The SPD chiefly consists of (see Fig. J45):
1)  one or more nonlinear components: the live part (varistor, gas discharge tube, etc.);
2)  a thermal protective device (internal disconnector) which protects it from thermal runaway at end of life (SPD with varistor);
3)  an indicator which indicates end of life of the SPD;
Some SPDs allow remote reporting of this indication;
4)  an external SCPD which provides protection against short circuits (this device can be integrated into the SPD).



Fig J45.jpg



















Fig. J45: Diagram of a SPD


Technology of the live part

Several technologies are available to implement the live part. They each have advantages and disadvantages:

  • Zener diodes;
  • The gas discharge tube (controlled or not controlled);
  • The varistor (zinc oxide varistor).

The table below shows the characteristics and the arrangements of 3 commonly used technologies.



Component Gas Discharge Tube (GDT) Encapsulated spark gap Zinc oxide varistor 
                                       
GDT and varistor in series               Encapsulated spark gap and varistor in paralle
Characteristics          
 
Fig J46a.jpg
 
Fig J46b.jpg
 
Fig J46c.jpg
Fig J46d.jpg
Fig J46e.jpg
Operating mode Voltage switching Voltage switching Voltage limiting Voltage-switching and -limiting in series Voltage-switching and -limiting in parallel
Operating curves
Fig J46f.jpg
Fig J46g.jpg
   
Application
  • Telecom network
  • LV network

(associated with varistor)

LV network LV network LV network LV network
SPD Type Type 2 Type 1 Type 1 ou Type 2 Type 1+ Type 2 Type 1+ Type 2

Fig. J46: Summary performance table


Note: Two technologies can be installed in the same SPD (see Fig. J47



Fig J47.jpg












Fig. J47: The Schneider Electric brand PRD SPD incorporates a gas discharge tube between neutral and earth and varistors between phase and neutral


Share