Instructions for use of MV equipment: Difference between revisions

From Electrical Installation Guide
(Created page with '{{Menu_Connection_to_the_MV_utility_distribution_network}} <br> The purpose of this chapter is to provide general guidelines on how to avoid or greatly reduce MV equipment degrad…')
 
No edit summary
Line 3: Line 3:
The purpose of this chapter is to provide general guidelines on how to avoid or greatly reduce MV equipment degradation on sites exposed to humidity and pollution.  
The purpose of this chapter is to provide general guidelines on how to avoid or greatly reduce MV equipment degradation on sites exposed to humidity and pollution.  


===== Normal service conditions for indoor MV equipment<br>  =====
== Normal service conditions for indoor MV equipment<br>  ==


All MV equipments comply with specific standards and with the IEC 62271-1 standard “Common specifications for high-voltage switchgear and controlgear”, which defines the normal conditions for the installation and use of such equipment.<br>For instance, regarding humidity, the standard mentions:<br>The conditions of humidity are as follows:  
All MV equipments comply with specific standards and with the IEC 62271-1 standard “Common specifications for high-voltage switchgear and controlgear”, which defines the normal conditions for the installation and use of such equipment.<br>For instance, regarding humidity, the standard mentions:<br>The conditions of humidity are as follows:  
Line 22: Line 22:
----
----


===== Remedial measures for condensation problems  =====
== Remedial measures for condensation problems  ==


*Carefully design or adapt substation ventilation.  
*Carefully design or adapt substation ventilation.  
Line 30: Line 30:
*Make sure cabling is in accordance with applicable rules.
*Make sure cabling is in accordance with applicable rules.


===== Remedial measures for pollution problems  =====
== Remedial measures for pollution problems  ==


*Equip substation ventilation openings with chevron-type baffles to reduce entry of dust and pollution.  
*Equip substation ventilation openings with chevron-type baffles to reduce entry of dust and pollution.  
Line 38: Line 38:
*Regularly clean all traces of pollution from metal and insulating parts.
*Regularly clean all traces of pollution from metal and insulating parts.


===== Ventilation<br>  =====
== Ventilation<br>  ==


Substation ventilation is generally required to dissipate the heat produced by transformers and to allow drying after particularly wet or humid periods.<br>However, a number of studies have shown that excessive ventilation can drastically increase condensation.<br>Ventilation should therefore be kept to the minimum level required.<br>Furthermore, ventilation should never generate sudden temperature variations that can cause the dew point to be reached.<br>For this reason:<br>Natural ventilation should be used whenever possible. If forced ventilation is necessary, the fans should operate continuously to avoid temperature fluctuations.<br>Guidelines for sizing the air entry and exit openings of substations are presented hereafter.<br>  
Substation ventilation is generally required to dissipate the heat produced by transformers and to allow drying after particularly wet or humid periods.<br>However, a number of studies have shown that excessive ventilation can drastically increase condensation.<br>Ventilation should therefore be kept to the minimum level required.<br>Furthermore, ventilation should never generate sudden temperature variations that can cause the dew point to be reached.<br>For this reason:<br>Natural ventilation should be used whenever possible. If forced ventilation is necessary, the fans should operate continuously to avoid temperature fluctuations.<br>Guidelines for sizing the air entry and exit openings of substations are presented hereafter.<br>  


===== Calculation methods<br>  =====
== Calculation methods<br>  ==


A number of calculation methods are available to estimate the required size of substation ventilation openings, either for the design of new substations or the adaptation of existing substations for which condensation problems have occurred.<br>The basic method is based on transformer dissipation.<br>The required ventilation opening surface areas S and S’ can be estimated using the following formulas: <br><br><math>\mbox{S}=\frac{1.8\times10^{-4}\mbox{P}}{\sqrt\mbox{H}}</math> and &nbsp; <math>\mbox{S}^'={1.10\times\mbox{S}}</math> <br>  
A number of calculation methods are available to estimate the required size of substation ventilation openings, either for the design of new substations or the adaptation of existing substations for which condensation problems have occurred.<br>The basic method is based on transformer dissipation.<br>The required ventilation opening surface areas S and S’ can be estimated using the following formulas: <br><br><math>\mbox{S}=\frac{1.8\times10^{-4}\mbox{P}}{\sqrt\mbox{H}}</math> and &nbsp; <math>\mbox{S}^'={1.10\times\mbox{S}}</math> <br>  
Line 68: Line 68:
The understanding and the optimization of the attached physical phenomena are subject to precise flow studies, based on the fluid dynamics laws, and realized with specific analytic software.<br>'''Example:<br>'''Transformer dissipation = 7,970 W<br>LV switchgear dissipation = 750 W<br>MV switchgear dissipation = 300 W<br>The height between ventilation opening mid-points is 1.5 m.<br>Calculation:<br>Dissipated Power P = 7,970 + 750 + 300 = 9,020 W<br><br><math>\mbox{S}=\frac{1.8\times10^{-4}P}{\sqrt\mbox{1.5}}=1.32\mbox{m}^2</math> and &nbsp; <math>\mbox{S}^'={1.1\times1.32}=1.46\mbox{m}^2</math>
The understanding and the optimization of the attached physical phenomena are subject to precise flow studies, based on the fluid dynamics laws, and realized with specific analytic software.<br>'''Example:<br>'''Transformer dissipation = 7,970 W<br>LV switchgear dissipation = 750 W<br>MV switchgear dissipation = 300 W<br>The height between ventilation opening mid-points is 1.5 m.<br>Calculation:<br>Dissipated Power P = 7,970 + 750 + 300 = 9,020 W<br><br><math>\mbox{S}=\frac{1.8\times10^{-4}P}{\sqrt\mbox{1.5}}=1.32\mbox{m}^2</math> and &nbsp; <math>\mbox{S}^'={1.1\times1.32}=1.46\mbox{m}^2</math>


===== Ventilation opening locations<br>  =====
== Ventilation opening locations<br>  ==


To favour evacuation of the heat produced by the transformer via natural convection, ventilation openings should be located at the top and bottom of the wall near the transformer. The heat dissipated by the MV switchboard is negligible.<br>To avoid condensation problems, the substation ventilation openings should be located as far as possible from the switchboard <br>(see Fig. '''B 17''').<br>  
To favour evacuation of the heat produced by the transformer via natural convection, ventilation openings should be located at the top and bottom of the wall near the transformer. The heat dissipated by the MV switchboard is negligible.<br>To avoid condensation problems, the substation ventilation openings should be located as far as possible from the switchboard <br>(see Fig. '''B 17''').<br>  
Line 78: Line 78:
----
----


===== Type of ventilation openings<br>  =====
== Type of ventilation openings<br>  ==


To reduce the entry of dust, pollution, mist, etc., the substation ventilation openings should be equipped with chevron-blade baffles.<br>Always make sure the baffles are oriented in the right direction (see Fig. '''B18''').<br>  
To reduce the entry of dust, pollution, mist, etc., the substation ventilation openings should be equipped with chevron-blade baffles.<br>Always make sure the baffles are oriented in the right direction (see Fig. '''B18''').<br>  
Line 88: Line 88:
----
----


===== Temperature variations inside cubicles<br>  =====
== Temperature variations inside cubicles<br>  ==


To reduce temperature variations, always install anti-condensation heaters inside MV&nbsp;cubicles if the average relative humidity can remain high over a long period of time. The heaters must operate continuously, 24 hours a day all year long.<br>Never connect them to a temperature control or regulation system as this could lead to temperature variations and condensation as well as a shorter service life for the heating elements. Make sure the heaters offer an adequate service life (standard versions are generally sufficient).  
To reduce temperature variations, always install anti-condensation heaters inside MV&nbsp;cubicles if the average relative humidity can remain high over a long period of time. The heaters must operate continuously, 24 hours a day all year long.<br>Never connect them to a temperature control or regulation system as this could lead to temperature variations and condensation as well as a shorter service life for the heating elements. Make sure the heaters offer an adequate service life (standard versions are generally sufficient).  


===== Temperature variations inside the substation<br>  =====
== Temperature variations inside the substation<br>  ==


The following measures can be taken to reduce temperature variations inside the substation:  
The following measures can be taken to reduce temperature variations inside the substation:  
Line 101: Line 101:
*Eliminate cold air drafts from cable trenches under cubicles or from openings in the substation (under doors, roof joints, etc.).&nbsp;
*Eliminate cold air drafts from cable trenches under cubicles or from openings in the substation (under doors, roof joints, etc.).&nbsp;


===== Substation environment and humidity  =====
== Substation environment and humidity  ==


Various factors outside the substation can affect the humidity inside.  
Various factors outside the substation can affect the humidity inside.  
Line 117: Line 117:
Make sure cable trenches are dry under all conditions.<br>A partial solution is to add sand to the bottom of the cable trench.<br>  
Make sure cable trenches are dry under all conditions.<br>A partial solution is to add sand to the bottom of the cable trench.<br>  


===== Pollution protection and cleaning  =====
== Pollution protection and cleaning  ==


Excessive pollution favours leakage current, tracking and flashover on insulators. <br>To prevent MV equipment degradation by pollution, it is possible to either protect the equipment against pollution or regularly clean the resulting contamination.<br>  
Excessive pollution favours leakage current, tracking and flashover on insulators. <br>To prevent MV equipment degradation by pollution, it is possible to either protect the equipment against pollution or regularly clean the resulting contamination.<br>  


===== Protection  =====
== Protection  ==


Indoor MV switchgear can be protected by enclosures providing a sufficiently high degree of protection (IP).  
Indoor MV switchgear can be protected by enclosures providing a sufficiently high degree of protection (IP).  


===== Cleaning  =====
== Cleaning  ==


If not fully protected, MV equipment must be cleaned regularly to prevent degradation by contamination from pollution.<br>Cleaning is a critical process. The use of unsuitable products can irreversibly damage the equipment.<br>For cleaning procedures, please check the documentation or ask the manufacturer.<br>
If not fully protected, MV equipment must be cleaned regularly to prevent degradation by contamination from pollution.<br>Cleaning is a critical process. The use of unsuitable products can irreversibly damage the equipment.<br>For cleaning procedures, please check the documentation or ask the manufacturer.<br>

Revision as of 08:00, 8 June 2011


The purpose of this chapter is to provide general guidelines on how to avoid or greatly reduce MV equipment degradation on sites exposed to humidity and pollution.

Normal service conditions for indoor MV equipment

All MV equipments comply with specific standards and with the IEC 62271-1 standard “Common specifications for high-voltage switchgear and controlgear”, which defines the normal conditions for the installation and use of such equipment.
For instance, regarding humidity, the standard mentions:
The conditions of humidity are as follows:

  • The average value of the relative humidity, measured over a period of 24 h does not exceed 90%;
  • The average value of the water vapour pressure, over a period of 24 h does not exceed 2.2 kPa;
  • The average value of the relative humidity, over a period of one month does not exceed 90%;
  • The average value of water vapour pressure, over a period of one month does not exceed 1.8 kPa;

Under these conditions, condensation may occasionally occur.
NOTE 1: Condensation can be expected where sudden temperature changes occur in period of high humidity.
NOTE 2: To withstand the effects of high humidity and condensation, such as a breakdown of insulation or corrosion of metallic parts, switchgear designed for such conditions and tested accordingly should be used.
NOTE 3: Condensation may be prevented by special design of the building or housing, by suitable ventilation and heating of the station or by use of dehumifying equipment.
As indicated in the standard, condensation may occasionally occur even under normal conditions. The standard goes on to indicate special measures concerning the substation premises that can be implemented to prevent condensation.

Use under severe conditions
Under certain severe conditions concerning humidity and pollution, largely beyond the normal conditions of use mentioned above, correctly designed electrical equipment can be subject to damage by rapid corrosion of metal parts and surface degradation of insulating parts.



FigB15.jpg
FigB15.jpg
FigB15.jpg













Fig. B15: SM6 metal enclosed indoor MV eqpuipment


Remedial measures for condensation problems

  • Carefully design or adapt substation ventilation.
  • Avoid temperature variations.
  • Eliminate sources of humidity in the substation environment.
  • Install an air conditioning system.
  • Make sure cabling is in accordance with applicable rules.

Remedial measures for pollution problems

  • Equip substation ventilation openings with chevron-type baffles to reduce entry of dust and pollution.
  • Keep substation ventilation to the minimum required for evacuation of transformer heat to reduce entry of pollution and dust.
  • Use MV cubicles with a sufficiently high degree of protection (IP).
  • Use air conditioning systems with filters to restrict entry of pollution and dust.
  • Regularly clean all traces of pollution from metal and insulating parts.

Ventilation

Substation ventilation is generally required to dissipate the heat produced by transformers and to allow drying after particularly wet or humid periods.
However, a number of studies have shown that excessive ventilation can drastically increase condensation.
Ventilation should therefore be kept to the minimum level required.
Furthermore, ventilation should never generate sudden temperature variations that can cause the dew point to be reached.
For this reason:
Natural ventilation should be used whenever possible. If forced ventilation is necessary, the fans should operate continuously to avoid temperature fluctuations.
Guidelines for sizing the air entry and exit openings of substations are presented hereafter.

Calculation methods

A number of calculation methods are available to estimate the required size of substation ventilation openings, either for the design of new substations or the adaptation of existing substations for which condensation problems have occurred.
The basic method is based on transformer dissipation.
The required ventilation opening surface areas S and S’ can be estimated using the following formulas:

[math]\displaystyle{ \mbox{S}=\frac{1.8\times10^{-4}\mbox{P}}{\sqrt\mbox{H}} }[/math] and   [math]\displaystyle{ \mbox{S}^'={1.10\times\mbox{S}} }[/math]

where:
S = Lower (air entry) ventilation opening area [m²] (grid surface deducted)
S’= Upper (air exit) ventilation opening area [m²] (grid surface deducted)
P = Total dissipated power [W]
P is the sum of the power dissipated by:

  • The transformer (dissipation at no load and due to load)
  • The LV switchgear
  • The MV switchgear

H = Height between ventilation opening mid-points [m] See Fig.B16



FigB16.jpg












Fig. B16: Natural ventilation


Note:
This formula is valid for a yearly average temperature of 20 °C and a maximum altitude of 1,000 m.
It must be noted that these formulae are able to determine only one order of magnitude of the sections S and S', which are qualified as thermal section, i.e. fully open and just necessary to evacuate the thermal energy generated inside the MV/LV substation.
The pratical sections are of course larger according to the adopted technological solution.
Indeed, the real air flow is strongly dependant:

  • on the openings shape and solutions adopted to ensure the cubicle protection index (IP): metal grid, stamped holes, chevron louvers,...
  • on internal components size and their position compared to the openings: transformer and/or retention oil box position and dimensions, flow channel between the components, ...
  • and on some physical and environmental parameters: outside ambient temperature, altitude, magnitude of the resulting temperature rise.

The understanding and the optimization of the attached physical phenomena are subject to precise flow studies, based on the fluid dynamics laws, and realized with specific analytic software.
Example:
Transformer dissipation = 7,970 W
LV switchgear dissipation = 750 W
MV switchgear dissipation = 300 W
The height between ventilation opening mid-points is 1.5 m.
Calculation:
Dissipated Power P = 7,970 + 750 + 300 = 9,020 W

[math]\displaystyle{ \mbox{S}=\frac{1.8\times10^{-4}P}{\sqrt\mbox{1.5}}=1.32\mbox{m}^2 }[/math] and   [math]\displaystyle{ \mbox{S}^'={1.1\times1.32}=1.46\mbox{m}^2 }[/math]

Ventilation opening locations

To favour evacuation of the heat produced by the transformer via natural convection, ventilation openings should be located at the top and bottom of the wall near the transformer. The heat dissipated by the MV switchboard is negligible.
To avoid condensation problems, the substation ventilation openings should be located as far as possible from the switchboard
(see Fig. B 17).



FigB17a.jpg













FigB17b.jpg












Fig. B17: Ventilation opening locations


Type of ventilation openings

To reduce the entry of dust, pollution, mist, etc., the substation ventilation openings should be equipped with chevron-blade baffles.
Always make sure the baffles are oriented in the right direction (see Fig. B18).



FigB18.jpg








Fig. B18: Chevron-blade baffles


Temperature variations inside cubicles

To reduce temperature variations, always install anti-condensation heaters inside MV cubicles if the average relative humidity can remain high over a long period of time. The heaters must operate continuously, 24 hours a day all year long.
Never connect them to a temperature control or regulation system as this could lead to temperature variations and condensation as well as a shorter service life for the heating elements. Make sure the heaters offer an adequate service life (standard versions are generally sufficient).

Temperature variations inside the substation

The following measures can be taken to reduce temperature variations inside the substation:

  • Improve the thermal insulation of the substation to reduce the effects of outdoor temperature variations on the temperature inside the substation.
  • Avoid substation heating if possible. If heating is required, make sure the regulation system and/or thermostat are sufficiently accurate and designed to avoid excessive temperature swings (e.g. no greater than 1 °C).
  • If a sufficiently accurate temperature regulation system is not available, leave the heating on continuously, 24 hours a day all year long.
  • Eliminate cold air drafts from cable trenches under cubicles or from openings in the substation (under doors, roof joints, etc.). 

Substation environment and humidity

Various factors outside the substation can affect the humidity inside.

  • Plants

Avoid excessive plant growth around the substation.

  • Substation waterproofing

The substation roof must not leak. Avoid flat roofs for which waterproofing is difficult to implement and maintain.

  • Humidity from cable trenches

Make sure cable trenches are dry under all conditions.
A partial solution is to add sand to the bottom of the cable trench.

Pollution protection and cleaning

Excessive pollution favours leakage current, tracking and flashover on insulators.
To prevent MV equipment degradation by pollution, it is possible to either protect the equipment against pollution or regularly clean the resulting contamination.

Protection

Indoor MV switchgear can be protected by enclosures providing a sufficiently high degree of protection (IP).

Cleaning

If not fully protected, MV equipment must be cleaned regularly to prevent degradation by contamination from pollution.
Cleaning is a critical process. The use of unsuitable products can irreversibly damage the equipment.
For cleaning procedures, please check the documentation or ask the manufacturer.

Share