All AC equipement and appliances that include electromagnetic devices, or depend on magnetically-coupled windings, require some degree of reactive current to create magnetic flux.
All AC equipment and appliances that include electromagnetic devices, or depend on magnetically coupled windings, require some degree of reactive current to create magnetic flux.


The most common items in this class are transformers and reactors, motors and discharge lamps (with magnetic ballasts) (see '''Fig. L2''').
The most common items in this class are transformers, reactors, motors and discharge lamps with magnetic ballasts (see '''Fig. L5''').


The proportion of reactive power (kvar) with respect to active power (kW) when an item of equipement is fully loaded varies according to the item concerned being:  
The proportion of reactive power (kvar) with respect to active power (kW) when a piece of equipment is fully loaded varies according to the item concerned being:
* 65-75% for asynchronous motors (corresponding to a Power Factor 0.8 – 0.85)
* 5-10% for transformers (corresponding to a Power Factor close to 0.995)


*65-75% for asynchronous motors
*5-10% for transformers


[[Image:FigL02.jpg|none|399px]]


[[Image:FigL02.jpg|none|399px]]


'''''Fig. L5:''''' '''Power consuming items that also require reactive energy'''


'''''Fig. L2:''''' '''Power consuming items that also require reactive energy'''


[[ru:Установки и приборы, требующие реактивной мощности]]
[[ru:Установки и приборы, требующие реактивной мощности]]
[[zh:设备需要的无功电能]]
[[zh:设备需要的无功电能]]

Revision as of 15:19, 23 August 2013


All AC equipment and appliances that include electromagnetic devices, or depend on magnetically coupled windings, require some degree of reactive current to create magnetic flux.

The most common items in this class are transformers, reactors, motors and discharge lamps with magnetic ballasts (see Fig. L5).

The proportion of reactive power (kvar) with respect to active power (kW) when a piece of equipment is fully loaded varies according to the item concerned being:

  • 65-75% for asynchronous motors (corresponding to a Power Factor 0.8 – 0.85)
  • 5-10% for transformers (corresponding to a Power Factor close to 0.995)


FigL02.jpg


Fig. L5: Power consuming items that also require reactive energy


ru:Установки и приборы, требующие реактивной мощности zh:设备需要的无功电能

Share