General method for cable sizing: Difference between revisions
m (r2.7.2) (robot Adding: zh:通用线缆大小分类方法) |
m (Text modifications done as per 2013 PDF) |
||
Line 799: | Line 799: | ||
|- | |- | ||
| > 45 | | > 45 | ||
| 1.0 | | 1.0 <sup>(1)</sup> | ||
|} | |} | ||
''(1) If the neutral current is more than 135 % of the phase current and the cable size is selected on the basis of the neutral current then the three phase conductors will not be fully loaded. The reduction in heat generated by the phase conductors offsets the heat generated by the neutral conductor to the extent that it is not necessary to apply any reduction factor to the current carrying capacity for three loaded conductors.'' | |||
'''''Fig. G19:'''''<i> Correction factors for harmonic currents in four-core and five-core cables (table D.52.1 of IEC 60364-5-52)</i> | '''''Fig. G19:'''''<i> Correction factors for harmonic currents in four-core and five-core cables (table D.52.1 of IEC 60364-5-52)</i> |
Revision as of 09:17, 28 May 2013
Possible methods of installation for different types of conductors or cables
The different admissible methods of installation are listed in Figure G8, in conjonction with the different types of conductors and cables.
Conductors and cables | Method of installation | |||||||||||
Without fixings | Clipped direct | Conduit | Cable trunking (including skirting trunking, flush floor trunking) |
Cable ducting | Cable ladder Cable tray Cable brackets |
On insulators | Support wire | |||||
Bare conductors | - | - | – | - | - | - | + | - | ||||
Insulated conductors | - | - | + | + | + | - | + | - | ||||
Sheathed cables (including armoured mineral insulated) |
Multi-core | + | + | + | + | + | + | 0 | + | |||
Single-core | 0 | + | + | + | + | + | 0 | + |
Cable brackets
+ Permitted.
– Not permitted.
0 Not applicable, or not normally used in practice.
Fig.G8: Selection of wiring systems (table 52-1 of IEC 60364-5-52)
Possible methods of installation for different situations:
Different methods of installation can be implemented in different situations. The possible combinations are presented in Figure G9.
The number given in this table refer to the different wiring systems considered.
(see also Fig. G10)
Situations | Method of installation | |||||||
Without fixings | With fixings | Conduit | Cable trunking (including skirting trunking,flush floor trunking) | Cable ducting | Cable ladder, cable tray,cable brackets | On insulators | Support wire | |
Building voids | 40, 46,15, 16 | 0 | 15, 16,41, 42 | - | 43 | 30, 31, 32, 33, 34 | - | - |
Cable channel | 56 | 56 | 54, 55 | 0 | 44, 45 | 30, 31, 32, 33, 34 | - | - |
Buried in ground | 72, 73 | 0 | 70, 71 | - | 70, 71 | 0 | - | |
Embedded in structure | 57, 58 | 3 | 1, 2, 59, 60 | 50, 51, 52, 53 | 44, 45 | 0 | - | - |
Surface mounted | - | 20,21 | 4, 5 | 6, 7, 8, 9, 12, 13, 14, 22, 23 | 6, 7, 8, 9 | 30, 31, 32, 33, 34 | 36 | - |
Overhead | - | - | 0 | 10, 11 | - | 30, 31, 32, 33, 34 | 36 | 35 |
Immersed | 80 | 80 | 0 | - | 0 | 0 | - | - |
– Not permitted.
0 Not applicable, or not normally used in practice.
Fig.G9: Erection of wiring systems (table 52-2 of IEC 60364-5-52)
Examples of wiring systems and reference methods of installations
An illustration of some of the many different wiring systems and methods of installation is provided in Figure G10.
Several reference methods are defined (with code letters A to G), grouping installation methods having the same characteristics relative to the current-carrying capacities of the wiring systems.
Fig.G10: Examples of methods of installation (part of table 52-3 of IEC 60364-5-52)
Maximum operating temperature:
The current-carrying capacities given in the subsequent tables have been determined so that the maximum insulation temperature is not exceeded for sustained periods of time.
For different type of insulation material, the maximum admissible temperature is given in Figure G11.
Type of insulation | Temperature limit °C |
Polyvinyl-chloride (PVC) | 70 at the conductor |
Cross-linked polyethylene (XLPE) and ethylene propylene rubber (EPR) | 90 at the conductor |
Mineral (PVC covered or bare exposed to touch) | 70 at the sheath |
Mineral (bare not exposed to touch and not in contact with combustible material) | 105 at the seath |
Fig.G11: Maximum operating temperatures for types of insulation (table 52-4 of IEC 60364-5-52)
Correction factors
In order to take environnement or special conditions of installation into account, correction factors have been introduced.
The cross sectional area of cables is determined using the rated load current IB divided by different correction factors, k1, k2, ...: [math]\displaystyle{ I^{'}{_B}=\frac{I_B}{k_1.k_2...} }[/math]
I’B is the corrected load current, to be compared to the current-carrying capacity of the considered cable.
- Ambient temperature
The current-carrying capacities of cables in the air are based on an average air temperature equal to 30 °C. For other temperatures, the correction factor is given in Figure G12 for PVC, EPR and XLPE insulation material.
The related correction factor is here noted k1.
Ambient temperature °C | Insulation | |
PVC | XLPE and EPR | |
10 | 1.22 | 1.15 |
15 | 1.17 | 1.12 |
20 | 1.12 | 1.08 |
25 | 1.06 | 1.04 |
35 | 0.94 | 0.96 |
40 | 0.87 | 0.91 |
45 | 0.79 | 0.87 |
50 | 0.71 | 0.82 |
55 | 0.61 | 0.76 |
60 | 0.50 | 0.71 |
65 | - | 0.65 |
70 | - | 0.58 |
75 | - | 0.50 |
80 | - | 0.41 |
Fig.G12: Correction factors for ambient air temperatures other than 30 °C to be applied to the current-carrying capacities for cables in the air (from table A.52-14 of IEC 60364-5-52)
The current-carrying capacities of cables in the ground are based on an average ground temperature equal to 20 °C. For other temperatures, the correction factor is given in Figure G13 for PVC, EPR and XLPE insulation material.
The related correction factor is here noted k2.
Ground temperature °C | Insulation | |
PVC | XLPE and EPR | |
10 | 1.10 | 1.07 |
15 | 1.05 | 1.04 |
25 | 0.95 | 0.96 |
30 | 0.89 | 0.93 |
35 | 0.84 | 0.89 |
40 | 0.77 | 0.85 |
45 | 0.71 | 0.80 |
50 | 0.63 | 0.76 |
55 | 0.55 | 0.71 |
60 | 0.45 | 0.65 |
65 | - | 0.60 |
70 | - | 0.53 |
75 | - | 0.46 |
80 | - | 0.38 |
Fig. G13: Correction factors for ambient ground temperatures other than 20 °C to be applied to the current-carrying capacities for cables in ducts in the ground (from table A.52-15 of IEC 60364-5-52)
- Soil thermal resistivity
The current-carrying capacities of cables in the ground are based on a ground resistivity equal to 2.5 K.m/W. For other values, the correction factor is given in Figure G14.
The related correction factor is here noted k3.
Thermal resistivity, K.m/W | 1 | 1.5 | 2 | 2.5 | 3 |
Correction factor | 1.18 | 1.1 | 1.05 | 1 | 0.96 |
Fig.G14: Correction factors for cables in buried ducts for soil thermal resistivities other than 2.5 K.m/W to be applied to the current-carrying capacities for reference method D (table A52.16 of IEC 60364-5-52)
Based on experience, a relationship exist between the soil nature and resistivity. Then, empiric values of correction factors k3 are proposed in Figure G15, depending on the nature of soil.
Nature of soil | k3 |
Very wet soil (saturated) | 1.21 |
Wet soil | 1.13 |
Damp soil | 1.05 |
Dry soil | 1.00 |
Very dry soil (sunbaked) | 0.86 |
Fig.G15: Correction factor k3 depending on the nature of soil
- Grouping of conductors or cables
The current-carrying capacities given in the subsequent tables relate to single circuits consisting of the following numbers of loaded conductors:
- Two insulated conductors or two single-core cables, or one twin-core cable (applicable to single-phase circuits);
- Three insulated conductors or three single-core cables, or one three-core cable (applicable to three-phase circuits).
Where more insulated conductors or cables are installed in the same group, a group reduction factor (here noted k4) shall be applied.
Examples are given in Figures G16 to G18 for different configurations (installation methods, in free air or in the ground).
Figure G16 gives the values of correction factor k4 for different configurations of unburied cables or conductors, grouping of more than one circuit or multi-core cables.
Arrangement (cables touching) | Number of circuits or multi-core cables | Reference methods | |||||||||||
1 | 2 | 3 | 4 | 5 | 6 | 7 | 8 | 9 | 12 | 16 | 20 | ||
Bunched in air, on a surface, embedded orenclosed | 1.00 | 0.80 | 0.70 | 0.65 | 0.60 | 0.57 | 0.54 | 0.52 | 0.50 | 0.45 | 0.41 | 0.38 | Methods A to F |
Single layer on wall, floor or unperforated tray | 1.00 | 0.85 | 0.79 | 0.75 | 0.73 | 0.72 | 0.72 | 0.71 | 0.70 | No further reduction factor for more than nine circuits or multi-core cables | Method C | ||
Single layer fixed directly under a wooden ceiling |
0.95 | 0.81 | 0.72 | 0.68 | 0.66 | 0.64 | 0.63 | 0.62 | 0.61 | ||||
Single layer on a perforated horizontal or vertical tray | 1.00 | 0.88 | 0.82 | 0.77 | 0.75 | 0.73 | 0.73 | 0.72 | 0.72 | Methods E and F | |||
Single layer on ladder support or cleats etc. | 1.00 | 0.87 | 0.82 | 0.80 | 0.80 | 0.79 | 0.79 | 0.78 | 0.78 |
Fig. G16: Reduction factors for groups of more than one circuit or of more than one multi-core cable (table A.52-17 of IEC 60364-5-52)
Figure G17 gives the values of correction factor k4 for different configurations of unburied cables or conductors, for groups of more than one circuit of single-core cables in free air.
Fig. G17: Reduction factors for groups of more than one circuit of single-core cables to be applied to reference rating for one circuit of single-core cables in free air - Method of installation F. (table A.52.21 of IEC 60364-5-52)
Figure G18 gives the values of correction factor k4 for different configurations of cables or conductors laid directly in the ground.
Number of circuits |
Cable to cable clearance (a)a | ||||
Nil (cables touching) | One cable diameter | 0.125 m | 0.25 m | 0.5 m | |
2 | 0.75 | 0.80 | 0.85 | 0.90 | 0.90 |
3 | 0.65 | 0.70 | 0.75 | 0.80 | 0.85 |
4 | 0.60 | 0.60 | 0.70 | 0.75 | 0.80 |
5 | 0.55 | 0.55 | 0.65 | 0.70 | 0.80 |
6 | 0.50 | 0.55 | 0.60 | 0.70 | 0.80 |
aMulti-core cables
aSingle-core cables
Fig. G18: Reduction factors for more than one circuit, single-core or multi-core cables laid directly in the ground. Installation method D. (table 52-18 of IEC 60364-5-52)
- Harmonic current
The current-carrying capacity of three-phase, 4-core or 5-core cables is based on the assumption that only 3 conductors are fully loaded.
However, when harmonic currents are circulating, the neutral current can be significant, and even higher than the phase currents. This is due to the fact that the 3rd harmonic currents of the three phases do not cancel each other, and sum up in the neutral conductor.
This of course affects the current-carrying capacity of the cable, and a correction factor noted here k5 shall be applied.
In addition, if the 3rd harmonic percentage h3 is greater than 33%, the neutral current is greater than the phase current and the cable size selection is based on the neutral current. The heating effect of harmonic currents in the phase conductors has also to be taken into account.
The values of k5 depending on the 3rd harmonic content are given in Figure G19.
Third harmonic content of phase current % | Correction factor | |
Size selection is based on phase current |
Size selection is based on neutral current | |
0 - 15 | 1.0 | |
15 - 33 | 0.86 | |
33 - 45 | 0.86 | |
> 45 | 1.0 (1) |
(1) If the neutral current is more than 135 % of the phase current and the cable size is selected on the basis of the neutral current then the three phase conductors will not be fully loaded. The reduction in heat generated by the phase conductors offsets the heat generated by the neutral conductor to the extent that it is not necessary to apply any reduction factor to the current carrying capacity for three loaded conductors.
Fig. G19: Correction factors for harmonic currents in four-core and five-core cables (table D.52.1 of IEC 60364-5-52)
Admissible current as a function of nominal cross-sectional area of conductors
IEC standard 60364-5-52 proposes extensive information in the form of tables giving the admissible currents as a function of cross-sectional area of cables. Many parameters are taken into account, such as the method of installation, type of insulation material, type of conductor material, number of loaded conductors.
As an example, Figure G20 gives the current-carrying capacities for different methods of installation of PVC insulation, three loaded copper or aluminium conductors, free air or in ground.
Fig. G20: Current-carrying capacities in amperes for different methods of installation, PVC insulation, three loaded conductors, copper or aluminium, conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground (table A.52.4 of IEC 60364-5-52)