for instance.

Depending of the application, protection against these two types of voltage surges may be necessary and are often ensured by means of ZnO surge arrestors preferably connected on the MV bushing of the transformer.

Stresses due to the load

A transformer overload is always due to an increase of the apparent power demand (kVA) of the installation. This increase of the demand can be the consequence of either a progressive adjunction of loads or an extension of the installation itself. The effect of any overload is an increase of the temperature of oil and windings of the transformer with a reduction of its life time.

The protection of a transformer against the overloads is performed by a dedicated protection usually called thermal overload relay. This type of protection simulates the temperature of the transformer’s windings. The simulation is based on the measure of the current and on the thermal time constant of the transformer. Some relays are able to take into account the effect of harmonics of the current due to non-linear loads such as rectifiers, computers, variable speed drives etc. This type of relay is also able to evaluate the remaining time before the emission of the tripping order and the time delay before re-energizing the transformer.

In addition, oil-filled transformers are equipped with thermostats controlling the temperature of the oil.

Dry-type transformers use heat sensors embedded in the hottest part of the windings insulation.

Each of these devices (thermal relay, thermostat, heat sensors) generally provides two levels of detection:

  • A low level used to generate an alarm to advise the maintenance staff,
  • A high level to de-energize the transformer.

Internal faults in oil filled transformers

In oil filled transformers, internal faults may be classified as follow:

  • Faults generating production of gases, mainly:
    • Micro arcs resulting from incipient faults in the winding insulation
    • Slow degradation of insulation materials
    • Inter turns short circuit
  • Faults generating internal over pressures with simultaneously high level of line over currents:
    • Phase to earth short circuit
    • Phase to Phase short circuit.

These faults may be the consequence of external lightning or switching over voltage.

Depending on the type of the transformer, there are two kinds of devices able to detect internal faults affecting an oil filled transformer.

  • The Buchholz dedicated to the transformers equipped with an air breathing conservator (see Fig. B16a).
The buchholz is installed on the pipe connecting the tank of the transformer to the conservator (see Fig. B16b). It traps the slow emissions of gasses and detect the flow back of oil due to the internal over pressures
  • The DGPT (Detection of Gas, Pressure and Temperature, see Fig. B18) for the integral filled transformers (see Fig. B17). This type of transformer is manufactured up to around10 MVA. The DGPT as the buchholz detects the emissions of gasses and the internal over pressures. In addition it monitors the temperature of the oil.


Fig. B17 – Integral filled transformer

Concerning the monitoring of gas and temperature the buchholz and the DGPT provide two levels of detection:

  • A low level used to generate an alarm to advise the maintenance staff,
  • A high level to trip the switching device installed on the primary side of the transformer (circuit breaker or load break switch associated with fuses).

In addition, both the buchholz and the DGPT are suitable for oil leakages detection.

Overloads and internal faults in dry type transformers

(see Fig. B19 and Fig. B20)

The dry type transformers are protected against over-heating due to possible downstream overloads by a dedicated relay monitoring thermal sensors embedded in the windings of the transformer (see Fig. B20).

The internal faults, mainly inter turns and phase to earth short circuits occurring inside a dry type transformers are cleared either by the circuit breaker or the fuses installed on the primary side of the transformer. The tripping of the circuit breakers when used is ordered by the phase to phase and phase to earth over current protections.

Inter turns faults need a dedicated attention:

  • They generally generate moderate line over currents. As an example when 5 % of a HV winding are short circuited the line current of the transformer does not exceed 2 In, for a short circuit affecting 10 % of the winding the line current is limited around 3 In.
  • Fuses are not appropriate to clear properly such currents
  • Dry type transformers are not equipped with additional protection devices such as DGPT dedicated to internal faults detection.
Hence, internal faults generating low level of line over current may not be safely cleared by fuses. Protection by means of over current relay with adequate characteristic and settings is preferred (Schneider Electric VIP relay range for example).
Fig. B19 – Dry type transformer
Fig. B20 – Thermal relay for protection of dry type transformer (Ziehl)

Selectivity between the protective devices upstream and downstream of the transformer

It is a common practice to ensure the selectivity between the MV circuit breaker or fuses installed on the primary side of a transformer and the LV circuit breaker.

The characteristics of the protection ordering the tripping or the MV circuit breaker or the operating curves of the fuses when used must be such as in case of downstream fault the LV circuit breaker only trips. The MV circuit breaker must remain closed or the fuse must not blow.

The tripping curves of MV fuses, MV protection and LV circuit breakers are given by graphs giving the operating time as a function of the current.

The curves are in general inverse-time type. LV circuit breakers have an abrupt discontinuity which defines the limit of the instantaneous action.

Typical curves are shown in Fig. B21.

Selectivity between LV circuit breaker and MV fuses

(see Fig. B21 and Fig. B22)

  • All parts of the MV fuse curve must be above and to the right of the LV CB curve.
  • In order to leave the fuses unaffected (i.e. undamaged), the two following conditions must be satisfied:
    • All parts of the minimum pre-arcing fuse curve must be shifted to the right of the LV CB curve by a factor of 1.35 or more.
      Example: where, at time T, the CB curve passes through a point corresponding to 100 A, the fuse curve at the same time T must pass through a point corresponding to 135 A, or more, and so on.
    • All parts of the fuse curve must be above the CB curve by a factor of 2 or more
      Example: where, at a current level I the CB curve passes through a point corresponding to 1.5 seconds, the fuse curve at the same current level I must pass through a point corresponding to 3 seconds, or more, etc.

The factors 1.35 and 2 are based on the maximum manufacturing tolerances given for MV fuses and LV circuit breakers.

In order to compare the two curves, the MV currents must be converted to the equivalent LV currents, or vice-versa.

Fig. B21 – Selectivity between MV fuse operation and LV circuit breaker tripping, for transformer protection
Fig. B22 – MV fuse and LV circuit breaker configuration

Selectivity between LV circuit breaker and MV circuit breaker

  • All parts of the minimum MV circuit breaker curve must be shifted to the right of the LV CB curve by a factor of 1.35 or more:
    • Example: where, at time T, the LV CB curve passes through a point corresponding to 100 A, the MV CB curve at the same time T must pass through a point corresponding to 135 A, or more, and so on.
  • All parts of the MV CB curve must be above the LV CB curve. The time difference between the two curves must be 0.3 s at least for any value of the current.

The factors 1.35 and 0.3 s are based on the maximum manufacturing tolerances given for MV current transformers, MV protection relay and LV circuit breakers.

Share