Worked example of cable calculation: Difference between revisions
(content modified as per 2016 PDF) |
*>CleanUpAuto (clean-up 2016 - imported revision step 20) |
||
Line 5: | Line 5: | ||
== Worked example of cable calculation == | == Worked example of cable calculation == | ||
(see | (see {{FigRef|G65}})<br>The installation is supplied through a 630 kVA transformer. The process requires a high degree of supply continuity and part of the installation can be supplied by a 250 kVA standby generator. The global earthing system is TN-S, except for the most critical loads supplied by an isolation transformer with a downstream IT configuration. | ||
The single-line diagram is shown in | The single-line diagram is shown in {{FigureRef|G65}} below. The results of a computer study for the circuit from transformer T1 down to the cable C7 is reproduced on {{FigureRef|G66}}. This study was carried out with Ecodial (a Schneider Electric software). | ||
This is followed by the same calculations carried out by the simplified method described in this guide. | This is followed by the same calculations carried out by the simplified method described in this guide. | ||
Line 19: | Line 19: | ||
{| class="wikitable | {| class="wikitable" | ||
|- | |- | ||
! colspan="3" | General network characteristics | ! colspan="3" | General network characteristics | ||
Line 29: | Line 29: | ||
| TN-S | | TN-S | ||
| Tripping unit | | Tripping unit | ||
| colspan="2" | Micrologic 2.3 | | colspan="2" | Micrologic 2.3 | ||
|- | |- | ||
| colspan="2" | Neutral distributed | | colspan="2" | Neutral distributed | ||
Line 60: | Line 60: | ||
| colspan="2" | PVC | | colspan="2" | PVC | ||
|- | |- | ||
! colspan="3" | Transformer T1 | ! colspan="3" | Transformer T1 | ||
| Ambient temperature (°C) | | Ambient temperature (°C) | ||
| colspan="2" | 30 | | colspan="2" | 30 | ||
Line 76: | Line 76: | ||
| colspan="2" | Transformer resistance RT (mΩ) | | colspan="2" | Transformer resistance RT (mΩ) | ||
| 3.472 | | 3.472 | ||
| Installation method | | Installation method | ||
| colspan="2" | F | | colspan="2" | F | ||
|- | |- | ||
Line 89: | Line 89: | ||
| colspan="2" | 2 x 95 | | colspan="2" | 2 x 95 | ||
|- | |- | ||
! colspan="3" | Cable C1 | ! colspan="3" | Cable C1 | ||
| PE conductor selected csa (mm<sup>2</sup>) | | PE conductor selected csa (mm<sup>2</sup>) | ||
| colspan="2" | 1 x 95 | | colspan="2" | 1 x 95 | ||
Line 115: | Line 115: | ||
| colspan="2" | Conductor material | | colspan="2" | Conductor material | ||
| Copper | | Copper | ||
! colspan="3" | Switchboard B6 | ! colspan="3" | Switchboard B6 | ||
|- | |- | ||
| colspan="2" | Single-core or multi-core cable | | colspan="2" | Single-core or multi-core cable | ||
Line 129: | Line 129: | ||
| colspan="2" | Number of layers | | colspan="2" | Number of layers | ||
| 1 | | 1 | ||
! colspan="3" | Circuit-breaker Q7 | ! colspan="3" | Circuit-breaker Q7 | ||
|- | |- | ||
| colspan="2" | Phase conductor selected csa (mm<sup>2</sup>) | | colspan="2" | Phase conductor selected csa (mm<sup>2</sup>) | ||
Line 161: | Line 161: | ||
| colspan="2" | Micrologic 2.3 | | colspan="2" | Micrologic 2.3 | ||
|- | |- | ||
! colspan="3" | Circuit-breaker Q1 | ! colspan="3" | Circuit-breaker Q1 | ||
| Overload trip Ir (A) | | Overload trip Ir (A) | ||
| colspan="2" | 258 | | colspan="2" | 258 | ||
|- | |- | ||
| colspan="2" | Load current (A) | | colspan="2" | Load current (A) | ||
Line 172: | Line 172: | ||
| colspan="2" | Type | | colspan="2" | Type | ||
| Compact | | Compact | ||
! colspan="3" | Cable C7 | ! colspan="3" | Cable C7 | ||
|- | |- | ||
| colspan="2" | Reference | | colspan="2" | Reference | ||
Line 197: | Line 197: | ||
| 900 | | 900 | ||
| Conductor material | | Conductor material | ||
| colspan="2" | Copper | | colspan="2" | Copper | ||
|- | |- | ||
| colspan="2" | Short-delay trip Im / Isd (A) | | colspan="2" | Short-delay trip Im / Isd (A) | ||
Line 209: | Line 209: | ||
| colspan="2" | F | | colspan="2" | F | ||
|- | |- | ||
! colspan="3" | Switchboard B2 | ! colspan="3" | Switchboard B2 | ||
| Phase conductor selected csa (mm<sup>2</sup>) | | Phase conductor selected csa (mm<sup>2</sup>) | ||
| colspan="2" | 1 x 95 | | colspan="2" | 1 x 95 | ||
Line 216: | Line 216: | ||
| Linergy 1250 | | Linergy 1250 | ||
| Neutral conductor selected csa (mm<sup>2</sup>) | | Neutral conductor selected csa (mm<sup>2</sup>) | ||
| colspan="2" | | | colspan="2" | - | ||
|- | |- | ||
| colspan="2" | Rated current (A) | | colspan="2" | Rated current (A) | ||
Line 223: | Line 223: | ||
| colspan="2" | 1 x 50 | | colspan="2" | 1 x 50 | ||
|- | |- | ||
! colspan="3" | Circuit breaker Q3 | ! colspan="3" | Circuit breaker Q3 | ||
| Cable voltage drop ΔU (%) | | Cable voltage drop ΔU (%) | ||
| colspan="2" | 0.14 | | colspan="2" | 0.14 | ||
Line 244: | Line 244: | ||
| colspan="2" | Rated current (A) | | colspan="2" | Rated current (A) | ||
| 630 | | 630 | ||
| colspan="3" | | | colspan="3" | | ||
|} | |} | ||
Line 257: | Line 257: | ||
Two single-core PVC-insulated copper cables in parallel will be used for each phase.These cables will be laid on cable trays according to method F. | Two single-core PVC-insulated copper cables in parallel will be used for each phase.These cables will be laid on cable trays according to method F. | ||
Each conductor will therefore carry 433A. | Each conductor will therefore carry 433A. {{FigureRef|G21a}} indicates that for 3 loaded conductors with PVC isolation, the required c.s.a. is 240mm<sup>2</sup>. | ||
The resistance and the inductive reactance, for the two conductors in parallel, and for a length of 5 metres, are: | The resistance and the inductive reactance, for the two conductors in parallel, and for a length of 5 metres, are: | ||
<math>R=\frac{23.7 \times 5}{240\times 2}=0.25 m\Omega</math> (cable resistance: 23.7 mΩ. | <math>R=\frac{23.7 \times 5}{240\times 2}=0.25 m\Omega</math> (cable resistance: 23.7 mΩ.mm<sup>2</sup>/m) | ||
<math>X = 0,08 \times 5 = 0.4 m\Omega</math> (cable reactance: 0.08 mΩ/m) | <math>X = 0,08 \times 5 = 0.4 m\Omega</math> (cable reactance: 0.08 mΩ/m) | ||
Line 270: | Line 270: | ||
Circuit C3 supplies two 150kW loads with cos φ = 0.85, so the total load current is: <math>I_B=\frac{300 \times 10^3}{\sqrt 3 \times 400 \times 0.85}=509 A</math> | Circuit C3 supplies two 150kW loads with cos φ = 0.85, so the total load current is: <math>I_B=\frac{300 \times 10^3}{\sqrt 3 \times 400 \times 0.85}=509 A</math> | ||
Two single-core PVC-insulated copper cables in parallel will be used for each phase. These cables will be laid on cable trays according to method F.<br>Each conductor will therefore carry 255A. | Two single-core PVC-insulated copper cables in parallel will be used for each phase. These cables will be laid on cable trays according to method F.<br>Each conductor will therefore carry 255A. {{FigureRef|G21a}} indicates that for 3 loaded conductors with PVC isolation, the required c.s.a. is 95mm<sup>2</sup>. | ||
The resistance and the inductive reactance, for the two conductors in parallel, and for a length of 20 metres, are: | The resistance and the inductive reactance, for the two conductors in parallel, and for a length of 20 metres, are: | ||
<math>R=\frac{23.7\times 20}{95\times 2}=2.5 m\Omega</math> (cable resistance: 23.7 mΩ. | <math>R=\frac{23.7\times 20}{95\times 2}=2.5 m\Omega</math> (cable resistance: 23.7 mΩ.mm<sup>2</sup>/m) | ||
<math>X = 0.08 \times 20 = 1.6m \Omega</math> (cable reactance: 0.08 mΩ/m) | <math>X = 0.08 \times 20 = 1.6m \Omega</math> (cable reactance: 0.08 mΩ/m) | ||
Line 285: | Line 285: | ||
One single-core PVC-insulated copper cable will be used for each phase. The cables will be laid on cable trays according to method F. | One single-core PVC-insulated copper cable will be used for each phase. The cables will be laid on cable trays according to method F. | ||
Each conductor will therefore carry 255A. | Each conductor will therefore carry 255A. {{FigureRef|G21a}} indicates that for 3 loaded conductors with PVC isolation, the required c.s.a. is 95mm<sup>2</sup>. | ||
The resistance and the inductive reactance for a length of 20 metres is: | The resistance and the inductive reactance for a length of 20 metres is: | ||
<math>R=\frac{23.7\times 5}{95}=1.25m\Omega</math> (cable resistance: 23.7 mΩ. | <math>R=\frac{23.7\times 5}{95}=1.25m\Omega</math> (cable resistance: 23.7 mΩ.mm<sup>2</sup>/m) | ||
<math>X = 0.8 \times 5 = 0.4m\Omega</math> (cable reactance: 0.08 mΩ/m) | <math>X = 0.8 \times 5 = 0.4m\Omega</math> (cable reactance: 0.08 mΩ/m) | ||
Line 296: | Line 296: | ||
=== Calculation of short-circuit currents for the selection of circuit-breakers Q1, Q3, Q7 (see Fig. G67) === | === Calculation of short-circuit currents for the selection of circuit-breakers Q1, Q3, Q7 (see Fig. G67) === | ||
{| class="wikitable | {| class="wikitable" | ||
|- | |- | ||
! Circuit components | ! Circuit components | ||
Line 304: | Line 304: | ||
! Ikmax (kA) | ! Ikmax (kA) | ||
|- | |- | ||
| Upstream MV network, 500MVA fault level (see | | Upstream MV network, 500MVA fault level (see {{FigRef|G34}}) | ||
| 0,035 | | 0,035 | ||
| 0,351 | | 0,351 | ||
Line 310: | Line 310: | ||
| | | | ||
|- | |- | ||
| Transformer 630kVA, 4% (see | | Transformer 630kVA, 4% (see {{FigRef|G35}}) | ||
| 2.9 | | 2.9 | ||
| 10.8 | | 10.8 | ||
Line 331: | Line 331: | ||
| 2.37 | | 2.37 | ||
| 1.6 | | 1.6 | ||
| | | | ||
| | | | ||
|- | |- | ||
| {{Table_HC1}} | Sub-total | | {{Table_HC1}} | Sub-total | ||
Line 357: | Line 357: | ||
=== The protective conductor === | === The protective conductor === | ||
When using the adiabatic method, the minimum c.s.a. for the protective earth conductor (PE) can be calculated by the formula given in | When using the adiabatic method, the minimum c.s.a. for the protective earth conductor (PE) can be calculated by the formula given in {{FigureRef|G58}}: | ||
<math>S_{PE}=\frac{\sqrt {I^2 . t} }{k}</math> | <math>S_{PE}=\frac{\sqrt {I^2 . t} }{k}</math> | ||
Line 376: | Line 376: | ||
=== Protection against indirect-contact hazards === | === Protection against indirect-contact hazards === | ||
For circuit C3 of | For circuit C3 of {{FigureRef|G65}}, Figures F41 and F40, or the formula given '''page F25 '''may be used for a 3-phase 4-wire circuit. | ||
The maximum permitted length of the circuit is given by: | The maximum permitted length of the circuit is given by: | ||
Line 389: | Line 389: | ||
=== Voltage drop === | === Voltage drop === | ||
The voltage drop is calculated using the data given in | The voltage drop is calculated using the data given in {{FigureRef|G28}}, for balanced three-phase circuits, motor power normal service (cos φ = 0.8).<br>The results are summarized on '''figure G68:'''<br> | ||
{| class="wikitable | {| class="wikitable" | ||
|- | |- | ||
! | ! | ||
Line 399: | Line 399: | ||
|- | |- | ||
| c.s.a. | | c.s.a. | ||
| 2 x | | 2 x 240mm<sup>2</sup> | ||
| 2 x | | 2 x 95mm<sup>2</sup> | ||
| 1 x | | 1 x 95mm<sup>2</sup> | ||
|- | |- | ||
| ∆U per conductor<br>(V/A/km)<br>see | | ∆U per conductor<br>(V/A/km)<br>see {{FigRef|G28}} | ||
| 0.22 | | 0.22 | ||
| 0.43 | | 0.43 | ||
Line 429: | Line 429: | ||
|} | |} | ||
'''''Fig. G68:'''''<i> Voltage drop introduced by the different cables</i> | '''''Fig. G68:'''''<i> Voltage drop introduced by the different cables</i> | ||
'''<big> The total voltage drop at the end of cable C7 is then: 0.77%. </big>''' | '''<big> The total voltage drop at the end of cable C7 is then: 0.77%. </big>''' |
Revision as of 15:28, 25 November 2016
Worked example of cable calculation
(see Fig. G65)
The installation is supplied through a 630 kVA transformer. The process requires a high degree of supply continuity and part of the installation can be supplied by a 250 kVA standby generator. The global earthing system is TN-S, except for the most critical loads supplied by an isolation transformer with a downstream IT configuration.
The single-line diagram is shown in Figure G65 below. The results of a computer study for the circuit from transformer T1 down to the cable C7 is reproduced on Figure G66. This study was carried out with Ecodial (a Schneider Electric software).
This is followed by the same calculations carried out by the simplified method described in this guide.
Fig. G65: Example of single-line diagram
Calculation using software Ecodial
General network characteristics | Number of poles and protected poles | 4P4d | ||||
---|---|---|---|---|---|---|
Earthing system | TN-S | Tripping unit | Micrologic 2.3 | |||
Neutral distributed | No | Overload trip Ir (A) | 510 | |||
Voltage (V) | 400 | Short-delay trip Im / Isd (A) | 5100 | |||
Frequency (Hz) | 50 | Cable C3 | ||||
Upstream fault level (MVA) | 500 | Length | 20 | |||
Resistance of MV network (mΩ) | 0.0351 | Maximum load current (A) | 509 | |||
Reactance of MV network (mΩ) | 0.351 | Type of insulation | PVC | |||
Transformer T1 | Ambient temperature (°C) | 30 | ||||
Rating (kVA) | 630 | Conductor material | Copper | |||
Short-circuit impedance voltage (%) | 4 | Single-core or multi-core cable | Single | |||
Transformer resistance RT (mΩ) | 3.472 | Installation method | F | |||
Transformer reactance XT (mΩ) | 10.64 | Phase conductor selected csa (mm2) | 2 x 95 | |||
3-phase short-circuit current Ik3 (kA) | 21.54 | Neutral conductor selected csa (mm2) | 2 x 95 | |||
Cable C1 | PE conductor selected csa (mm2) | 1 x 95 | ||||
Length (m) | 5 | Cable voltage drop ΔU (%) | 0.53 | |||
Maximum load current (A) | 860 | Total voltage drop ΔU (%) | 0.65 | |||
Type of insulation | PVC | 3-phase short-circuit current Ik3 (kA) | 19.1 | |||
Ambient temperature (°C) | 30 | 1-phase-to-earth fault current Id (kA) | 11.5 | |||
Conductor material | Copper | Switchboard B6 | ||||
Single-core or multi-core cable | Single | Reference | Linergy 800 | |||
Installation method | F | Rated current (A) | 750 | |||
Number of layers | 1 | Circuit-breaker Q7 | ||||
Phase conductor selected csa (mm2) | 2 x 240 | Load current (A) | 255 | |||
Neutral conductor selected csa (mm2) | 2 x 240 | Type | Compact | |||
PE conductor selected csa (mm2) | 1 x 120 | Reference | NSX400F | |||
Voltage drop ΔU (%) | 0.122 | Rated current (A) | 400 | |||
3-phase short-circuit current Ik3 (kA) | 21.5 | Number of poles and protected poles | 3P3d | |||
Courant de défaut phase-terre Id (kA) | 15.9 | Tripping unit | Micrologic 2.3 | |||
Circuit-breaker Q1 | Overload trip Ir (A) | 258 | ||||
Load current (A) | 860 | Short-delay trip Im / Isd (A) | 2576 | |||
Type | Compact | Cable C7 | ||||
Reference | NS1000N | Length | 5 | |||
Rated current (A) | 1000 | Maximum load current (A) | 255 | |||
Number of poles and protected poles | 4P4d | Type of insulation | PVC | |||
Tripping unit | Micrologic 5.0 | Ambient temperature (°C) | 30 | |||
Overload trip Ir (A) | 900 | Conductor material | Copper | |||
Short-delay trip Im / Isd (A) | 9000 | Single-core or multi-core cable | Single | |||
Tripping time tm (ms) | 50 | Installation method | F | |||
Switchboard B2 | Phase conductor selected csa (mm2) | 1 x 95 | ||||
Reference | Linergy 1250 | Neutral conductor selected csa (mm2) | - | |||
Rated current (A) | 1050 | PE conductor selected csa (mm2) | 1 x 50 | |||
Circuit breaker Q3 | Cable voltage drop ΔU (%) | 0.14 | ||||
Load current (A) | 509 | Total voltage drop ΔU (%) | 0.79 | |||
Type | Compact | 3-phase short-circuit current Ik3 (kA) | 18.0 | |||
Reference | NSX630F | 1-phase-to-earth fault current Id (kA) | 10.0 | |||
Rated current (A) | 630 |
Fig. G66: Partial results of calculation carried out with Ecodial software (Schneider Electric). The calculation is performed according to Cenelec TR50480
The same calculation using the simplified method recommended in this guide
Dimensioning circuit C1
The MV/LV 630 kVA transformer has a rated no-load voltage of 420 V. Circuit C1 must be suitable for a current of: [math]\displaystyle{ I_B=\frac{630 \times 10^3}{\sqrt 3 \times 420}=866 A }[/math] per phase
Two single-core PVC-insulated copper cables in parallel will be used for each phase.These cables will be laid on cable trays according to method F.
Each conductor will therefore carry 433A. Figure G21a indicates that for 3 loaded conductors with PVC isolation, the required c.s.a. is 240mm2.
The resistance and the inductive reactance, for the two conductors in parallel, and for a length of 5 metres, are:
[math]\displaystyle{ R=\frac{23.7 \times 5}{240\times 2}=0.25 m\Omega }[/math] (cable resistance: 23.7 mΩ.mm2/m)
[math]\displaystyle{ X = 0,08 \times 5 = 0.4 m\Omega }[/math] (cable reactance: 0.08 mΩ/m)
Dimensioning circuit C3
Circuit C3 supplies two 150kW loads with cos φ = 0.85, so the total load current is: [math]\displaystyle{ I_B=\frac{300 \times 10^3}{\sqrt 3 \times 400 \times 0.85}=509 A }[/math]
Two single-core PVC-insulated copper cables in parallel will be used for each phase. These cables will be laid on cable trays according to method F.
Each conductor will therefore carry 255A. Figure G21a indicates that for 3 loaded conductors with PVC isolation, the required c.s.a. is 95mm2.
The resistance and the inductive reactance, for the two conductors in parallel, and for a length of 20 metres, are:
[math]\displaystyle{ R=\frac{23.7\times 20}{95\times 2}=2.5 m\Omega }[/math] (cable resistance: 23.7 mΩ.mm2/m)
[math]\displaystyle{ X = 0.08 \times 20 = 1.6m \Omega }[/math] (cable reactance: 0.08 mΩ/m)
Dimensioning circuit C7
Circuit C7 supplies one 150kW load with cos φ = 0.85, so the total load current is: [math]\displaystyle{ I_B=\frac{150 \times 10^3}{\sqrt 3 \times 400 \times 0.85}=255 A }[/math]
One single-core PVC-insulated copper cable will be used for each phase. The cables will be laid on cable trays according to method F.
Each conductor will therefore carry 255A. Figure G21a indicates that for 3 loaded conductors with PVC isolation, the required c.s.a. is 95mm2.
The resistance and the inductive reactance for a length of 20 metres is:
[math]\displaystyle{ R=\frac{23.7\times 5}{95}=1.25m\Omega }[/math] (cable resistance: 23.7 mΩ.mm2/m)
[math]\displaystyle{ X = 0.8 \times 5 = 0.4m\Omega }[/math] (cable reactance: 0.08 mΩ/m)
Calculation of short-circuit currents for the selection of circuit-breakers Q1, Q3, Q7 (see Fig. G67)
Circuit components | R (mΩ) | X (mΩ) | Z (mΩ) | Ikmax (kA) |
---|---|---|---|---|
Upstream MV network, 500MVA fault level (see Fig. G34) | 0,035 | 0,351 | ||
Transformer 630kVA, 4% (see Fig. G35) | 2.9 | 10.8 | ||
Cable C1 | 0.23 | 0.4 | ||
Sub-total | 3.16 | 11.55 | 11.97 | 20.2 |
Cable C3 | 2.37 | 1.6 | ||
Sub-total | 5.53 | 13.15 | 14.26 | 17 |
Cable C7 | 1.18 | 0.4 | ||
Sub-total | 6.71 | 13.55 | 15.12 | 16 |
Fig. G67: Example of short-circuit current evaluation
The protective conductor
When using the adiabatic method, the minimum c.s.a. for the protective earth conductor (PE) can be calculated by the formula given in Figure G58:
[math]\displaystyle{ S_{PE}=\frac{\sqrt {I^2 . t} }{k} }[/math]
For circuit C1, I = 20.2kA and k = 143.
t is the maximum operating time of the MV protection, e.g. 0.5s
This gives:
[math]\displaystyle{ S_{PE}=\frac{\sqrt {I^2 . t} }{k}=\frac {20200 \times \sqrt {0.5} }{143}=100 mm^2 }[/math]
A single 120 mm2 conductor is therefore largely sufficient, provided that it also satisfies the requirements for indirect contact protection (i.e. that its impedance is sufficiently low).
Generally, for circuits with phase conductor c.s.a. Sph ≥ 50 mm2, the PE conductor minimum c.s.a. will be Sph / 2. Then, for circuit C3, the PE conductor will be 95mm2, and for circuit C7, the PE conductor will be 50mm2.
Protection against indirect-contact hazards
For circuit C3 of Figure G65, Figures F41 and F40, or the formula given page F25 may be used for a 3-phase 4-wire circuit.
The maximum permitted length of the circuit is given by:
[math]\displaystyle{ L_{max}=\frac{0.8 \times U_0 \times S_{ph} }{\rho \times \left ( 1 + m \right )\times I_a } }[/math]
[math]\displaystyle{ L_{max}=\frac{0.8 \times 230 \times 2 \times 95}{23.7 \times 10^{-3}\times \left ( 1 + 2 \right )\times 630\times 11 } = 71 m }[/math]
(The value in the denominator 630 x 11 is the maximum current level at which the instantaneous short-circuit magnetic trip of the 630 A circuit-breaker operates).
The length of 20 metres is therefore fully protected by “instantaneous” over-current devices.
Voltage drop
The voltage drop is calculated using the data given in Figure G28, for balanced three-phase circuits, motor power normal service (cos φ = 0.8).
The results are summarized on figure G68:
C1 | C3 | C7 | |
---|---|---|---|
c.s.a. | 2 x 240mm2 | 2 x 95mm2 | 1 x 95mm2 |
∆U per conductor (V/A/km) see Fig. G28 |
0.22 | 0.43 | 0.43 |
Load current (A) | 866 | 509 | 255 |
Length (m) | 5 | 20 | 5 |
Voltage drop (V) | 0.48 | 2.19 | 0.55 |
Voltage drop (%) | 0.12 | 0.55 | 0.14 |
Fig. G68: Voltage drop introduced by the different cables
The total voltage drop at the end of cable C7 is then: 0.77%.