SPD and protection device coordination table: Difference between revisions

From Electrical Installation Guide
(Cleanup_2016)
(Updated the coordination table image + text modifications + link to the related document for latest version)
 
(8 intermediate revisions by 3 users not shown)
Line 1: Line 1:
{{Menu_Overvoltage_protection}}
{{Menu_Overvoltage_protection}}__TOC__
 
The table in {{FigureRef|J37}} below shows the coordination of disconnecting circuit breakers (external SCPD) for Type 1 and 2 SPDs of the Schneider Electric brand for all levels of short-circuit currents (always refer to the latest tables provided by manufacturers).
__TOC__
 
The table in {{FigureRef|J37}} below shows the coordination of disconnecting circuit breakers (external SCPD) for Type 1 and 2 SPDs of the Schneider Electric brand for all levels of short-circuit currents.


Coordination between SPD and its disconnecting circuit breakers, indicated and guaranteed by Schneider Electric, ensures reliable protection (lightning wave withstand, reinforced protection of impedant short-circuit currents, etc.)  
Coordination between SPD and its disconnecting circuit breakers, indicated and guaranteed by Schneider Electric, ensures reliable protection (lightning wave withstand, reinforced protection of impedant short-circuit currents, etc.)  


{{FigImage|DB422496_EN|svg|J37|Coordination table between SPDs and their disconnecting circuit breakers of the Schneider Electric brand|
{{FigImage|DB422496_EN|svg|J37|Example of coordination table between SPDs and their disconnecting circuit breakers (Schneider Electric brand). Always refer to [https://www.se.com/ww/en/download/document/CA903014E/ the latest table].}}
All circuit breakers are C curve'' <br>
(*) Compact NSX in this case is for lightning impulse current withstand.}}


== Coordination with upstream protection devices ==
== Coordination with upstream protection devices ==
Line 15: Line 10:
=== Coordination with overcurrent protection devices ===
=== Coordination with overcurrent protection devices ===


In an electrical installation, the external SCPD is an apparatus identical to the protection apparatus: this makes it possible to apply '''discrimination and cascading '''techniques for technical and economic optimization of the protection plan.  
In an electrical installation, the external SCPD is an apparatus identical to the protection apparatus: this makes it possible to apply '''selectivity and cascading '''techniques for technical and economic optimization of the protection plan.


===Coordination with residual current devices===
===Coordination with residual current devices===


If the SPD is installed downstream of an earth leakage protection device, the latter should be of the "si" or selective type with an immunity to pulse currents of at least 3 kA (8/20 μs current wave).  
If the SPD is installed downstream of an earth leakage protection device, the latter should be of the "si" or selective type with an immunity to pulse currents of at least 3 kA (8/20 μs current wave).
 
[[zh:SPD和外部SCPD配对表]]

Latest revision as of 11:25, 21 May 2024

The table in Figure J37 below shows the coordination of disconnecting circuit breakers (external SCPD) for Type 1 and 2 SPDs of the Schneider Electric brand for all levels of short-circuit currents (always refer to the latest tables provided by manufacturers).

Coordination between SPD and its disconnecting circuit breakers, indicated and guaranteed by Schneider Electric, ensures reliable protection (lightning wave withstand, reinforced protection of impedant short-circuit currents, etc.)

Fig. J37 – Example of coordination table between SPDs and their disconnecting circuit breakers (Schneider Electric brand). Always refer to the latest table.

Coordination with upstream protection devices

Coordination with overcurrent protection devices

In an electrical installation, the external SCPD is an apparatus identical to the protection apparatus: this makes it possible to apply selectivity and cascading techniques for technical and economic optimization of the protection plan.

Coordination with residual current devices

If the SPD is installed downstream of an earth leakage protection device, the latter should be of the "si" or selective type with an immunity to pulse currents of at least 3 kA (8/20 μs current wave).

Share