===== Definition  =====
== Definition  ==


The disturber and the victim are coupled by a magnetic field. The level of disturbance depends on the current variations (di/dt) and the mutual coupling inductance.<br>Inductive coupling increases with:  
The disturber and the victim are coupled by a magnetic field. The level of disturbance depends on the current variations (di/dt) and the mutual coupling inductance.<br>Inductive coupling increases with:  
Line 10: Line 10:
*The load impedance of the disturbing circuit.
*The load impedance of the disturbing circuit.


===== Examples  =====
== Examples  ==


(see '''Fig. R28''')  
(see '''Fig. R28''')  
Line 28: Line 28:
----
----


===== Counter-measures =====
== Counter-measures ==


*Limit the length of parallel runs of disturbers and victims to the strict minimum
*Limit the length of parallel runs of disturbers and victims to the strict minimum

Revision as of 08:48, 17 June 2011

Definition

The disturber and the victim are coupled by a magnetic field. The level of disturbance depends on the current variations (di/dt) and the mutual coupling inductance.
Inductive coupling increases with:

  • The frequency
  • The proximity of the disturber to the victim and the length of the parallel cables,
  • The height of the cables with respect to a ground referencing plane,
  • The load impedance of the disturbing circuit.

Examples

(see Fig. R28)

  • Nearby cables subjected to rapid current variations (di/dt)
  • Short-circuits
  • Fault currents
  • Lightning strikes
  • Stator control systems
  • Welding machines
  • Inductors


Fig R28.jpg
















Fig. R28: Example of inductive coupling


Counter-measures

  • Limit the length of parallel runs of disturbers and victims to the strict minimum
  • Increase the distance between the disturber and the victim
  • For two-wire connections, run the two wires as close together as possible
  • Use multi-core or touching single-core cables, preferably in a triangular layout
  • Position a PEC bonded at both ends and between the disturber and the victim
  • Use symmetrical transmission systems on correctly implemented, symmetrical wiring systems
  • Shield the disturbing cables, the victim cables or both (the shielding must be bonded)
  • Reduce the dv/dt of the disturber by increasing the signal rise time where possible (series-connected resistors or PTC resistors on the disturbing cable, ferrite rings on the disturbing and/or victim cable)

 