== Transformers  ==
== Transformers  ==


A two-winding transformer included on the upstream side of the static contactor of circuit 2 allows:  
A two-winding transformer included on the upstream side of the static contactor of circuit 2 allows:  
*A change of voltage level when the power network voltage is different to that of the load  
*A change of voltage level when the power network voltage is different to that of the load  
*A change of system of earthing between the networks  
*A change of system of earthing between the networks  
*Moreover, such a transformer :  
Moreover, such a transformer:  
*Reduces the short-circuit current level on the secondary, (i.e load) side compared with that on the power network side  
*Reduces the short-circuit current level on the secondary, (i.e load) side compared with that on the power network side  
*Prevents third harmonic currents which may be present on the secondary side from passing into the power-system network, providing that the primary winding is connected in delta.
*Prevents third harmonic currents which may be present on the secondary side from passing into the power-system network, providing that the primary winding is connected in delta.
Line 13: Line 11:
== Anti-harmonic filter  ==
== Anti-harmonic filter  ==


The UPS system includes a battery charger which is controlled by thyristors or transistors. The resulting regularly-chopped current cycles “generate” harmonic components in the power-supply network.<br>These indesirable components are filtered at the input of the rectifier and for most cases this reduces the harmonic current level sufficiently for all practical purposes.<br>In certain specific cases however, notably in very large installations, an additional filter circuit may be necessary.<br>For example when&nbsp;:
The UPS system includes a battery charger which is controlled by thyristors or transistors. The resulting regularly-chopped current cycles “generate” harmonic components in the power-supply network.
 
These indesirable components are filtered at the input of the rectifier and for most cases this reduces the harmonic current level sufficiently for all practical purposes.
 
In certain specific cases however, notably in very large installations, an additional filter circuit may be necessary.


For example when:
*The power rating of the UPS system is large relative to the MV/LV transformer suppllying it  
*The power rating of the UPS system is large relative to the MV/LV transformer suppllying it  
*The LV busbars supply loads which are particularly sensitive to harmonics  
*The LV busbars supply loads which are particularly sensitive to harmonics  
Line 21: Line 24:
In such cases, the manufacturer of the UPS system should be consulted  
In such cases, the manufacturer of the UPS system should be consulted  


'''Communication equipment'''
=== Communication equipment ===
 
Communication with equipment associated with computer systems may entail the need for suitable facilities within the UPS system. Such facilities may be incorporated in an original design (see '''Fig. N30a'''&nbsp;), or added to existing systems on request <br>(see '''Fig. N30b ''').
 
----
 
[[File:FigN30a.jpg|none]]
'''''Fig. N30a:'''''<i>  Ready-to-use UPS unit (with DIN module)</i>


----
Communication with equipment associated with computer systems may entail the need for suitable facilities within the UPS system. Such facilities may be incorporated in an original design (see {{FigRef|N31}}) , or added to existing systems on request (see {{FigRef|N32}}).


[[File:FigN30b.jpg|none]]
{{FigImage|PB116809|jpg|N31|Ready-to-use UPS unit (with DIN module)}}
'''''Fig. N30b:&nbsp;'''''<i>UPS unit achieving disponibility and quality of computer system power supply</i>


[[ru:Дополнительное оборудование для ИБП]]
{{FigImage|PB116810|jpg|N32|UPS unit achieving disponibility and quality of computer system power supply}}
[[zh:UPS配套设备]]

Latest revision as of 09:49, 22 June 2022

Transformers

A two-winding transformer included on the upstream side of the static contactor of circuit 2 allows:

  • A change of voltage level when the power network voltage is different to that of the load
  • A change of system of earthing between the networks

Moreover, such a transformer:

  • Reduces the short-circuit current level on the secondary, (i.e load) side compared with that on the power network side
  • Prevents third harmonic currents which may be present on the secondary side from passing into the power-system network, providing that the primary winding is connected in delta.

Anti-harmonic filter

The UPS system includes a battery charger which is controlled by thyristors or transistors. The resulting regularly-chopped current cycles “generate” harmonic components in the power-supply network.

These indesirable components are filtered at the input of the rectifier and for most cases this reduces the harmonic current level sufficiently for all practical purposes.

In certain specific cases however, notably in very large installations, an additional filter circuit may be necessary.

For example when:

  • The power rating of the UPS system is large relative to the MV/LV transformer suppllying it
  • The LV busbars supply loads which are particularly sensitive to harmonics
  • A diesel (or gas-turbine, etc,) driven alternator is provided as a standby power supply

In such cases, the manufacturer of the UPS system should be consulted

Communication equipment

Communication with equipment associated with computer systems may entail the need for suitable facilities within the UPS system. Such facilities may be incorporated in an original design (see Fig. N31) , or added to existing systems on request (see Fig. N32).

Fig. N31 – Ready-to-use UPS unit (with DIN module)
Fig. N32 – UPS unit achieving disponibility and quality of computer system power supply