== Grid connected PV system ≤ 10kW (Residential)  ==
== Grid connected PV system ≤ 10kW (Residential)  ==


Line 11: Line 8:


{{FigImage|DB422723_EN|svg|P22|Grid connected <{{=}} 10kW}}
{{FigImage|DB422723_EN|svg|P22|Grid connected <{{=}} 10kW}}
== 10 to 100kW grid connected PV system (Small building) ==


=== One three phase inverter with one string combiner box ===
=== One three phase inverter with one string combiner box ===
Line 31: Line 30:
== 150kW to 500kW Grid connected PV system (Large building and farm)  ==
== 150kW to 500kW Grid connected PV system (Large building and farm)  ==


=== Three phase inverter with more than two Array boxes ===
=== Three phase inverter with more than two string combiner boxes ===


* Typically, 150kW to 500kW single inverter.  
* Typically, 150kW to 500kW single inverter.  
Line 38: Line 37:


{{FigImage|DB422728_EN|svg|P25|150-500kW single MPPT inverter with N arrays > 2}}
{{FigImage|DB422728_EN|svg|P25|150-500kW single MPPT inverter with N arrays > 2}}
==  Connection of PV system to the grid or to the private low voltage installation ==
=== Direct connection of PV system to the grid ===
When PV system is installed for "grid feeding", Utility that operates the grid will provide requirements for protection, disconnection, and metering function.
Each utility may have specific requirements according to local habits and grid specificity.
As a general rules the following functions are required :
* Energy meter (both direction)
* Disconnecting device (some countries require visual break)
* Over-current and earth fault protection according to earthing system
* Anti-islanding protection like VDE0126.
=== Connection of PV system to the private low voltage installation ===
See [[Photovoltaic architectures for self-consumption]].

Latest revision as of 17:52, 20 December 2019

Grid connected PV system ≤ 10kW (Residential)

One single phase inverter

  • Typically, a 5kW grid-connected single-phase inverter. with UOC MAX ≤ 600V. One or two strings – Isctc < 25A, IAC < 32A. In this design there is no string protection.
  • A PV main switch is necessary. When the inverter is indoors, an additional remote controlled switch at the DC cable entry point is recommended for emergencies services.
Fig. P22 – Grid connected <= 10kW

10 to 100kW grid connected PV system (Small building)

One three phase inverter with one string combiner box

  • Typically, 30kW to 60kW grid-connected inverters. UOC max is generally higher than 600V (up to 1000V), Isctc does not exceed 200A, Iac does not exceed 100A.
  • This design has more than 2 strings.
  • Reverse current protection is therefore necessary.
  • A main PV switch is required. When an inverter is inside, additional remote-controlled switch at DC cable entry point is recommended for emergencies.
Fig. P23 – 10-100kW single MPPT inverter

Multi single phase inverters design

  • Typically, 6x5 to 20x5kW grid-connected inverters.
  • The design used for residential building can be duplicated as often as necessary.
  • In that case, the DC system is very simple and the AC system is very similar to usual AC systems.
Fig. P24 – 10-100kW multi single MPPT inverter

150kW to 500kW Grid connected PV system (Large building and farm)

Three phase inverter with more than two string combiner boxes

  • Typically, 150kW to 500kW single inverter.
  • This design is very similar to the three phase inverter with one string combiner box except that it has more arrays, which requires array cable protection.
  • Istc <= 400A, IAC <= 600A.
Fig. P25 – 150-500kW single MPPT inverter with N arrays > 2