Coordination of residual current protective devices: Difference between revisions

From Electrical Installation Guide
Home > Protection against electric shocks and electrical fires > Residual Current Devices (RCDs) > Coordination of residual current protective devices
m (Text modified as per 2013 PDF)
(updated image size FigF37 (guide 2013))
Line 10: Line 10:


*In general, at distribution boards (and sub-distribution boards, if existing) and on individual-appliance protection, devices for automatic disconnection in the event of an indirect-contact hazard occurring are installed together with additional protection against direct-contact hazards.<br>
*In general, at distribution boards (and sub-distribution boards, if existing) and on individual-appliance protection, devices for automatic disconnection in the event of an indirect-contact hazard occurring are installed together with additional protection against direct-contact hazards.<br>


== Discrimination between RCDs  ==
== Discrimination between RCDs  ==
Line 27: Line 28:


----
----


== Discrimination at 2 levels  ==
== Discrimination at 2 levels  ==
Line 47: Line 49:


----
----


== Discrimination at 3 or 4 levels  ==
== Discrimination at 3 or 4 levels  ==
Line 71: Line 74:


----
----


'''Discriminative protection at three levels''' (see '''Fig. F37''')  
'''Discriminative protection at three levels''' (see '''Fig. F37''')  
Line 76: Line 80:
----
----


<br>[[Image:FigF37.jpg|left]] <br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br><br>'''''Fig. F37: '''Typical 3-level installation, showing the protection of distribution circuits in a TT-earthed system. One motor is provided with specific protection''
<br>[[Image:FigF37.jpg|none]]  
'''''Fig. F37: '''Typical 3-level installation, showing the protection of distribution circuits in a TT-earthed system. One motor is provided with specific protection''


[[ru:Система TT: координация устройств защиты от замыканий на землю]]
[[ru:Система TT: координация устройств защиты от замыканий на землю]]
[[zh:TT系统剩余电流保护装置间的配合]]
[[zh:TT系统剩余电流保护装置间的配合]]

Revision as of 09:51, 13 August 2013



Discriminative-tripping coordination is achieved either by time-delay or by subdivision of circuits, which are then protected individually or by groups, or by a combination of both methods.
Such discrimination avoids the tripping of any RCD, other than that immediately upstream of a fault position:

  • With equipment currently available, discrimination is possible at three or four different levels of distribution :

  - At the main general distribution board
  - At local general distribution boards
  - At sub-distribution boards
  - At socket outlets for individual appliance protection

  • In general, at distribution boards (and sub-distribution boards, if existing) and on individual-appliance protection, devices for automatic disconnection in the event of an indirect-contact hazard occurring are installed together with additional protection against direct-contact hazards.


Discrimination between RCDs

The general specification for achieving total discrimination between two RCDs is as follow:

  • The ratio between the rated residual operating currents must be > 2
  • Time delaying the upstream RCD

Discrimination is achieved by exploiting the several levels of standardized sensitivity: 30 mA, 100 mA, 300 mA and 1 A and the corresponding tripping times, as shown in Figure F34.



FigF34.jpg





















Fig. F34: Total discrimination at 2 levels



Discrimination at 2 levels

(see Fig. F35)
Protection

  • Level A: RCD time-delayed setting I (for industrial device) or type S (for domestic device) for protection against indirect contacts
  • Level B: RCD instantaneous, with high sensitivity on circuits supplying socket-outlets or appliances at high risk (washing machines, etc.)

Schneider Electric solutions

  • Level A: Compact or Acti 9 circuit-breaker with adaptable RCD module (Vigicompact NSX160), setting I or S type
  • Level B: Circuit-breaker with integrated RCD module (DPN Vigi) or adaptable RCD module (e.g. Vigi iC60) or Vigicompact NSX

Note: The setting of upstream RCCB must comply with selectivity rules and take into account all the downstream earth leakage currents.



FigF35.jpg











Fig. F35: Total discrimination at 2 levels



Discrimination at 3 or 4 levels

(see Fig. F36)
Protection

  • Level A: RCD time-delayed (setting III)
  • Level B: RCD time-delayed (setting II)
  • Level C: RCD time-delayed (setting I) or type S
  • Level D: RCD instantaneous

Schneider Electric solutions

  • Level A: Circuit-breaker associated with RCD and separate toroidal transformer (Vigirex RH)
  • Level B: Vigicompact NSX or Vigirex
  • Level C: Vigirex, Vigicompact NSX or Vigi iC60
  • Level D:

  - Vigicompact NSX or
  - Vigirex or
  - Acti 9 with integrated or adaptable RCD module: Vigi iC60 or DPN Vigi
Note: The setting of upstream RCCB must comply with selectivity rules and take into account all the downstream earth leakage currents



FigF36.jpg




















Fig. F36: Total discrimination at 3 or 4 levels



Discriminative protection at three levels (see Fig. F37)



FigF37.jpg

Fig. F37: Typical 3-level installation, showing the protection of distribution circuits in a TT-earthed system. One motor is provided with specific protection