Harmonic measurement in electrical networks: Difference between revisions

From Electrical Installation Guide
Home > Power harmonics management > Harmonic measurement in electrical networks
(updated according to guide 2013)
Line 1: Line 1:
{{Menu_Harmonic_management}}
{{Menu_Harmonic_management}}


== <br>Devices used to measure the indicators  ==
== Procedures for harmonic measurement==
=== Device selection  ===


The traditional observation and measurement methods include:
'''Harmonic measurements are carried out on industrial or commercial sites:'''
* Preventively, to obtain an overall idea on distribution-network status (network mapping),
* In view of corrective action, to determine the origin of a disturbance and determine the solutions required to eliminate it,
* To check the validity of a solution (followed by modifications in the distribution network to check the reduction of harmonic disturbances)


*Observations using an oscilloscope
'''The harmonic indicators can be measured:'''
* By an expert present on the site for a limited period of time (one day), giving precise, but limited perception,
* By instrumentation devices installed and operating for a significant period of time (at least one week) giving a reliable overview of the situation,
* Or by devices permanently installed in the distribution network, allowing a follow-up of Power Quality.


An initial indication on the distortion affecting a signal can be obtained by viewing the current or the voltage on an oscilloscope.<br>The waveform, when it diverges from a sinusoidal, clearly indicates the presence of harmonics. Current and voltage peaks can be viewed.<br>Note, however, that this method does not offer precise quantification of the harmonic components
=== One-shot or corrective actions ===


*Analogue spectral analysers
This kind of action is carried-out in case of observed disturbances, for which harmonics are suspected. In order to determine the origin of the disturbances, measurements of current and voltage are performed:
* At the supply source level,
* On the busbars of the main distribution switchboard (or on the MV busbars),
* On each outgoing circuit in the main distribution switchboard (or on the MV busbars).


They are made up of passband filters coupled with an rms voltmeter. They offer mediocre performance and do not provide information on phase displacement.<br>'''Only the recent digital analysers can determine sufficiently precisely the values of all the mentioned indicators.'''
For accurate results, it is necessary to know the precise operating conditions of the installation and particularly the status of the capacitor banks (operating or not, number of connected steps).


=== Functions of digital analysers  ===
The results of measurement will help the analysis in order to:
* Determine any necessary derating of equipment in the installation, or
* Quantify any necessary harmonic protection and filtering systems to be installed in the distribution network, or
* Check the compliance of the electrical installation with the applicable standards or Utility regulations (maximum permissible harmonic emission).


The microprocessors in digital analysers:
=== Long-term or preventive actions ===


*Calculate the values of the harmonic indicators (power factor, crest factor, distortion power, THD)
For a number of reasons, the installation of permanent measurement devices in the distribution network is very valuable.
*Carry out various complementary functions (corrections, statistical detection, measurement management, display, communication, etc.)  
* The presence of an expert on site is limited in time and it is not always possible to observe all the possible situations. Only a number of measurements at different points in the installation and over a sufficiently long period (one week to a month) provide an overall view of operation and take into account all the situations that can occur following:
*In multi-channel analysers, supply virtually in real time the simultaneous spectral decomposition of the currents and voltages<br>
** Fluctuations in the supply source,
** Variations in the operation of the installation,
** The addition of new equipment in the installation.
* Measurement devices installed in the distribution network prepare and facilitate the diagnosis of the experts, thus reducing the number and duration of their visits.
* Permanent measurement devices detect any new disturbances arising following the installation of new equipment, the implementation of new operating modes or fluctuations in the supply network.
* For an overall evaluation of network status (preventive analysis), this avoids:
**Renting of measurement equipment,
**Calling in experts,
**Having to connect and disconnect the measurement equipment. For the overall evaluation of network status, the analysis on the main low-voltage distribution switchboards (MLVS) can often be carried out by the incoming device and/or the measurement devices equipping each outgoing circuit,
* For corrective actions, it is possible to:
**Determine the operating conditions at the time of the incident,
**Draw-up a map of the distribution network and evaluate the implemented solution.


=== Analyser operation and data processing  ===
The diagnosis may be improved by the use of additional dedicated equipment in case of specific problem.


The analogue signals are converted into a series of numerical values.<br>Using this data, an algorithm implementing the Fast Fourier Transform (FFT) calculates the amplitudes and the phases of the harmonics over a large number of time windows.<br>Most digital analysers measure harmonics up to order 20 or 25 when calculating the THD.<br>Processing of the successive values calculated using the FFT (smoothing, classification, statistics) can be carried out by the measurement device or by external software.
== Harmonic measurement devices ==


== <br>Procedures for harmonic analysis of distribution networks  ==
Measurement devices provide instantaneous and average information concerning harmonics. Instantaneous values are used for analysis of disturbances linked to harmonics. Average values are used for Power Quality assessment.


Measurements are carried out on industrial or commercial site:
The most recent measurement devices are designed referring to IEC standard 61000-4-7: "Electromagnetic compatibility (EMC) – Part 4-7: Testing and measurement techniques – General guide on harmonics and interharmonics measurements and instrumentation, for power supply systems and equipment connected thereto".


*Preventively, to obtain an overall idea on distribution-network status (network map)  
The supplied values include:
*In view of corrective action:
* The harmonic spectrum of currents and voltages (amplitudes and percentage of the fundamental),
* The THD for current and voltage,
* For specific analysis: the phase angle between harmonic voltage and current of the same order and the phase of the harmonics with respect to a common reference (e.g. the fundamental voltage).


&nbsp; - To determine the origin of a disturbance and determine the solutions required to eliminate it<br>&nbsp; - To check the validity of a solution (followed by modifications in the distribution network to check the reduction in harmonics)
Average values are indicators of the long-term Power Quality. Typical and relevant statistical data are for example measures averaged by periods of 10 minutes, during observation periods of 1 week.


=== Operating mode  ===
In order to meet the Power Quality objectives, 95% of the measured values should be less than specified values.


The current and voltage are studied:  
'''Fig. M10''' gives the maximum harmonic voltage in order to meet the requirements of standard EN50160: "Voltage characteristics of electricity supplied by public distribution networks", for Low and Medium Voltage.


*At the supply source
{| style="width: 789px; height: 194px" cellspacing="1" cellpadding="1" width="789" border="1"
*On the busbars of the main distribution switchboard (or on the MV busbars)
|-
*On each outgoing circuit in the main distribution switchboard (or on the&nbsp;MV busbars)
| valign="top" bgcolor="#0099cc" colspan="2" | '''Odd harmonic <br>non-multiples of 3'''
| valign="top" bgcolor="#0099cc" colspan="2" | '''Odd harmonic <br> multiples of 3'''
| valign="top" bgcolor="#0099cc" colspan="2" | '''Even harmonic'''
|-
| '''Order h'''
| '''Relative amplitude <br> U<sub>h</sub>: %'''
| '''Order h'''
| '''Relative amplitude <br> U<sub>h</sub>: %'''
| '''Order h'''
| '''Relative amplitude <br> U<sub>h</sub>: %''' 
|-
| 5
| 6
| 3
| 5
| 2
| 2
|-
| 7
| 5
| 9
| 1.5
| 4
| 1
|-
| 11
| 3.5
| 15
| 0.5
| 6...24
| 0.5
|-
| 13
| 3
| 21
| 0.5
| &nbsp;
| &nbsp;
|-
| 17
| 2
| &nbsp;
| &nbsp;
| &nbsp;
| &nbsp;
|-
| 19
| 1.5
| &nbsp;
| &nbsp;
| &nbsp;
| &nbsp;
|-
| 123
| 1.5
| &nbsp;
| &nbsp;
| &nbsp;
| &nbsp;
|-
| 25
| 1.5
| &nbsp;
| &nbsp;
| &nbsp;
| &nbsp;
|}
'''''Fig. M10 :''''' ''Values of individual harmonic voltages at the supply terminals for orders up to 25 given in percent of the fundamental voltage U<sub>1</sub>''


For the measurements, it is necessary to know the precise operating conditions of the installation and particularly the status of the capacitor banks (operating, not operating, the number of disconnected steps).
=== Portable instruments ===


=== Analysis results  ===
The traditional observation and measurement methods include:


*Determine any necessary derating of equipment in the installation or  
==== Oscilloscope ====
*Quantify any necessary harmonic protection and filtering systems to be installed in the distribution network
An initial indication on the distortion affecting a signal can be obtained by viewing the current or the voltage on an oscilloscope.<br>
*Enable comparison between the measured values and the reference values of the utility (maximum harmonic values, acceptable values, reference values)
The waveform, when it diverges from a sinusoidal, clearly indicates the presence of harmonics. Current and voltage peaks can be observed.<br>
Note, however, that this method does not offer precise quantification of the harmonic components.


=== Use of measurement devices<br> ===
==== Digital analyser ====
Only recent digital analysers can determine the values of all the mentioned indicators with sufficient accuracy. <br>
They are using digital technology, specifically a high performance algorithm called Fast Fourier Transform (FFT). Current or voltage signals are digitized and the algorithm is applied on data relative to time windows of 10 (50Hz systems) or 12
periods (for 60Hz systems) of the power frequency.<br>
The amplitude and phase of harmonics up to the 40th or 50th order are calculated, depending on the class of measurement.


Measurement devices serve to show both the instantaneous and long-term effects of harmonics. Analysis requires values spanning durations ranging from a few seconds to several minutes over observation periods of a number of days.<br>The required values include:
Processing of the successive values calculated using the FFT (smoothing, classification, statistics) can be carried out by the measurement device or by external software.


*The amplitudes of the harmonic currents and voltages
'''Functions of digital analysers'''
*The individual harmonic content of each harmonic order of the current and voltage
* Calculate the values of the harmonic indicators (power factor, crest factor, individual harmonic amplitude, THD)
*The THD for the current and voltage
* In multi-channel analysers, supply virtually in real time the simultaneous spectral decomposition of the currents and voltages
*Where applicable, the phase displacement between the harmonic voltage and current of the same harmonic order and the phase of the harmonics with respect to a common reference (e.g. the fundamental voltage)
* Carry out various complementary functions (corrections, statistical detection, measurement management, display, communication, etc.)
* Storage of data


== <br>Keeping a close eye on harmonics  ==
[[Image:Fig_M11.jpg|none]]
'''''Fig. M11 :''''' ''Implementation of a digital Power Quality recorder in a cabinet''


The harmonic indicators can be measured:  
=== Fixed instruments ===
Panel instrumentation provides continuous information to the Manager of the electrical installation. Data can be accessible through dedicated power monitoring devices or through the digital trip units of circuit breakers.
[[Image:Fig_M12.jpg|none]]
'''''Fig. M12 :''''' ''Example of Power and Energy meter''


*Either by devices permanently installed in the distribution network
== Which harmonic orders must be monitored and mitigated?==
*Or by an expert present at least a half day on the site (limited perception)


=== Permanent devices are preferable  ===
The most significant harmonic orders in three-phase distribution networks are the odd orders (3, 5, 7, 9, 11, 13 ….)


For a number of reasons, the installation of permanent measurement devices in the distribution network is preferable.  
Triplen harmonics (order multiple of 3) are present only in three-phase, four-wire systems, when single phase loads are connected between phase and neutral.


*The presence of an expert is limited in time. Only a number of measurements at different points in the installation and over a sufficiently long period (one week to a month) provide an overall view of operation and take into account all the situations that can occur following:
Utilities are mainly focusing on low harmonic orders (5, 7, 11, and 13).


&nbsp; - Fluctuations in the supply source<br>&nbsp; - Variations in the operation of the installation<br>&nbsp; - The addition of new equipment in the installation
Generally speaking, harmonic conditioning of the lowest orders (up to 13) is sufficient. More comprehensive conditioning takes into account harmonic orders up to 25.


*Measurement devices installed in the distribution network prepare and facilitate the diagnosis of the experts, thus reducing the number and duration of their visits
Harmonic amplitudes normally decrease as the frequency increases. Sufficiently accurate measurements are obtained by measuring harmonics up to order 30.
*Permanent measurement devices detect any new disturbances arising following the installation of new equipment, the implementation of new operating modes or fluctuations in the supply network


=== Take advantage of built-in measurement and detection devices  ===
[[Image:Fig_M13.jpg|none|250px]]
'''''Fig. M13 :''''' ''Example of electronic trip units of circuit-breakers providing harmonic related information''


Measurement and detection devices built into the electrical distribution equipment:
*For an overall evaluation of network status (preventive analysis), avoid:
&nbsp; - Renting measurement equipment<br>&nbsp; - Calling in experts<br>&nbsp; - Having to connect and disconnect the measurement equipment.<br>For the overall evaluation of network status, the analysis on the main low-voltage distribution switchboards (MLVS) can often be carried out by the incoming device and/or the measurement devices equipping each outgoing circuit
*For corrective action, are the means to:
&nbsp; - Determine the operating conditions at the time of the incident<br>&nbsp; - Draw up a map of the distribution network and evaluate the implemented solution<br>The diagnosis is improved by the use of equipment intended for the studied problem.


[[ru:Измерение показателей гармоник]]
[[ru:Измерение показателей гармоник]]
[[zh:谐波指标的测量]]
[[zh:谐波指标的测量]]

Revision as of 16:26, 18 October 2013


Procedures for harmonic measurement

Harmonic measurements are carried out on industrial or commercial sites:

  • Preventively, to obtain an overall idea on distribution-network status (network mapping),
  • In view of corrective action, to determine the origin of a disturbance and determine the solutions required to eliminate it,
  • To check the validity of a solution (followed by modifications in the distribution network to check the reduction of harmonic disturbances)

The harmonic indicators can be measured:

  • By an expert present on the site for a limited period of time (one day), giving precise, but limited perception,
  • By instrumentation devices installed and operating for a significant period of time (at least one week) giving a reliable overview of the situation,
  • Or by devices permanently installed in the distribution network, allowing a follow-up of Power Quality.

One-shot or corrective actions

This kind of action is carried-out in case of observed disturbances, for which harmonics are suspected. In order to determine the origin of the disturbances, measurements of current and voltage are performed:

  • At the supply source level,
  • On the busbars of the main distribution switchboard (or on the MV busbars),
  • On each outgoing circuit in the main distribution switchboard (or on the MV busbars).

For accurate results, it is necessary to know the precise operating conditions of the installation and particularly the status of the capacitor banks (operating or not, number of connected steps).

The results of measurement will help the analysis in order to:

  • Determine any necessary derating of equipment in the installation, or
  • Quantify any necessary harmonic protection and filtering systems to be installed in the distribution network, or
  • Check the compliance of the electrical installation with the applicable standards or Utility regulations (maximum permissible harmonic emission).

Long-term or preventive actions

For a number of reasons, the installation of permanent measurement devices in the distribution network is very valuable.

  • The presence of an expert on site is limited in time and it is not always possible to observe all the possible situations. Only a number of measurements at different points in the installation and over a sufficiently long period (one week to a month) provide an overall view of operation and take into account all the situations that can occur following:
    • Fluctuations in the supply source,
    • Variations in the operation of the installation,
    • The addition of new equipment in the installation.
  • Measurement devices installed in the distribution network prepare and facilitate the diagnosis of the experts, thus reducing the number and duration of their visits.
  • Permanent measurement devices detect any new disturbances arising following the installation of new equipment, the implementation of new operating modes or fluctuations in the supply network.
  • For an overall evaluation of network status (preventive analysis), this avoids:
    • Renting of measurement equipment,
    • Calling in experts,
    • Having to connect and disconnect the measurement equipment. For the overall evaluation of network status, the analysis on the main low-voltage distribution switchboards (MLVS) can often be carried out by the incoming device and/or the measurement devices equipping each outgoing circuit,
  • For corrective actions, it is possible to:
    • Determine the operating conditions at the time of the incident,
    • Draw-up a map of the distribution network and evaluate the implemented solution.

The diagnosis may be improved by the use of additional dedicated equipment in case of specific problem.

Harmonic measurement devices

Measurement devices provide instantaneous and average information concerning harmonics. Instantaneous values are used for analysis of disturbances linked to harmonics. Average values are used for Power Quality assessment.

The most recent measurement devices are designed referring to IEC standard 61000-4-7: "Electromagnetic compatibility (EMC) – Part 4-7: Testing and measurement techniques – General guide on harmonics and interharmonics measurements and instrumentation, for power supply systems and equipment connected thereto".

The supplied values include:

  • The harmonic spectrum of currents and voltages (amplitudes and percentage of the fundamental),
  • The THD for current and voltage,
  • For specific analysis: the phase angle between harmonic voltage and current of the same order and the phase of the harmonics with respect to a common reference (e.g. the fundamental voltage).

Average values are indicators of the long-term Power Quality. Typical and relevant statistical data are for example measures averaged by periods of 10 minutes, during observation periods of 1 week.

In order to meet the Power Quality objectives, 95% of the measured values should be less than specified values.

Fig. M10 gives the maximum harmonic voltage in order to meet the requirements of standard EN50160: "Voltage characteristics of electricity supplied by public distribution networks", for Low and Medium Voltage.

Odd harmonic
non-multiples of 3
Odd harmonic
multiples of 3
Even harmonic
Order h Relative amplitude
Uh: %
Order h Relative amplitude
Uh: %
Order h Relative amplitude
Uh: %
5 6 3 5 2 2
7 5 9 1.5 4 1
11 3.5 15 0.5 6...24 0.5
13 3 21 0.5    
17 2        
19 1.5        
123 1.5        
25 1.5        

Fig. M10 : Values of individual harmonic voltages at the supply terminals for orders up to 25 given in percent of the fundamental voltage U1

Portable instruments

The traditional observation and measurement methods include:

Oscilloscope

An initial indication on the distortion affecting a signal can be obtained by viewing the current or the voltage on an oscilloscope.
The waveform, when it diverges from a sinusoidal, clearly indicates the presence of harmonics. Current and voltage peaks can be observed.
Note, however, that this method does not offer precise quantification of the harmonic components.

Digital analyser

Only recent digital analysers can determine the values of all the mentioned indicators with sufficient accuracy.
They are using digital technology, specifically a high performance algorithm called Fast Fourier Transform (FFT). Current or voltage signals are digitized and the algorithm is applied on data relative to time windows of 10 (50Hz systems) or 12 periods (for 60Hz systems) of the power frequency.
The amplitude and phase of harmonics up to the 40th or 50th order are calculated, depending on the class of measurement.

Processing of the successive values calculated using the FFT (smoothing, classification, statistics) can be carried out by the measurement device or by external software.

Functions of digital analysers

  • Calculate the values of the harmonic indicators (power factor, crest factor, individual harmonic amplitude, THD)
  • In multi-channel analysers, supply virtually in real time the simultaneous spectral decomposition of the currents and voltages
  • Carry out various complementary functions (corrections, statistical detection, measurement management, display, communication, etc.)
  • Storage of data
Fig M11.jpg

Fig. M11 : Implementation of a digital Power Quality recorder in a cabinet

Fixed instruments

Panel instrumentation provides continuous information to the Manager of the electrical installation. Data can be accessible through dedicated power monitoring devices or through the digital trip units of circuit breakers.

Fig M12.jpg

Fig. M12 : Example of Power and Energy meter

Which harmonic orders must be monitored and mitigated?

The most significant harmonic orders in three-phase distribution networks are the odd orders (3, 5, 7, 9, 11, 13 ….)

Triplen harmonics (order multiple of 3) are present only in three-phase, four-wire systems, when single phase loads are connected between phase and neutral.

Utilities are mainly focusing on low harmonic orders (5, 7, 11, and 13).

Generally speaking, harmonic conditioning of the lowest orders (up to 13) is sufficient. More comprehensive conditioning takes into account harmonic orders up to 25.

Harmonic amplitudes normally decrease as the frequency increases. Sufficiently accurate measurements are obtained by measuring harmonics up to order 30.

Fig M13.jpg

Fig. M13 : Example of electronic trip units of circuit-breakers providing harmonic related information


ru:Измерение показателей гармоник zh:谐波指标的测量

Share