Possible solutions for power-system harmonics: Difference between revisions

From Electrical Installation Guide
Home > Power Factor Correction > The effects of harmonics > Possible solutions for power-system harmonics
m (1 revision imported: Migrated pages - Tables)
(removed empty lines at the beginning of wiki pages)
Line 1: Line 1:
{{Menu_Power_Factor_Correction}}  
{{Menu_Power_Factor_Correction}}__TOC__
 
__TOC__  
 
== Standard capacitors  ==
== Standard capacitors  ==



Revision as of 17:35, 20 December 2019

Standard capacitors

The presence of harmonics in the supply voltage results in abnormally high current levels through the capacitors. An allowance is made for this by designing capacitors for an r.m.s. value of current equal to 1.3 times the nominal rated current. All series elements, such as connections, fuses, switches, etc., associated with the capacitors are similarly oversized, between 1.3 to 1.5 times the nominal ratings.

Standard capacitors can be used if the percentage of non-linear loads is lower than 10% (NLL ≤ 10%).

Capacitors with increased current rating

Capacitors with improved current capability ("heavy duty") can be used in order to increase the safety margin. The technology of these capacitors allows a higher overcurrent compared to what is strictly requested by the standards.

Another possibility is to use capacitors with increased rated current and voltage.

As the same reactive power must be generated, the capacitors must have the same capacitance.

With a rated voltage UN (higher than the system voltage U), the rated current IN and the rated power

QN will be given by the formulas:

[math]\displaystyle{ \frac{I_N}{I}=\frac{U_N}{U} }[/math] and [math]\displaystyle{ \frac{Q_N}{Q}= \left ( \frac{U_N}{U} \right )^2 }[/math]

Capacitors with improved current rating can be used if the percentage of non-linear loads is lower than 20% (NLL ≤ 20%).

Connection of Power Factor Correction capacitors with detuned reactors

In order to attenuate the effects of harmonics (significant increase of capacitor current as well as high current and voltage distortion ), reactors should be associated to capacitors. Reactors and capacitors are configured in a series resonant circuit, tuned so that the series resonant frequency is below the lowest harmonic frequency present in the system (See Figure L31).

The use of detuned reactors thus prevents harmonic resonance problems, avoids the risk of overloading the capacitors and helps reduce voltage harmonic distortion in the network.

Fig. L31 – Simplified circuit diagram

The tuning frequency can be expressed by the relative impedance of the reactor (in %, relative to the capacitor impedance), or by the tuning order, or directly in Hz.

The most common values of relative impedance are 5.7, 7 and 14 (14% is used with high level of 3rd harmonic voltages).

Fig. L32 – Correspondance between relative impedance, tuning order and tuning frequency
Relative impedance(%) Tuning order Tuning frequency @50Hz (Hz) Tuning frequency @60Hz (Hz)
5.7 4.2 210 250
7 3.8 190 230
14 2.7 135 160

In this arrangement, the presence of the reactor increases the fundamental frequency voltage (50 or 60Hz) across the capacitor.

This feature is taken into account by using capacitors which are designed with a rated voltage UN higher than the network service voltage US, as shown on the following table.

Fig. L33 – Typical values of capacitor rated voltage
Capacitor Rated Voltage UN (V) Network Service Voltage US (V)
50 Hz 60 Hz
400 690 400 480 600
Relative Impedance (%) 5.7 480 830 480 575 690
7 480 830 480 575 690
14 480 480

Summary

Practical rules are suggested in Fig. L34, for selection of the suitable configuration, depending on the system parameters:

  • SSC = 3-phase short-circuit power in kVA at the busbar level
  • Sn = sum of the kVA ratings of all transformers supplying (i.e. directly connected to)the busbar
  • Gh = sum of the kVA ratings of all harmonic-generating devices (static converters,inverters, variable speed drives, etc.) connected to the busbar.
If the ratings of some of these devices are quoted in kW only, assume an average power factor of 0.7 to obtain the kVA ratings
Fig. L34 – Simplified rules
General rule (for any size of transformer):
[math]\displaystyle{ G_h\le \frac{S_{sc} }{120} }[/math] [math]\displaystyle{ \frac{S_{sc} }{120} \lt G_h\le \frac{S_{sc} }{70} }[/math] [math]\displaystyle{ \frac{S_{sc} }{70} \lt G_h\le \frac{S_{sc} }{30} }[/math] [math]\displaystyle{ G_h \gt \frac{S_{sc} }{30} }[/math]
Standard capacitors Heavy Duty capacitors or capacitors with voltage rating increased by 10% Heavy Duty capacitors or capacitors with voltage rating increased by 20% + detuned reactor Harmonic filtering necessary See chapter Power harmonics management
Simplified rule (if transformer rating ≤ 2MVA):
[math]\displaystyle{ G_h \le 0.1 \times S_n }[/math] [math]\displaystyle{ 0.1 \times S_n \lt G_h \le 0.2 \times S_n }[/math] [math]\displaystyle{ 0.2 \times S_n \lt G_h \le 0.5 \times S_n }[/math] [math]\displaystyle{ G_h \gt 0.5 \times S_n }[/math]
Standard capacitors Heavy Duty capacitors or capacitors with voltage rating increased by 10% Heavy Duty capacitors or capacitors with voltage rating increased by 20% + detuned reactor Harmonic filtering necessary
See chapter Power harmonics management

Zh:电力系统谐波可能的解决方案

ru:Возможные решения, связанные с гармоническими составляющими напряжения

Share