Chapter G

Sizing and protection of conductors


Overcurrent protection principles: Difference between revisions

From Electrical Installation Guide
m (1 revision)
*>CleanUpAuto
(clean-up 2016 - imported revision step 20)
Line 1: Line 1:
{{Menu_Sizing_and_protection_of_conductors}}
{{Menu_Sizing_and_protection_of_conductors}}


A protective device is provided at the origin of the circuit concerned (see '''Fig. G3 '''and '''Fig. G4''').
A protective device is provided at the origin of the circuit concerned (see '''Fig. G3 '''and {{FigRef|G4}}).
*Acting to cut-off the current in a time shorter than that given by the I<sup>2</sup>t characteristic of the circuit cabling  
*Acting to cut-off the current in a time shorter than that given by the I<sup>2</sup>t characteristic of the circuit cabling  
*But allowing the maximum load current IB to flow indefinitely
*But allowing the maximum load current IB to flow indefinitely
Line 12: Line 12:
:<big>'''S'''</big>: Cross sectional area of insulated conductor (mm<sup>2</sup>)<br>
:<big>'''S'''</big>: Cross sectional area of insulated conductor (mm<sup>2</sup>)<br>
:<big>'''I'''</big>: Short-circuit current (A r.m.s.)<br>
:<big>'''I'''</big>: Short-circuit current (A r.m.s.)<br>
:<big>'''k'''</big>: Insulated conductor constant (values of k<sup>2</sup> are given in Figure G52&nbsp;)<br>
:<big>'''k'''</big>: Insulated conductor constant (values of k<sup>2</sup> are given in {{FigureRef|G52}})<br>


For a given insulated conductor, the maximum permissible current varies according to the environment. For instance, for a high ambient temperature (θa1 &gt; θa2), Iz1 is less than Iz2 (see '''Fig. G5'''). θ means “temperature”.
For a given insulated conductor, the maximum permissible current varies according to the environment. For instance, for a high ambient temperature (θa1 &gt; θa2), Iz1 is less than Iz2 (see {{FigRef|G5}}). θ means “temperature”.
<br>Note: <br>
<br>Note: <br>
:'''ISC''': 3-phase short-circuit current<br>
:'''ISC''': 3-phase short-circuit current<br>
:'''ISCB''': rated 3-ph. short-circuit breaking current of the circuit-breaker<br>
:'''ISCB''': rated 3-ph. short-circuit breaking current of the circuit-breaker<br>
:'''Ir (or Irth)<sup>(1)</sup>'''&nbsp;: regulated “nominal” current level; e.g. a 50 A nominal circuit-breaker can be regulated to have a protective range, i.e. a conventional overcurrent tripping level (see '''Fig. G6 ''') similar to that of a 30 A circuit-breaker.  
:'''Ir (or Irth)<sup>(1)</sup>'''&nbsp;: regulated “nominal” current level; e.g. a 50 A nominal circuit-breaker can be regulated to have a protective range, i.e. a conventional overcurrent tripping level (see '''Fig. G6 ''') similar to that of a 30 A circuit-breaker.


<br>
----
[[File:FigG03.jpg|none]]
[[File:FigG03.jpg|none]]
'''''Fig. G3:'''''<i>&nbsp;Circuit protection by circuit-breaker</i>  
'''''Fig. G3:'''''<i>&nbsp;Circuit protection by circuit-breaker</i>
 
----


[[File:FigG04.jpg|none]]
[[File:FigG04.jpg|none]]
'''''Fig. G4:'''''<i>&nbsp;Circuit protection by fuses</i>  
'''''Fig. G4:'''''<i>&nbsp;Circuit protection by fuses</i>
 
----


[[File:FigG05.jpg|none]]
[[File:FigG05.jpg|none]]

Revision as of 15:27, 25 November 2016


A protective device is provided at the origin of the circuit concerned (see Fig. G3 and Fig. G4).

  • Acting to cut-off the current in a time shorter than that given by the I2t characteristic of the circuit cabling
  • But allowing the maximum load current IB to flow indefinitely


The characteristics of insulated conductors when carrying short-circuit currents can, for periods up to 5 seconds following short-circuit initiation, be determined approximately by the formula:

I2t = k2 S2

which shows that the allowable heat generated is proportional to the squared cross-sectional-area of the condutor.
where

t: Duration of short-circuit current (seconds)
S: Cross sectional area of insulated conductor (mm2)
I: Short-circuit current (A r.m.s.)
k: Insulated conductor constant (values of k2 are given in Figure G52)

For a given insulated conductor, the maximum permissible current varies according to the environment. For instance, for a high ambient temperature (θa1 > θa2), Iz1 is less than Iz2 (see Fig. G5). θ means “temperature”.
Note:

ISC: 3-phase short-circuit current
ISCB: rated 3-ph. short-circuit breaking current of the circuit-breaker
Ir (or Irth)(1) : regulated “nominal” current level; e.g. a 50 A nominal circuit-breaker can be regulated to have a protective range, i.e. a conventional overcurrent tripping level (see Fig. G6 ) similar to that of a 30 A circuit-breaker.
FigG03.jpg

Fig. G3: Circuit protection by circuit-breaker

FigG04.jpg

Fig. G4: Circuit protection by fuses

FigG05.jpg

Fig. G5: I2t characteristic of an insulated conductor at two different ambient temperatures