Chapter G

Sizing and protection of conductors


Breaking of the neutral conductor: Difference between revisions

From Electrical Installation Guide
Home > Sizing and protection of conductors > The neutral conductor > Breaking of the neutral conductor
m (r2.7.2) (robot Adding: zh:中性线的分断)
m (cleaned up source: table format, etc ...)
Line 2: Line 2:
<br>
<br>


<br>[[Image:PictoChap7c.jpg|left]]<br><br>(see '''Fig. G64''')<br>The need to break or not the neutral conductor is related to the protection against indirect contact.<br>'''In TN-C scheme'''<br>The neutral conductor must not be open-circuited under any circumstances since it constitutes a PE as well as a neutral conductor.<br>'''In TT, TN-S and IT schemes'''<br>In the event of a fault, the circuit-breaker will open all poles, including the neutral pole, i.e. the circuit-breaker is omnipolar.<br>The action can only be achieved with fuses in an indirect way, in which the operation of one or more fuses triggers a mechanical trip-out of all poles of an associated series-connected load-break switch.
[[File:PictoChap7c.jpg|none]]
(see '''Fig. G64''')<br>The need to break or not the neutral conductor is related to the protection against indirect contact.<br>'''In TN-C scheme'''<br>The neutral conductor must not be open-circuited under any circumstances since it constitutes a PE as well as a neutral conductor.<br>'''In TT, TN-S and IT schemes'''<br>In the event of a fault, the circuit-breaker will open all poles, including the neutral pole, i.e. the circuit-breaker is omnipolar.<br>The action can only be achieved with fuses in an indirect way, in which the operation of one or more fuses triggers a mechanical trip-out of all poles of an associated series-connected load-break switch.


[[ru:Отключение нейтрального провода]]
[[ru:Отключение нейтрального провода]]
[[zh:中性线的分断]]
[[zh:中性线的分断]]

Revision as of 13:10, 15 November 2013


PictoChap7c.jpg

(see Fig. G64)
The need to break or not the neutral conductor is related to the protection against indirect contact.
In TN-C scheme
The neutral conductor must not be open-circuited under any circumstances since it constitutes a PE as well as a neutral conductor.
In TT, TN-S and IT schemes
In the event of a fault, the circuit-breaker will open all poles, including the neutral pole, i.e. the circuit-breaker is omnipolar.
The action can only be achieved with fuses in an indirect way, in which the operation of one or more fuses triggers a mechanical trip-out of all poles of an associated series-connected load-break switch.