Form factors of RCDs: Difference between revisions

From Electrical Installation Guide
(Updated format of image integration + new image names (book 2013))
(updated new imges sizes FigF64 (guide 2013))
Line 22: Line 22:
|}
|}


<br>[[Image:FigF64a_2013.jpg]][[Image:FigF64b_2013.jpg]][[Image:FigF64c_2013.jpg|162x183px]]
<br>[[Image:FigF64a_2013.jpg]][[Image:FigF64b_2013.jpg|x183px]][[Image:FigF64c_2013.jpg|x200px]]


Industrial type circuit-&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;Acti 9 DIN-rail industrial <br>breaker Vigi Compact&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;Circuit-breaker with adaptable Vigi RCD module <br><br>'''''Fig. F64:''' Industrial-type CB with RCD module''  
Industrial type circuit-&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;Acti 9 DIN-rail industrial <br>breaker Vigi Compact&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;&nbsp;Circuit-breaker with adaptable Vigi RCD module <br><br>'''''Fig. F64:''' Industrial-type CB with RCD module''  
Line 28: Line 28:


Adaptable residual current circuit-breakers, including DIN-rail mounted units (e.g. Compact or Acti 9), are available, to which may be associated an auxiliary RCD module (e.g. Vigi). <br>The ensemble provides a comprehensive range of protective functions (isolation, protection against short-circuit, overload, and earth-fault.
Adaptable residual current circuit-breakers, including DIN-rail mounted units (e.g. Compact or Acti 9), are available, to which may be associated an auxiliary RCD module (e.g. Vigi). <br>The ensemble provides a comprehensive range of protective functions (isolation, protection against short-circuit, overload, and earth-fault.


== Household and similar miniature circuit-breakers with RCD  ==
== Household and similar miniature circuit-breakers with RCD  ==

Revision as of 12:03, 13 August 2013

Residual current devices (RCD) are commonly incorporated in or associated with the following components:

  • Industrial-type moulded-case circuit-breakers (MCCB) and air circuit-breakers (ACB) conforming to IEC 60947-2 and its appendix B and M
  • Industrial type miniature circuit-breakers (MCB) conforming to IEC 60947-2 and its appendix B and M
  • Household and similar miniature circuit-breakers (MCB) complying with IEC 60898, IEC 61008, IEC 61009
  • Residual load switch conforming to particular national standards
  • Relays with separate toroidal (ring-type) current transformers, conforming to IEC 60947-2 Appendix M

RCDs are mandatorily used at the origin of TT-earthed installations, where their ability to discriminate with other RCDs allows selective tripping, thereby ensuring the level of service continuity required.


Industrial type circuit-breakers with integrated or adaptable RCD module

(see Fig. F64)

Industrial circuit-breakers with an integrated RCD are covered in IEC 60947-2 and its appendix B


FigF64a 2013.jpgFigF64b 2013.jpgFigF64c 2013.jpg

Industrial type circuit-      Acti 9 DIN-rail industrial
breaker Vigi Compact      Circuit-breaker with adaptable Vigi RCD module

Fig. F64: Industrial-type CB with RCD module


Adaptable residual current circuit-breakers, including DIN-rail mounted units (e.g. Compact or Acti 9), are available, to which may be associated an auxiliary RCD module (e.g. Vigi).
The ensemble provides a comprehensive range of protective functions (isolation, protection against short-circuit, overload, and earth-fault.

Household and similar miniature circuit-breakers with RCD

(see Fig. F65

Household or domestic circuit-breakers with an integrated RCD are covered in IEC 60898, IEC 61008 and IEC 61009

FigF65a 2013.jpg FigF65b 2013.jpg

The incoming-supply        “Monobloc” Déclic Vigi residual
circuit-breaker can           current circuit-breakers intended
also have time-delayed     for protection of terminal socket-outlet
characteristics and          circuits in domestic and tertiary
integrate a RCD              sector applications.
(type S).

Fig. F65: Domestic residual current circuit-breakers (RCCBs) for earth leakage protection


Residual current circuit-breakers and RCDs with separate toroidal current transformer

(see Fig. F66)

Residual current load break switches are covered by particular national standards.RCDs with separate toroidal current transformers are standardized in IEC 60947-2 appendix M

RCDs with separate toroidal CTs can be used in association with circuit-breakers or contactors.


FigF66a 2013.jpgFigF66b 2013.jpg

Fig. F66: RCDs with separate toroidal current transformers (Vigirex)


ru:Типы УЗО zh:RCDs简述

Share