Different kinds of motor control solution are compared in the following tables.
Is / In | Ts / Tn | Speed control | Torque control | |
Direct on line | 5-10 | 5-10 | No | No |
Star – Delta | 2-3 | 1-2 | No | No |
Auto-transformer | 2-3 | 1-2 | No | No |
Soft starter | 3-5 | 1.5-2.5 | No | Yes |
Variable speed drive | 1.5 | 1.5-2 | Yes | Yes |
pros | cons | |
Direct on line |
Reduced cost High starting torque when necessary |
High in-rush current High torque so high constraints on motor, mechanics, ... not necessarily needed for the application starting |
Star – Delta | Reduced in-rush current | Reduced starting torque, switching voltage & currents |
Auto-transformer | Reduced in-rush current | Weight |
Soft starter |
Reduced in-rush current controlled start and stop Interesting solution in medium voltage as good value for money |
Reduced starting torque |
Variable speed drive |
Controlled speed Energy saving at reduced speed Sometimes the main "modern" solution according to the driven process characteristics |
Higher cost |
Fig. N63a: Comparison of different motor control solution