EMC behaviour of different electrical distribution architecturing: Difference between revisions

From Electrical Installation Guide
Home > ElectroMagnetic Compatibility (EMC) > EMC behaviour of different electrical distribution architecturing
(updated according to guide 2013)
Line 1: Line 1:
<br> {{Menu_EMC_guidelines}}
{{Menu_EMC_guidelines}}
The system earthing arrangement must be properly selected to ensure the safety of life and property. The behaviour of the different systems with respect to EMC&nbsp;considerations must be taken into account.'''Figure R1 '''below presents a summary of their main characteristics.<br>European standards (see EN 50174-2 § 6.4 and EN 50310 § 6.3) recommend the TN-S system which causes the fewest EMC problems for installations comprising information-technology equipment (including telecom equipment).


----
The system earthing arrangement must be properly selected to ensure the safety of life and property. The behaviour of the different systems with respect to EMC considerations must be taken into account. '''Figure R1''' below presents a summary of their main characteristics.
 
<br>


European standards (see EN 50174-2, EN 50310 and HD 60364-4-444) recommend the TN-S eathing system which causes the fewest EMC problems for installations comprising information-technology equipment (including telecom equipment).
{| style="width: 770px; height: 201px" cellspacing="1" cellpadding="1" width="770" border="1"
{| style="width: 770px; height: 201px" cellspacing="1" cellpadding="1" width="770" border="1"
|-
|-
Line 15: Line 13:
|-
|-
| valign="top" | Safety of persons  
| valign="top" | Safety of persons  
| Good<br>RCD mandatory  
| Correct <br> Use of residual current devices (circuit breaker)is mandatory
| colspan="3" | Good<br>Continuity of the PE conductor must be ensured throughout the installation
| colspan="3" | Correct <br>Continuity of the PE conductor must be ensured throughout the installation
|-
|-
| Safety&nbsp;of&nbsp;property&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;
| Safety of property
| Good
| Correct
| Poor  
| Poor  
| Good
| Correct
| Poor
| Poor
|-
|-
| &nbsp;&nbsp;&nbsp;&nbsp;  
| &nbsp;&nbsp;&nbsp;&nbsp;  
| valign="top" | Medium fault current<br>(&lt; a few dozen amperes)  
| valign="top" | Medium ground-fault current (< about ten amps)  
| valign="top" | High fault current<br>(around 1 kA)  
| valign="top" | High ground-fault current (about 1 kA)  
| Low current for first fault <br>(&lt; a few dozen mA),<br>but high for second fault  
| Low ground-fault current for first fault (< about ten mA), but high for second fault
| valign="top" | High fault current<br>(around 1 kA)
| valign="top" | High ground-fault current <br> (about 1 kA)
|-
|-
| Availability of energy  
| Availability of energy  
| Good
| Correct
| Good
| Correct
| Excellent  
| Excellent  
| Good
| Correct
|-
|-
| valign="top" | EMC behaviour
| valign="top" | EMC performance
| valign="top" | Good<br>- Risk of overvoltages<br>- Equipotential problems<br>- Need to manage devices with high leakage currents&nbsp;
| valign="top" | Correct <br>  
| valign="top" | Excellent<br>- Few equipotential problems<br>- Need to manage<br>devices with high <br>leakage currents<br>- High fault currents <br>(transient&nbsp;disturbances)  
- Risk of overvoltages<br>
| valign="top" | Poor (to be avoided)<br>- Risk of overvoltages<br>- Common-mode filters and<br>surge arrestors must handle&nbsp;the phase- to-phase voltages<br>- RCDs subject&nbsp;to&nbsp;nuisance tripping if&nbsp;common-mode&nbsp;<br>capacitors are present<br>- Equivalent to TN system for second&nbsp;fault&nbsp;&nbsp;
- Equipotential problems<br>
| valign="top" | Poor <br>(should never be used)<br>- Neutral and PE are the same<br>- Circulation of disturbed currents in exposed conductive parts (high<br>magnetic-field radiation)<br>- High fault currents(transient disturbances)
- Need to manage devices with high leakage currents
| valign="top" | Excellent <br>
- Good equipotential situation<br>
- Need to manage devices with high leakage currents<br>
- High ground- currents (transient disturbances)<br>
| valign="top" | Poor (to be avoided)<br>
- Risk of overvoltages<br>
- Common-mode filters and surge arrestors must handle the phase- to-phase voltages<br>
- RCDs subject to nuisance tripping if common-mode capacitors are present<br>
- Equivalent to TN system for second fault<br>
| valign="top" | Poor (not recommended)<br>
- Neutral and PE are combined<br>
- 50/60 Hz and harmonics currents circulate in the earthing and grounding structures<br>
- High ground-fault currents (transient disturbances)
|}
|}


'''''Fig. R1:''' Main characteristics of system earthing''  
'''''Fig. R1:''''' ''Main characteristics of the different earthing sytems''


----
----


When an installation includes high-power equipment (motors, air-conditioning, lifts, power electronics, etc.), it is advised to install one or more transformers specifically for these systems. Electrical distribution must be organised in a star system and all outgoing circuits must exit the main low-voltage switchboard (MLVS).<br>Electronic systems (control/monitoring, regulation, measurement instruments, etc.) must be supplied by a dedicated transformer in a TN-S system.<br>'''Figure R2 '''below illustrate these recommendations.  
When an installation includes high-power equipment (motors, air-conditioning, lifts, power electronics, etc.), it is advised to install one or more transformers specifically for these systems. Electrical distribution must be organised in a star system and all outgoing circuits must exit the main low-voltage switchboard (MLVS).<br>Electronic systems (control/monitoring, regulation, measurement instruments, etc.) must be supplied by a dedicated transformer in a TN-S system.<br>'''Figure R2 '''below illustrates these recommendations.  


----
----


<br>[[Image:Fig R02.jpg|left]]<br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br>'''''Fig. R2:''' Recommendations of separated distributions''
<br>[[Image:Fig R02.jpg|left]]<br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br>'''''Fig. R2:''' Recommendations of separated distributions''


[[ru:ЭМС для различных схем распределения электроэнергии]]
[[ru:ЭМС для различных схем распределения электроэнергии]]
[[zh:不同配电系统结构的电磁兼容性能]]
[[zh:不同配电系统结构的电磁兼容性能]]

Revision as of 12:29, 19 October 2013


The system earthing arrangement must be properly selected to ensure the safety of life and property. The behaviour of the different systems with respect to EMC considerations must be taken into account. Figure R1 below presents a summary of their main characteristics.

European standards (see EN 50174-2, EN 50310 and HD 60364-4-444) recommend the TN-S eathing system which causes the fewest EMC problems for installations comprising information-technology equipment (including telecom equipment).

  TT TN-S IT TN-C
Safety of persons Correct
Use of residual current devices (circuit breaker)is mandatory
Correct
Continuity of the PE conductor must be ensured throughout the installation
Safety of property Correct Poor Correct Poor
     Medium ground-fault current (< about ten amps) High ground-fault current (about 1 kA) Low ground-fault current for first fault (< about ten mA), but high for second fault High ground-fault current
(about 1 kA)
Availability of energy Correct Correct Excellent Correct
EMC performance Correct

- Risk of overvoltages
- Equipotential problems
- Need to manage devices with high leakage currents

Excellent

- Good equipotential situation
- Need to manage devices with high leakage currents
- High ground- currents (transient disturbances)

Poor (to be avoided)

- Risk of overvoltages
- Common-mode filters and surge arrestors must handle the phase- to-phase voltages
- RCDs subject to nuisance tripping if common-mode capacitors are present
- Equivalent to TN system for second fault

Poor (not recommended)

- Neutral and PE are combined
- 50/60 Hz and harmonics currents circulate in the earthing and grounding structures
- High ground-fault currents (transient disturbances)

Fig. R1: Main characteristics of the different earthing sytems


When an installation includes high-power equipment (motors, air-conditioning, lifts, power electronics, etc.), it is advised to install one or more transformers specifically for these systems. Electrical distribution must be organised in a star system and all outgoing circuits must exit the main low-voltage switchboard (MLVS).
Electronic systems (control/monitoring, regulation, measurement instruments, etc.) must be supplied by a dedicated transformer in a TN-S system.
Figure R2 below illustrates these recommendations.



Fig R02.jpg






















Fig. R2: Recommendations of separated distributions