Photovoltaic system: electrical equipments selection: Difference between revisions

From Electrical Installation Guide
No edit summary
(added table of fig P22 and associated footnotes (guide 2013))
Line 10: Line 10:
[[Image:Fig P22.png|none|Fig P22.png]]  
[[Image:Fig P22.png|none|Fig P22.png]]  


{| width="800" border="1" cellpadding="1" cellspacing="1"
{| width="800" valign="top" border="1"
|-
|-
| bgcolor="#D1E9D4" | '''Needs''' || String junction box || PV array main switch || Inverter || AC box (400V)
! align="left"  width="180px" | Needs
|-
! align="center" width="110px" | String junction box
| bgcolor="#79C68C" colspan="4"| '''Switchgears and control'''
! align="center" width="170px" | PV array main switch
|-
! align="center" width="170px" | Inverter
| bgcolor="#79C68C" |  
! align="center" width="170px" | AC box (400V)
:Isolation || • || • (d) || (a) || • (d)  
|- bgcolor="#79C68C" align="center"
|-
| align="left" colspan="5" | '''Switchgears and control (Q)'''
| bgcolor="#79C68C" |  
|- bgcolor="#79C68C" align="center"
:Switching<br>(Making & breaking<br>rated current || •<br>DC21B || (a) || • (d) ||
| align="left" | - Isolation || • || • (d) || (a) || • (d)  
|-
|- bgcolor="#79C68C" align="center"
| bgcolor="#79C68C" |  
| align="left" | - Switching<br>(Making & breaking<br>rated current || •<br>DC21B || • (d)<nr>DC21B || (a) || • (d)
:Control || • (b) || • (d) || (e) || • (d)
|- bgcolor="#79C68C" align="center"
|-
| align="left" | - Control || • (b) || • (d) || (e) || • (d)
| bgcolor="#79C68C" |  
|- bgcolor="#79C68C" align="center"
:Over-current protection || (c) ||  ||  ||
| align="left" | - Over-current protection || (c) ||  ||  || • (f)
|-
|- bgcolor="#79C68C" align="center"
| bgcolor="#79C68C" |  
| align="left" | - Protection against<br>Insulation fault ||  ||  || (h) || (h)<br>RCD type B or A SI
:Protection against<br>Insulation fault ||  ||  || (h) || (h)<br>RCD type B or A SI
|- bgcolor="#A6D6AE" align="center"
|-
| align="left" | '''Surge protection (SPD)''' ||  || • type 2 ||  || • type 1 or 2
| bgcolor="#A6D6AE" | '''Surge protection''' ||  || • type 2 ||  || • type 1 or 2
|- bgcolor="#D1D3D4" align="center"
|-
| align="left" | '''Enclosure (E)''' || Outdoor<br>Double insulation || Indoor<br>Double insulation || || Standard AC requirement +<br>grid code requirement  
| bgcolor="#D1D3D4" | Enclosure || Outdoor IP5x<br>Double insulation || Indoor IP5x<br>Double insulation || || Standard AC requirement +<br>grid code requirement  
|}
|}
(a) PV array main switch could be included in the inverter. This solution makes inverter service or replacement more difficult.<br>
(b) Remote switching for emergency services located as closely as possible to the PV modules or to the point of entry of DC cables in the building.<br>
(c) No protection is required when the number of string does not exceed 2.<br>
(d) Service and emergency switching<br>
(e) Inverter shall include a protection for anti-islanding (in accordance with VDE 0126 for example)<br>
(f) Overload and short-circuit protection B curve recommended.<br>
(g) This SPD could be unnecessary if there is another SPD in the AC installation at a distance of less than 10 metres.<br>
(h) If the inverter provides no galvanic separation a RCD protection is necessary on AC side. IEC 60364-712 specifies RCD type B. Some local regulations require RCD type A SI<br>


<br> '''''Fig. P23&nbsp;:''''' '''10-100kW single multi MPPT inverter'''
'''''Fig. P23&nbsp;:''''' ''10-100kW single multi MPPT inverter''

Revision as of 15:31, 16 October 2013

Grid connected PV system <= 10kW (Residential)

One single phase inverter

  • Typically, a 5kW grid-connected single-phase inverter. with UOC MAX  600V.
  • One or two strings – Isctc < 25A, IAC < 32A.
  • In this design there is no string protection.
  • A PV main switch is necessary. When the inverter is indoors, an additional remote controlled switch at the DC cable entry point is recommended for emergencies services.
Fig P22.png
Needs String junction box PV array main switch Inverter AC box (400V)
Switchgears and control (Q)
- Isolation • (d) (a) • (d)
- Switching
(Making & breaking
rated current

DC21B
• (d)<nr>DC21B (a) • (d)
- Control • (b) • (d) (e) • (d)
- Over-current protection (c) • (f)
- Protection against
Insulation fault
(h) (h)
RCD type B or A SI
Surge protection (SPD) • type 2 • type 1 or 2
Enclosure (E) Outdoor
Double insulation
Indoor
Double insulation
Standard AC requirement +
grid code requirement

(a) PV array main switch could be included in the inverter. This solution makes inverter service or replacement more difficult.
(b) Remote switching for emergency services located as closely as possible to the PV modules or to the point of entry of DC cables in the building.
(c) No protection is required when the number of string does not exceed 2.
(d) Service and emergency switching
(e) Inverter shall include a protection for anti-islanding (in accordance with VDE 0126 for example)
(f) Overload and short-circuit protection B curve recommended.
(g) This SPD could be unnecessary if there is another SPD in the AC installation at a distance of less than 10 metres.
(h) If the inverter provides no galvanic separation a RCD protection is necessary on AC side. IEC 60364-712 specifies RCD type B. Some local regulations require RCD type A SI

Fig. P23 : 10-100kW single multi MPPT inverter

Share