The consumer substation with MV metering: Difference between revisions
From Electrical Installation Guide
(Text updated (guide 2015)) |
m (Text replacement - "\[\[ru:[^]]*\]\][ \r\n]*" to "") |
||
(10 intermediate revisions by 4 users not shown) | |||
Line 1: | Line 1: | ||
{{Menu_Connection_to_the_MV_utility_distribution_network}} | {{Menu_Connection_to_the_MV_utility_distribution_network}} | ||
== Definition == | == Definition == | ||
A consumer substation with MV metering is an electrical installation connected to a utility supply system at a nominal voltage usually between 1 kV - 35 kV, which for example may supply: | A consumer substation with MV metering is an electrical installation connected to a utility supply system at a nominal voltage usually between 1 kV - 35 kV, which for example may supply: | ||
* A single MV/LV transformer exceeding generally 1250 kVA | * A single MV/LV transformer exceeding generally 1250 kVA | ||
* Several MV/LV transformers | * Several MV/LV transformers | ||
Line 12: | Line 10: | ||
For example a substation may: | For example a substation may: | ||
* Include one single room containing the MV switchboard, the metering panel, the transformer(s) and the low voltage main distribution board(s), | * Include one single room containing the MV switchboard, the metering panel, the transformer(s) and the low voltage main distribution board(s), | ||
* Supply one or several transformers, each installed in a dedicated room including the corresponding main LV distribution switchboard | * Supply one or several transformers, each installed in a dedicated room including the corresponding main LV distribution switchboard | ||
* Supply one or several secondary MV/LV substations. | * Supply one or several secondary MV/LV substations. | ||
{{Section-TOC}} | |||
{{ | |||
}} | |||
Latest revision as of 07:33, 4 August 2022
Definition
A consumer substation with MV metering is an electrical installation connected to a utility supply system at a nominal voltage usually between 1 kV - 35 kV, which for example may supply:
- A single MV/LV transformer exceeding generally 1250 kVA
- Several MV/LV transformers
- One or several MV/LV secondary substations.
The single line diagram and the layout of a substation with MV metering depend on the complexity of the installation and the presence of secondary substations.
For example a substation may:
- Include one single room containing the MV switchboard, the metering panel, the transformer(s) and the low voltage main distribution board(s),
- Supply one or several transformers, each installed in a dedicated room including the corresponding main LV distribution switchboard
- Supply one or several secondary MV/LV substations.