Inductive coupling: Difference between revisions

From Electrical Installation Guide
(Cleanup_2016)
m (Text replacement - "\[\[ru:[^]]*\]\][ \r\n]*" to "")
 
(5 intermediate revisions by 2 users not shown)
Line 1: Line 1:
{{Menu_EMC_guidelines}}
{{Menu_EMC_guidelines}}__TOC__
 
__TOC__
 
== Definition  ==
== Definition  ==


Line 14: Line 11:


== Examples  ==
== Examples  ==
(see {{FigRef|R34}})  
(see {{FigRef|R36}})  


*Nearby cables subjected to rapid current variations (di/dt)  
*Nearby cables subjected to rapid current variations (di/dt)  
Line 24: Line 21:
*Inductors
*Inductors


{{FigImage|DB422802_EN|svg|R34|Example of inductive coupling}}
{{FigImage|DB422802_EN|svg|R36|Example of inductive coupling}}


== Counter-measures ==
== Counter-measures ==
Line 36: Line 33:
*Shield the disturbing cables, the victim cables or both (the shielding must be bonded)
*Shield the disturbing cables, the victim cables or both (the shielding must be bonded)
*Reduce the dv/dt of the disturber by increasing the signal rise time where possible (series-connected resistors or PTC resistors on the disturbing cable, ferrite rings on the disturbing and/or victim cable)
*Reduce the dv/dt of the disturber by increasing the signal rise time where possible (series-connected resistors or PTC resistors on the disturbing cable, ferrite rings on the disturbing and/or victim cable)
[[ru:Индуктивная связь]]
[[zh:电感耦合]]

Latest revision as of 09:49, 22 June 2022

Definition

The disturber and the victim are coupled by a magnetic field. The level of disturbance depends on the current variations (di/dt) and the mutual coupling inductance.

Inductive coupling increases with:

  • The frequency
  • The proximity of the disturber to the victim and the length of the parallel cables,
  • The height of the cables with respect to a ground referencing plane,
  • The load impedance of the disturbing circuit.

Examples

(see Fig. R36)

  • Nearby cables subjected to rapid current variations (di/dt)
  • Short-circuits
  • Fault currents
  • Lightning strikes
  • Stator control systems
  • Welding machines
  • Inductors
Fig. R36 – Example of inductive coupling

Counter-measures

  • Limit the length of parallel runs of disturbers and victims to the strict minimum
  • Increase the distance between the disturber and the victim
  • For two-wire connections, run the two wires as close together as possible
  • Use multi-core or touching single-core cables, preferably in a triangular layout
  • Position a PEC bonded at both ends and between the disturber and the victim
  • Use symmetrical transmission systems on correctly implemented, symmetrical wiring systems
  • Shield the disturbing cables, the victim cables or both (the shielding must be bonded)
  • Reduce the dv/dt of the disturber by increasing the signal rise time where possible (series-connected resistors or PTC resistors on the disturbing cable, ferrite rings on the disturbing and/or victim cable)
Share