EMC guidelines PDF download: Difference between revisions

From Electrical Installation Guide
(Created page with 'The system earthing arrangement must be properly selected to ensure the safety of life and property. The behaviour of the different systems with respect to EMC consideration…')
 
No edit summary
Line 43: Line 43:


----
----
  
When an installation includes high-power equipment (motors, air-conditioning, lifts, power electronics, etc.), it is advised to install one or more transformers specifically for these systems. Electrical distribution must be organised in a star system and all outgoing circuits must exit the main low-voltage switchboard (MLVS).
Electronic systems (control/monitoring, regulation, measurement instruments, etc.) must be supplied by a dedicated transformer in a TN-S system.
'''Figure R2''' below illustrate these recommendations.
----
 
'''''Fig. R2:''' Recommendations of separated distributions''

Revision as of 04:25, 23 February 2010

The system earthing arrangement must be properly selected to ensure the safety of life and property. The behaviour of the different systems with respect to EMC considerations must be taken into account. Figure R1 below presents a summary of their main characteristics.
European standards (see EN 50174-2 § 6.4 and EN 50310 § 6.3) recommend the TN-S system which causes the fewest EMC problems for installations comprising information-technology equipment (including telecom equipment).



   TT TN-S IT TN-C
Safety of persons Good
RCD mandatory
Good
Continuity of the PE conductor must be ensured throughout the installation
Safety of property Good Poor Good Poor
Medium fault current
(< a few dozenamperes)
High fault  current
(around 1 kA)
Low current for first fault
(< a few dozen mA),
but high for second fault
High fault current
(around 1 kA)
Availability of energy Good Good Excellent Good
EMC behaviour Good
- Risk of overvoltages    
- Equipotential problems
- Need to manage
devices with high leakage currents
Excellent
- Few equipotential problems
- Need to manage devices with high leakage currents
- High fault currents
(transient disturbances)
Poor (to be avoided)
- Risk of overvoltages
- Common-mode filters and surge    arrestors must handle the phase- to-phase voltages
- RCDs subject to nuisance tripping if common-mode capacitors are present
- Equivalent to TN system for second fault
Poor
(should never be used)
- Neutral and PE are
the same
- Circulation of disturbed
currents in exposed
conductive parts (high
magnetic-field radiation)
- High fault currents
(transient disturbances)               

Fig. R1: Main characteristics of system earthing


When an installation includes high-power equipment (motors, air-conditioning, lifts, power electronics, etc.), it is advised to install one or more transformers specifically for these systems. Electrical distribution must be organised in a star system and all outgoing circuits must exit the main low-voltage switchboard (MLVS). Electronic systems (control/monitoring, regulation, measurement instruments, etc.) must be supplied by a dedicated transformer in a TN-S system. Figure R2 below illustrate these recommendations.


Fig. R2: Recommendations of separated distributions

Share