Chapter G

Sizing and protection of conductors


General method for cable sizing: Difference between revisions

From Electrical Installation Guide
m (1 revision: no page modification, previous revision = imported ch.G pages cleaned-up)
(Cleanup_2016)
Line 1: Line 1:
{{Menu_Sizing_and_protection_of_conductors}}  
{{Menu_Sizing_and_protection_of_conductors}}  
__TOC__
__TOC__
== Possible methods of installation for different types of conductors or cables  ==
== Possible methods of installation for different types of conductors or cables  ==


The different admissible methods of installation are listed in {{FigureRef|G8}}, in conjonction with the different types of conductors and cables.  
The different admissible methods of installation are listed in {{FigureRef|G8}}, in conjonction with the different types of conductors and cables.  


{| class="wikitable"
{{TableStart|Tab1180|5col}}
|-
|-
! width="100" colspan="2" rowspan="2" | Conductors and cables  
! colspan="2" rowspan="2" | Conductors cables  
! colspan="11" | Method of installation
! colspan="11" | Method of installation
|-
|-
Line 13: Line 15:
! Clipped direct  
! Clipped direct  
! Conduit systems
! Conduit systems
! Cable trunking systems (including skirting trunking,<br>flush floor trunking)  
! Cable trunking systems (including skirting trunking,
flush floor trunking)  
! Cable ducting systems
! Cable ducting systems
! Cable ladder, <br>Cable tray, Cable rackets  
! Cable ladder,  
Cable tray, Cable rackets  
! On insulators  
! On insulators  
! Support wire <br>
! Support wire  
|-
|-
| colspan="2" | Bare conductors  
| colspan="2" | Bare conductors  
Line 29: Line 33:
| -
| -
|-
|-
| colspan="2" | Insulated conductors <sup> (2) </sup>
| colspan="2" | Insulated conductors{{TabRef|Tab1180|b}}
| -  
| -  
| -  
| -  
| +  
| +  
| + <sup> (1) </sup>
| +{{TabRef|Tab1180|a}}
| +  
| +  
| -  
| -  
Line 39: Line 43:
| -
| -
|-
|-
| rowspan="2" | Sheathed cables <br>(including <br>armoured and mineral <br>insulated)  
| rowspan="2" | Sheathed cables  
(including armoured and mineral insulated)  
| Multi-core  
| Multi-core  
| +  
| +  
Line 59: Line 64:
| 0  
| 0  
| +
| +
|}
|-
|colspan="10" | + : Permitted.
­– : Not permitted. <br>
0 : Not applicable, or not normally used in practice.
|-
{{TableEnd|Tab1180|G8|Selection of wiring systems (table A.52.1 of IEC 60364-5-52)
|a|Insulated conductors are admitted if the cable trunking systems provide at least he degree of protection IP4X or IPXXD and if the cover can only be removed by means of a tool or a deliberate action.
|b|Insulated conductors which are used as protective conductors or protective bonding conductors may use any appropriate method of installation and need not be laid in conduits, trunking or ducting systems.}}


+ Permitted.<br>­– Not permitted.<br>0 Not applicable, or not normally used in practice.
== Possible methods of installation for different situations:  ==


(1) Insulated conductors are admitted if the cable trunking systems provide at least he degree of protection IP4X or IPXXD and if the cover can only be removed by means of a tool or a deliberate action.
Different methods of installation can be implemented in different situations. The possible combinations are presented in {{FigureRef|G9}}.


(2) Insulated conductors which are used as protective conductors or protective bonding conductors may use any appropriate method of installation and need not be laid in conduits, trunking or ducting systems.
The number given in this table refer to the different wiring systems considered.


'''''Fig.G8:&nbsp;'''''<i>Selection of wiring systems (table A.52.1 of IEC 60364-5-52)</i>
{{TableStart|Tab1181|5col}}
 
 
== Possible methods of installation for different situations:  ==
 
Different methods of installation can be implemented in different situations. The possible combinations are presented in {{FigureRef|G9}}.<br>The number given in this table refer to the different wiring systems considered.
 
{| class="wikitable"
|-
|-
! width="100" colspan="2" rowspan="2" |  Situations
! colspan="2" rowspan="2" |  Situations
! colspan="9" | Method of installation
! colspan="9" | Method of installation
|-
|-
Line 86: Line 91:
! Cable ladder, cable tray, cable brackets  
! Cable ladder, cable tray, cable brackets  
! On insulators  
! On insulators  
! Support wire<br>
! Support wire
|-
|-
| rowspan="2" | Building voids
| rowspan="2" | Building voids
Line 109: Line 114:
| 0
| 0
|-
|-
| width="100" colspan="2" rowspan="1" | Cable channel  
|colspan="2" rowspan="1" | Cable channel  
| ­56  
| ­56  
| 56  
| 56  
Line 119: Line 124:
| -
| -
|-
|-
| width="100" colspan="2" rowspan="1" | Buried in ground  
| colspan="2" rowspan="1" | Buried in ground  
| 72, 73  
| 72, 73  
| 0  
| 0  
Line 129: Line 134:
| -
| -
|-
|-
| width="100" colspan="2" rowspan="1" | Embedded in structure
| colspan="2" rowspan="1" | Embedded in structure
| 57, 58  
| 57, 58  
| 3  
| 3  
Line 139: Line 144:
| -
| -
|-
|-
| width="100" colspan="2" rowspan="1" | Surface mounted  
| colspan="2" rowspan="1" | Surface mounted  
| -  
| -  
| 20, 21, 22, 23, 33  
| 20, 21, 22, 23, 33  
Line 149: Line 154:
| -
| -
|-
|-
| width="100" colspan="2" rowspan="1" | Overhead/free in air
| colspan="2" rowspan="1" | Overhead/free in air
| -  
| -  
| 33  
| 33  
Line 159: Line 164:
| 35
| 35
|-
|-
| width="100" colspan="2" rowspan="1" | Window frames  
| colspan="2" rowspan="1" | Window frames  
| 16  
| 16  
| 0  
| 0  
Line 169: Line 174:
| -
| -
|-
|-
| width="100" colspan="2" rowspan="1" | Architrave  
| colspan="2" rowspan="1" | Architrave  
| 15  
| 15  
| 0  
| 0  
Line 179: Line 184:
| -
| -
|-
|-
| width="100" colspan="2" rowspan="1" | Immersed 1  
| colspan="2" rowspan="1" | Immersed 1  
| +  
| +  
| +
| +
Line 188: Line 193:
| -  
| -  
| -
| -
|}
|-
 
|colspan="10" | ­– : Not permitted.  
Not permitted.<br>0 Not applicable, or not normally used in practice.<br> + Follow manufacturer’s instructions.
0 : Not applicable, or not normally used in practice. <br>
 
+ : Follow manufacturer’s instructions.
Note: The number in each box, e.g. 40, 46, refers to the number of the method of installation in Table A.52.3.
{{TableEnd|Tab1181|G9|Erection of wiring systems (table A.52.2 of IEC 60364-5-52)
 
||Note: The number in each box, e.g. 40, 46, refers to the number of the method of installation in Table A.52.3.}}
'''''Fig.G9:&nbsp;'''Erection of wiring systems (table A.52.2 of IEC 60364-5-52)''


== Examples of wiring systems and reference methods of installations  ==


== Examples of wiring systems and reference methods of installations  ==
An illustration of some of the many different wiring systems and methods of installation is provided in {{FigureRef|G10}}.


An illustration of some of the many different wiring systems and methods of installation is provided in {{FigureRef|G10}}.<br>Several reference methods are defined (with code letters A to G), grouping installation methods having the same characteristics relative to the current-carrying capacities of the wiring systems.  
Several reference methods are defined (with code letters A to G), grouping installation methods having the same characteristics relative to the current-carrying capacities of the wiring systems.  


{| class="wikitable"
{{TableStart|Tab1182|5col}}
|-
|-
! Item&nbsp;No.
! Item No.
! Methods of installation  
! Methods of installation  
! Description  
! Description  
Line 209: Line 214:
|-
|-
| 1  
| 1  
| [[File:FigG10bis-1a.jpg]]  
| [[File:DB422287.svg]]
| Insulated conductors or single-core cables in conduit in a thermally insulated wall  
| Insulated conductors or single-core cables in conduit in a thermally insulated wall  
| A1
| A1
|-
|-
| 2  
| 2  
| [[File:FigG10bis-1b.jpg]]  
| [[File:DB422287.svg]]
| Multi-core cables in conduit in a thermally insulated wall  
| Multi-core cables in conduit in a thermally insulated wall  
| A2
| A2
|-
|-
| 4  
| 4  
| [[File:FigG10bis-1c.jpg]]  
| [[File:DB422288.svg]]  
| Insulated conductors or single-core cables in conduit on a wooden, or masonry wall or spaced less than 0,3 x conduit diameter from it  
| Insulated conductors or single-core cables in conduit on a wooden, or masonry wall or spaced less than 0,3 x conduit diameter from it  
| B1
| B1
|-
|-
| 5  
| 5  
| [[File:FigG10bis-1d.jpg]]  
| [[File:DB422289.svg]]
| Multi-core cable in conduit on a wooden, or mansonry wall or spaced less than 0,3 x conduit diameter <br>from it  
| Multi-core cable in conduit on a wooden, or mansonry wall or spaced less than 0,3 x conduit diameter <br>from it  
| B2<br>
| B2<br>
|-
|-
| 20  
| 20  
| [[File:FigG10bis-1e.jpg]]  
| [[File:DB422290.svg]]
| Single-core or multi-core cables: - fixed on, or sapced less than 0.3 x cable diameter from a wooden wall  
| Single-core or multi-core cables: - fixed on, or sapced less than 0.3 x cable diameter from a wooden wall  
| C
| C
|-
|-
| 30  
| 30  
| [[File:FigG10bis-1f.jpg]] <br>[[File:FigG10bis-1g.jpg]]  
| [[File:DB422291.svg]] <br> [[File:DB422292.svg]]
| Single-core or multi-core cables:  
| Single-core or multi-core cables:  


Line 241: Line 246:
|-
|-
| 31  
| 31  
| [[File:FigG10bis-2a.jpg]] <br>[[File:FigG10bis-2b.jpg]]  
| [[File:DB422291.svg]] <br> [[File:DB422292.svg]]  
| Single-core or multi-core cables:
| Single-core or multi-core cables:
On perforated tray run horizontally or vertically  
On perforated tray run horizontally or vertically  
| E or F
| E or F
|-
|-
| 36  
| 36  
| [[File:FigG10bis-2c.jpg]]  
| [[File:DB422293.svg]]
| Bare or insulated conductors on insulators  
| Bare or insulated conductors on insulators  
| G
| G
|-
|-
| 70  
| 70  
| [[File:FigG10bis-2d.jpg]]  
| [[File:DB422294.svg]]
| Multi-core cables in conduit or in cable ducting in the ground  
| Multi-core cables in conduit or in cable ducting in the ground  
| D1
| D1
|-
|-
| 71  
| 71  
| [[File:FigG10bis-2e.jpg]]  
| [[File:DB422295.svg]]  
| Single-core cable in conduit or in cable ducting in the ground  
| Single-core cable in conduit or in cable ducting in the ground  
| D1
| D1
|}
|-
 
{{TableEnd|Tab1182|G10|Examples of methods of installation (part of table A.52.3 of IEC 60364-5-52)}}
'''''Fig.G10:'''''<i>&nbsp;Examples of methods of installation (part of table A.52.3 of IEC 60364-5-52)</i>
 


== Maximum operating temperature:  ==
== Maximum operating temperature:  ==
Line 270: Line 272:
The current-carrying capacities given in the subsequent tables have been determined so that the maximum insulation temperature is not exceeded for sustained periods of time.<br>For different type of insulation material, the maximum admissible temperature is given in {{FigureRef|G11}}.  
The current-carrying capacities given in the subsequent tables have been determined so that the maximum insulation temperature is not exceeded for sustained periods of time.<br>For different type of insulation material, the maximum admissible temperature is given in {{FigureRef|G11}}.  


{| class="wikitable"
{{TableStart|Tab1183|5col}}
|-
|-
! Type of insulation  
! Type of insulation  
Line 285: Line 287:
|-
|-
| Mineral (bare not exposed to touch and not in contact with combustible material)  
| Mineral (bare not exposed to touch and not in contact with combustible material)  
| 105 at the seath<br>
| 105 at the seath
|}
|-
 
{{TableEnd|Tab1183|G11|Maximum operating temperatures for types of insulation (table 52.1 of IEC 60364-5-52)}}
'''''Fig.G11:'''''<i>&nbsp;Maximum operating temperatures for types of insulation (table 52.1 of IEC 60364-5-52)</i>
 


== Correction factors  ==
== Correction factors  ==
Line 299: Line 299:
*Ambient temperature
*Ambient temperature


The current-carrying capacities of cables in the air are based on an average air temperature equal to 30 °C. For other temperatures, the correction factor is given in {{FigureRef|G12}} for PVC, EPR and XLPE insulation material.<br>The related correction factor is here noted k<sub>1</sub>.  
The current-carrying capacities of cables in the air are based on an average air temperature equal to 30 °C. For other temperatures, the correction factor is given in {{FigureRef|G12}} for PVC, EPR and XLPE insulation material.
 
The related correction factor is here noted k<sub>1</sub>.  


{| class="wikitable"
{{TableStart|Tab1184|5col}}
|-
|-
! rowspan="2" | Ambient temperature °C  
! rowspan="2" | Ambient temperature °C  
Line 368: Line 370:
| -  
| -  
| 0.41
| 0.41
|}
|-
{{TableEnd|Tab1184|G12|Correction factors for ambient air temperatures other than 30 °C to be applied to the current-carrying capacities for cables in the air (from table B.52.14 of IEC 60364-5-52)}}


'''''Fig.G12:'''''<i>&nbsp;Correction factors for ambient air temperatures other than 30 °C to be applied to the current-carrying capacities for cables in the air (from table B.52.14 of IEC 60364-5-52)</i> <br>
The current-carrying capacities of cables in the ground are based on an average ground temperature equal to 20 °C. For other temperatures, the correction factor is given in {{FigureRef|G13}} for PVC, EPR and XLPE insulation material.


The current-carrying capacities of cables in the ground are based on an average ground temperature equal to 20 °C. For other temperatures, the correction factor is given in {{FigureRef|G13}} for PVC, EPR and XLPE insulation material.<br>The related correction factor is here noted k<sub>2</sub>.  
The related correction factor is here noted k<sub>2</sub>.  


{| class="wikitable"
{{TableStart|Tab1185|5col}}
|-
|-
! rowspan="2" | Ground temperature °C  
! rowspan="2" | Ground temperature °C  
Line 441: Line 444:
| -  
| -  
| 0.38
| 0.38
|}
|-
{{TableEnd|Tab1185|G13|Correction factors for ambient ground temperatures other than 20 °C to be applied to the current-carrying capacities for cables in ducts in the ground (from table B.52.15 of IEC 60364-5-52)}}


'''''Fig. G13:'''''<i>&nbsp;Correction factors for ambient ground temperatures other than 20 °C to be applied to the current-carrying capacities for cables in ducts in the ground (from table B.52.15 of IEC 60364-5-52)</i>
*Soil thermal resistivity


*Soil thermal resistivity
The current-carrying capacities of cables in the ground are based on a ground resistivity equal to 2.5 K•m/W. For other values, the correction factor is given in {{FigureRef|G14}}.


The current-carrying capacities of cables in the ground are based on a ground resistivity equal to 2.5 K•m/W. For other values, the correction factor is given in {{FigureRef|G14}}.<br>The related correction factor is here noted k3.  
The related correction factor is here noted k3.  


{| class="wikitable"
{{TableStart|Tab1186|5col}}
|-
|-
! colspan="8" |
! colspan="8" |
Line 479: Line 483:
| 1
| 1
| 0.90
| 0.90
|}
|-
 
{{TableEnd|Tab1186|G14|Correction factors for cables in buried ducts for soil thermal resistivities other than 2.5 K.m/W to be applied to the current-carrying capacities for reference method D (table B.52.16 of IEC 60364-5-52)
Note 1: The correction factors given have been averaged over the range of conductor sizes and types of installation included in Tables B.52.2 to B.52.5.
|| '''Note 1''': The correction factors given have been averaged over the range of conductor sizes and types of installation included in Tables B.52.2 to B.52.5.  
 
: The overall accuracy of correction factors is within ±5 %.
The overall accuracy of correction factors is within ±5 %.
|| '''Note 2''': The correction factors are applicable to cables drawn into buried ducts; for cables laid direct in the ground the correction factors for thermal resistivities less than 2.5 K•m/W will be higher. Where more precise values are required they may be calculated by methods given in the IEC 60287 series.
 
|| '''Note 3''': The correction factors are applicable to ducts buried at depths of up to 0.8 m.
Note 2: The correction factors are applicable to cables drawn into buried ducts; for cables laid direct in the ground the correction factors for thermal resistivities less than 2.5 K•m/W will be higher. Where more precise values are required they may be calculated by methods given in the IEC 60287 series.
|| '''Note 4''': It is assumed that the soil properties are uniform. No allowance had been made for the possibility of moisture migration which can lead to a region of high thermal resistivity around the cable. If partial drying out of the soil is foreseen, the permissible current rating should be derived by the methods specified in the IEC 60287 series.}}
 
Note 3: The correction factors are applicable to ducts buried at depths of up to 0.8 m.
 
Note 4: It is assumed that the soil properties are uniform. No allowance had been made for the possibility of moisture migration which can lead to a region of high thermal resistivity around the cable. If partial drying out of the soil is foreseen, the permissible current rating should be derived by the methods specified in the IEC 60287 series.
 
'''''Fig.G14:'''''<i>&nbsp;Correction factors for cables in buried ducts for soil thermal resistivities other than 2.5 K.m/W to be applied to the current-carrying capacities for reference method D (table B.52.16 of IEC 60364-5-52)</i>
 


Based on experience, a relationship exist between the soil nature and resistivity. Then, empiric values of correction factors k3 are proposed in {{FigureRef|G15}}, depending on the nature of soil.  
Based on experience, a relationship exist between the soil nature and resistivity. Then, empiric values of correction factors k3 are proposed in {{FigureRef|G15}}, depending on the nature of soil.  


{| class="wikitable"
{{TableStart|Tab1187|5col}}
|-
|-
! Nature of soil  
! Nature of soil  
Line 515: Line 512:
| Very dry soil (sunbaked)  
| Very dry soil (sunbaked)  
| 0.86
| 0.86
|}
|-
 
{{TableEnd|Tab1186|G15|Correction factor k3 depending on the nature of soil}}
'''''Fig.G15:'''&nbsp;Correction factor k3 depending on the nature of soil''
 


*Grouping of conductors or cables
*Grouping of conductors or cables
The current-carrying capacities given in the subsequent tables relate to single circuits consisting of the following numbers of loaded conductors:<br>&nbsp; - &nbsp;Two insulated conductors or two single-core cables, or one twin-core cable (applicable to single-phase circuits);<br>&nbsp; - &nbsp;Three insulated conductors or three single-core cables, or one three-core cable (applicable to three-phase circuits).<br>Where more insulated conductors or cables are installed in the same group, a group reduction factor (here noted k4) shall be applied.<br>Examples are given in '''Figures G16 to G18 '''for different configurations (installation methods, in free air or in the ground).<br>{{FigureRef|G16}} gives the values of correction factor k4 for different configurations of unburied cables or conductors, grouping of more than one circuit or multi-core cables.  
The current-carrying capacities given in the subsequent tables relate to single circuits consisting of the following numbers of loaded conductors:<br>&nbsp; - &nbsp;Two insulated conductors or two single-core cables, or one twin-core cable (applicable to single-phase circuits);<br>&nbsp; - &nbsp;Three insulated conductors or three single-core cables, or one three-core cable (applicable to three-phase circuits).<br>Where more insulated conductors or cables are installed in the same group, a group reduction factor (here noted k4) shall be applied.<br>Examples are given in '''Figures G16 to G18 '''for different configurations (installation methods, in free air or in the ground).<br>{{FigureRef|G16}} gives the values of correction factor k4 for different configurations of unburied cables or conductors, grouping of more than one circuit or multi-core cables.  


{| class="wikitable"
{{TableStart|Tab1188|5col}}
|-
|-
! rowspan="2" | Arrangement (cables touching)  
! rowspan="2" | Arrangement (cables touching)  
Line 604: Line 598:
| 0.78  
| 0.78  
| 0.78
| 0.78
|}
|-
 
{{TableEnd|Tab1188|G16|Reduction factors for groups of more than one circuit or of more than one multi-core cable (table B.52.17 of IEC 60364-5-52)}}
'''''Fig. G16:'''&nbsp;Reduction factors for groups of more than one circuit or of more than one multi-core cable (table B.52.17 of IEC 60364-5-52)''
 


{{FigureRef|G17}} gives the values of correction factor k<sub>4</sub> for different configurations of unburied cables or conductors, for groups of more than one circuit of single-core cables in free air.  
{{FigureRef|G17}} gives the values of correction factor k<sub>4</sub> for different configurations of unburied cables or conductors, for groups of more than one circuit of single-core cables in free air.  


{| class="wikitable"
{{TableStart|Tab1189|5col}}
|-
|-
! colspan="3" rowspan="2" | Method of installation  
! colspan="3" rowspan="2" | Method of installation  
Line 732: Line 724:
| 0.94  
| 0.94  
| 0.90
| 0.90
|}
|-
 
{{TableEnd|Tab1189|G17|Reduction factors for groups of more than one circuit of single-core cables to be applied to reference rating for one circuit of single-core cables in free air - Method of installation F. (table B.52.21 of IEC 60364-5-52)}}
'''''Fig. G17:'''''<i>&nbsp;Reduction factors for groups of more than one circuit of single-core cables to be applied to reference rating for one circuit of single-core cables in free air - Method of installation F. (table B.52.21 of IEC 60364-5-52)</i>
 


{{FigureRef|G18}} gives the values of correction factor k4 for different configurations of cables or conductors laid directly in the ground.<br>
{{FigureRef|G18}} gives the values of correction factor k4 for different configurations of cables or conductors laid directly in the ground.<br>


{| class="wikitable"
{{TableStart|Tab1190|5col}}
|-
|-
! rowspan="2" | Number of circuits&nbsp;<br>&nbsp; <br>
! rowspan="2" | Number of circuits&nbsp;<br>&nbsp; <br>
Line 826: Line 816:
| 0.53  
| 0.53  
| 0.66
| 0.66
|}
|-
 
{{TableEnd|Tab1190|G18|Reduction factors for more than one circuit, single-core or multi-core cables laid directly in the ground. Installation method D. (table B.52.18 of IEC 60364-5-52)}}
 
<sup>'''a'''</sup>'''Multi-core cables<br>'''[[File:FigG18.jpg|none]]
<sup>'''a'''</sup>'''Single-core cables<br>'''<br>
 
'''''Fig. G18:'''&nbsp;Reduction factors for more than one circuit, single-core or multi-core cables laid directly in the ground. Installation method D. (table B.52.18 of IEC 60364-5-52)''
 


*Harmonic current
*Harmonic current
The current-carrying capacity of three-phase, 4-core or 5-core cables is based on the assumption that only 3 conductors are fully loaded.<br>However, when harmonic currents are circulating, the neutral current can be significant, and even higher than the phase currents. This is due to the fact that the 3<sup>rd</sup> harmonic currents of the three phases do not cancel each other, and sum up in the neutral conductor.<br>This of course affects the current-carrying capacity of the cable, and a correction factor noted here k5 shall be applied.<br>In addition, if the 3<sup>rd</sup> harmonic percentage h<sub>3</sub> is greater than 33%, the neutral current is greater than the phase current and the cable size selection is based on the neutral current. The heating effect of harmonic currents in the phase conductors has also to be taken into account.<br>The values of k5 depending on the 3<sup>rd</sup> harmonic content are given in {{FigureRef|G19}}.  
The current-carrying capacity of three-phase, 4-core or 5-core cables is based on the assumption that only 3 conductors are fully loaded.<br>However, when harmonic currents are circulating, the neutral current can be significant, and even higher than the phase currents. This is due to the fact that the 3<sup>rd</sup> harmonic currents of the three phases do not cancel each other, and sum up in the neutral conductor.<br>This of course affects the current-carrying capacity of the cable, and a correction factor noted here k5 shall be applied.<br>In addition, if the 3<sup>rd</sup> harmonic percentage h<sub>3</sub> is greater than 33%, the neutral current is greater than the phase current and the cable size selection is based on the neutral current. The heating effect of harmonic currents in the phase conductors has also to be taken into account.<br>The values of k5 depending on the 3<sup>rd</sup> harmonic content are given in {{FigureRef|G19}}.  



Revision as of 23:46, 27 November 2016


Possible methods of installation for different types of conductors or cables

The different admissible methods of installation are listed in Figure G8, in conjonction with the different types of conductors and cables.

Conductors cables Method of installation
Without fixings Clipped direct Conduit systems Cable trunking systems (including skirting trunking,

flush floor trunking)

Cable ducting systems Cable ladder,

Cable tray, Cable rackets

On insulators Support wire
Bare conductors - - - - - - + -
Insulated conductors[b] - - + +[a] + - + -
Sheathed cables

(including armoured and mineral insulated)

Multi-core + + + + + + 0 +
Single-core 0 + + + + + 0 +
+ : Permitted.

­– : Not permitted.
0 : Not applicable, or not normally used in practice.

[a] Insulated conductors are admitted if the cable trunking systems provide at least he degree of protection IP4X or IPXXD and if the cover can only be removed by means of a tool or a deliberate action.
[b] Insulated conductors which are used as protective conductors or protective bonding conductors may use any appropriate method of installation and need not be laid in conduits, trunking or ducting systems.

Fig. G8 – Selection of wiring systems (table A.52.1 of IEC 60364-5-52)

Possible methods of installation for different situations:

Different methods of installation can be implemented in different situations. The possible combinations are presented in Figure G9.

The number given in this table refer to the different wiring systems considered.

Situations Method of installation
Without fixings Clipped direct Conduit Systems Cable trunking (including skirting trunking, flush floor trunking) Cable ducting systems Cable ladder, cable tray, cable brackets On insulators Support wire
Building voids Accessible 40 33 41, 42 6, 7, 8, 9,12 43, 44 30, 31, 32, 33, 34 - 0
Not accessible 40 0 41, 42 0 43 0 0 0
Cable channel ­56 56 54, 55 0 30, 31, 32, 34 - -
Buried in ground 72, 73 0 70, 71 - 70, 71 0 - -
Embedded in structure 57, 58 3 1, 2, 59, 60 50, 51, 52, 53 46, 45 0 - -
Surface mounted - 20, 21, 22, 23, 33 4, 5 6, 7, 8, 9, 12 6, 7, 8, 9 30, 31, 32, 34 36 -
Overhead/free in air - 33 0 10, 11 10, 11 30, 31, 32, 34 36 35
Window frames 16 0 16 0 0 0 - -
Architrave 15 0 15 0 0 0 - -
Immersed 1 + + + - + 0 - -
­– : Not permitted.

0 : Not applicable, or not normally used in practice.
+ : Follow manufacturer’s instructions.

Note: The number in each box, e.g. 40, 46, refers to the number of the method of installation in Table A.52.3.

Fig. G9 – Erection of wiring systems (table A.52.2 of IEC 60364-5-52)

Examples of wiring systems and reference methods of installations

An illustration of some of the many different wiring systems and methods of installation is provided in Figure G10.

Several reference methods are defined (with code letters A to G), grouping installation methods having the same characteristics relative to the current-carrying capacities of the wiring systems.

Item No. Methods of installation Description Reference method of installation to be used to obtain current-carrying capacity
1 DB422287.svg Insulated conductors or single-core cables in conduit in a thermally insulated wall A1
2 DB422287.svg Multi-core cables in conduit in a thermally insulated wall A2
4 DB422288.svg Insulated conductors or single-core cables in conduit on a wooden, or masonry wall or spaced less than 0,3 x conduit diameter from it B1
5 DB422289.svg Multi-core cable in conduit on a wooden, or mansonry wall or spaced less than 0,3 x conduit diameter
from it
B2
20 DB422290.svg Single-core or multi-core cables: - fixed on, or sapced less than 0.3 x cable diameter from a wooden wall C
30 DB422291.svg
DB422292.svg
Single-core or multi-core cables:

On unperforated tray run horizontally or vertically

C
31 DB422291.svg
DB422292.svg
Single-core or multi-core cables:

On perforated tray run horizontally or vertically

E or F
36 DB422293.svg Bare or insulated conductors on insulators G
70 DB422294.svg Multi-core cables in conduit or in cable ducting in the ground D1
71 DB422295.svg Single-core cable in conduit or in cable ducting in the ground D1
Fig. G10 – Examples of methods of installation (part of table A.52.3 of IEC 60364-5-52)

Maximum operating temperature:

The current-carrying capacities given in the subsequent tables have been determined so that the maximum insulation temperature is not exceeded for sustained periods of time.
For different type of insulation material, the maximum admissible temperature is given in Figure G11.

Type of insulation Temperature limit °C
Polyvinyl-chloride (PVC) 70 at the conductor
Cross-linked polyethylene (XLPE) and ethylene propylene rubber (EPR) 90 at the conductor
Mineral (PVC covered or bare exposed to touch) 70 at the sheath
Mineral (bare not exposed to touch and not in contact with combustible material) 105 at the seath
Fig. G11 – Maximum operating temperatures for types of insulation (table 52.1 of IEC 60364-5-52)

Correction factors

In order to take environment or special conditions of installation into account, correction factors have been introduced.
The cross sectional area of cables is determined using the rated load current IB divided by different correction factors, k1, k2, ...: [math]\displaystyle{ I^{'}{_B}=\frac{I_B}{k_1.k_2...} }[/math]

I’B is the corrected load current, to be compared to the current-carrying capacity of the considered cable.

  • Ambient temperature

The current-carrying capacities of cables in the air are based on an average air temperature equal to 30 °C. For other temperatures, the correction factor is given in Figure G12 for PVC, EPR and XLPE insulation material.

The related correction factor is here noted k1.

Ambient temperature °C Insulation
PVC XLPE and EPR
10 1.22 1.15
15 1.17 1.12
20 1.12 1.08
25 1.06 1.04
30 1 1
35 0.94 0.96
40 0.87 0.91
45 0.79 0.87
50 0.71 0.82
55 0.61 0.76
60 0.50 0.71
65 - 0.65
70 - 0.58
75 - 0.50
80 - 0.41
Fig. G12 – Correction factors for ambient air temperatures other than 30 °C to be applied to the current-carrying capacities for cables in the air (from table B.52.14 of IEC 60364-5-52)

The current-carrying capacities of cables in the ground are based on an average ground temperature equal to 20 °C. For other temperatures, the correction factor is given in Figure G13 for PVC, EPR and XLPE insulation material.

The related correction factor is here noted k2.

Ground temperature °C Insulation
PVC XLPE and EPR
10 1.10 1.07
15 1.05 1.04
20 1 1
25 0.95 0.96
30 0.89 0.93
35 0.84 0.89
40 0.77 0.85
45 0.71 0.80
50 0.63 0.76
55 0.55 0.71
60 0.45 0.65
65 - 0.60
70 - 0.53
75 - 0.46
80 - 0.38
Fig. G13 – Correction factors for ambient ground temperatures other than 20 °C to be applied to the current-carrying capacities for cables in ducts in the ground (from table B.52.15 of IEC 60364-5-52)
  • Soil thermal resistivity

The current-carrying capacities of cables in the ground are based on a ground resistivity equal to 2.5 K•m/W. For other values, the correction factor is given in Figure G14.

The related correction factor is here noted k3.

Thermal resistivity, K•m/W 0.5 0.7 1 1.5 2 2.5 3
Correction factor for cables in buried ducts 1.28 1.20 1.18 1.1 1.05 1 0.96
Correction factor for direct buried cables 1.88 1.62 1.5 1.28 1.12 1 0.90

Note 1: The correction factors given have been averaged over the range of conductor sizes and types of installation included in Tables B.52.2 to B.52.5.

The overall accuracy of correction factors is within ±5 %.
Note 2: The correction factors are applicable to cables drawn into buried ducts; for cables laid direct in the ground the correction factors for thermal resistivities less than 2.5 K•m/W will be higher. Where more precise values are required they may be calculated by methods given in the IEC 60287 series.
Note 3: The correction factors are applicable to ducts buried at depths of up to 0.8 m.
Note 4: It is assumed that the soil properties are uniform. No allowance had been made for the possibility of moisture migration which can lead to a region of high thermal resistivity around the cable. If partial drying out of the soil is foreseen, the permissible current rating should be derived by the methods specified in the IEC 60287 series.

Fig. G14 – Correction factors for cables in buried ducts for soil thermal resistivities other than 2.5 K.m/W to be applied to the current-carrying capacities for reference method D (table B.52.16 of IEC 60364-5-52)

Based on experience, a relationship exist between the soil nature and resistivity. Then, empiric values of correction factors k3 are proposed in Figure G15, depending on the nature of soil.

Nature of soil k3
Very wet soil (saturated) 1.21
Wet soil 1.13
Damp soil 1.05
Dry soil 1.00
Very dry soil (sunbaked) 0.86
Fig. G15 – Correction factor k3 depending on the nature of soil
  • Grouping of conductors or cables

The current-carrying capacities given in the subsequent tables relate to single circuits consisting of the following numbers of loaded conductors:
  -  Two insulated conductors or two single-core cables, or one twin-core cable (applicable to single-phase circuits);
  -  Three insulated conductors or three single-core cables, or one three-core cable (applicable to three-phase circuits).
Where more insulated conductors or cables are installed in the same group, a group reduction factor (here noted k4) shall be applied.
Examples are given in Figures G16 to G18 for different configurations (installation methods, in free air or in the ground).
Figure G16 gives the values of correction factor k4 for different configurations of unburied cables or conductors, grouping of more than one circuit or multi-core cables.

Arrangement (cables touching) Number of circuits or multi-core cables Reference methods
1 2 3 4 5 6 7 8 9 12 16 20
Bunched in air, on a surface, embedded orenclosed 1.00 0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50 0.45 0.41 0.38 Methods A to F
Single layer on wall, floor or unperforated tray 1.00 0.85 0.79 0.75 0.73 0.72 0.72 0.71 0.70 No further reduction factor for more than nine circuits or multi-core cables Method C
Single layer fixed directly
under a wooden ceiling
0.95 0.81 0.72 0.68 0.66 0.64 0.63 0.62 0.61
Single layer on a perforated horizontal or vertical tray 1.00 0.88 0.82 0.77 0.75 0.73 0.73 0.72 0.72 Methods E and F
Single layer on ladder support or cleats etc. 1.00 0.87 0.82 0.80 0.80 0.79 0.79 0.78 0.78
Fig. G16 – Reduction factors for groups of more than one circuit or of more than one multi-core cable (table B.52.17 of IEC 60364-5-52)

Figure G17 gives the values of correction factor k4 for different configurations of unburied cables or conductors, for groups of more than one circuit of single-core cables in free air.

Method of installation Number of tray 
Number of three-phase circuits
Use as a multiplier to
rating for
1 2 3
Perforated trays 31 FigG17a.jpg 1 0.98 0.91 0.87 Three cables in
horizontal formation


2 0.96 0.87 0.81
3 0.95 0.85 0.78
Vertical perforated trays 31 FigG17b.jpg 1 0.96 0.86 Three cables in vertical formation
2 0.95 0.84
Ladder supports, cleats, etc... formation
32 FigG17c.jpg 1 1.00 0.97 0.96 Three cables in
horizontal formation
33 2 0.98 0.93 0.89
34
3 0.97 0.90 0.86
Perforated trays 31


FigG17d.jpg 1 1.00 0.98 0.96 Three cables in trefoil formation
2 0.97 0.93 0.89
3 0.96 0.92 0.86
Vertical perforated trays 31

FigG17e.jpg 1 1.00 0.91 0.89
2 1.00 0.90 0.86
Ladder supports, cleats, etc...



32 FigG17f.jpg 1 1.00 1.00 1.00
33 2 0.97 0.95 0.93
34 3 0.96 0.94 0.90
Fig. G17 – Reduction factors for groups of more than one circuit of single-core cables to be applied to reference rating for one circuit of single-core cables in free air - Method of installation F. (table B.52.21 of IEC 60364-5-52)

Figure G18 gives the values of correction factor k4 for different configurations of cables or conductors laid directly in the ground.

Number of circuits 
 
Cable to cable clearancea
Nil (cables touching) One cable diameter 0.125 m 0.25 m 0.5 m
2 0.75 0.80 0.85 0.90 0.90
3 0.65 0.70 0.75 0.80 0.85
4 0.60 0.60 0.70 0.75 0.80
5 0.55 0.55 0.65 0.70 0.80
6 0.50 0.55 0.60 0.70 0.80
7 0.45 0.51 0.59 0.67 0.76
8 0.43 0.48 0.57 0.65 0.75
9 0.41 0.46 0.55 0.63 0.74
12 0.36 0.42 0.51 0.59 0.71
16 0.32 0.38 0.47 0.56 0.38
20 0.29 0.35 0.44 0.53 0.66
Fig. G18 – Reduction factors for more than one circuit, single-core or multi-core cables laid directly in the ground. Installation method D. (table B.52.18 of IEC 60364-5-52)
  • Harmonic current

The current-carrying capacity of three-phase, 4-core or 5-core cables is based on the assumption that only 3 conductors are fully loaded.
However, when harmonic currents are circulating, the neutral current can be significant, and even higher than the phase currents. This is due to the fact that the 3rd harmonic currents of the three phases do not cancel each other, and sum up in the neutral conductor.
This of course affects the current-carrying capacity of the cable, and a correction factor noted here k5 shall be applied.
In addition, if the 3rd harmonic percentage h3 is greater than 33%, the neutral current is greater than the phase current and the cable size selection is based on the neutral current. The heating effect of harmonic currents in the phase conductors has also to be taken into account.
The values of k5 depending on the 3rd harmonic content are given in Figure G19.


Third harmonic content of phase current % Correction factor
Size selection is based
on phase current
Size selection is based on neutral current
0 ­­­­­­­- 15 1.0   
15 - 33 0.86 
  
33 - 45 0.86
> 45  1.0 (3)

(3) If the neutral current is more than 135 % of the phase current and the cable size is selected on the basis of the neutral current then the three phase conductors will not be fully loaded. The reduction in heat generated by the phase conductors offsets the heat generated by the neutral conductor to the extent that it is not necessary to apply any reduction factor to the current carrying capacity for three loaded conductors.

 Fig. G19: Correction factors for harmonic currents in four-core and five-core cables (table E.52.1 of IEC 60364-5-52)


Admissible current as a function of nominal cross-sectional area of conductors

IEC standard 60364-5-52 proposes extensive information in the form of tables giving the admissible currents as a function of cross-sectional area of cables. Many parameters are taken into account, such as the method of installation, type of insulation material, type of conductor material, number of loaded conductors.

As an example, Figure G20 gives the current-carrying capacities for different methods of installation of PVC insulation, three loaded copper or almunium conductors, free air or in ground.


Nominal cross-sectional area of conductors
(mm2)
Installation methods of Table B.52.1
A1 A2 B1 B2 C D1 D2
FigG20a.jpg FigG20b.jpg FigG20c.jpg FigG20d.jpg FigG20e.jpg FigG20f.jpg FigG20g.jpg
1 2 3 4 5 6 7 8
Copper
1.5 13.5 13 15.5 15 17.5 18 19
2.5 18 17.5 21 20 24 24 24
4 24 23 28 27 32 30 33
6 31 29 36 34 41 38 41
10 42 39 50 46 57 50 54
16 56 52 68 62 76 64 70
25 73 68 89 80 96 82 92
35 89 83 110 99 119 98 110
50 108 99 134 118 144 116 130
70 136 125 171 149 184 143 162
95 164 150 207 179 223 169 193
120 188 172 239 206 259 192 220
150 216 196 262 225 299 217 246
185 245 223 296 255 341 243 278
240 286 261 346 297 403 280 320
300 328 298 394 339 464 316 359
Aluminium
2.5 14 13.5 16.5 15.5 18.5 18.5
4 18.5 17.5 22 21 25 24
6 24 23 28 27 32 30
10 32 31 39 36 44 39
16 43 41 53 48 59 50 53
25 57 53 70 62 73 64 69
35 70 65 86 77 90 77 83
50 84 78 104 92 110 91 99
70 107 98 133 116 140 112 122
95 129 118 161 139 170 132 148
120 149 135 186 160 197 150 169
150 170 155 204 176 227 169 189
185 194 176 230 199 259 190 214
240 227 207 269 232 305 218 250
300 261 237 306 265 351 247 282

Note: In columns 3, 5, 6, 7 and 8, circular conductors are assumed for sizes up to and including 16 mm2. Values for larger sizes relate to shaped conductors and may safely be applied to circular conductors.

Fig. G20: Current-carrying capacities in amperes for different methods of installation, PVC insulation, three loaded conductors, copper or aluminium, conductor temperature: 70 °C, ambient temperature: 30 °C in air, 20 °C in ground (table B.52.4 of IEC 60364-5-52)


ru:Общие принципы определения сечения кабелей zh:通用线缆大小分类方法

Share