Breaking of the neutral conductor: Difference between revisions
(update_2018) |
(update_2018) |
||
Line 3: | Line 3: | ||
[[File:DB422335.png]] | [[File:DB422335.png]] | ||
(see {{FigRef| | (see {{FigRef|G67}}) | ||
The need to break or not the neutral conductor is related to the protection against indirect contact (fault protection). | The need to break or not the neutral conductor is related to the protection against indirect contact (fault protection). |
Revision as of 02:50, 14 May 2018
(see Fig. G67)
The need to break or not the neutral conductor is related to the protection against indirect contact (fault protection).
In TN-C scheme
The neutral conductor must not be open-circuited under any circumstances since it constitutes a PE as well as a neutral conductor.
In TT, TN-S and IT schemes[1]
In the event of a fault, the circuit-breaker will open all poles, including the neutral pole, i.e. the circuit-breaker is omnipolar.
The action can only be achieved with fuses in an indirect way, in which the operation of one or more fuses triggers a mechanical trip-out of all poles of an associated series-connected load-break switch.
Notes
- ^ In some coutries the rules applied for TN-S are the same than the rules for TN-C