Fundamental characteristics of a circuit-breaker: Difference between revisions
(format improved) |
(cleaned up source: table format, etc ...) |
||
Line 56: | Line 56: | ||
[[ | [[File:FigH30.jpg|none]] | ||
'''''Fig. H30:''' Example of a NSX630N circuit-breaker equipped with a Micrologic 6.3E trip unit adjusted to 0.9, to give Ir = 360 A'' | '''''Fig. H30:''' Example of a NSX630N circuit-breaker equipped with a Micrologic 6.3E trip unit adjusted to 0.9, to give Ir = 360 A'' | ||
Line 72: | Line 72: | ||
{| style="width: 801px; height: 215px | {| class="wikitable" style="width: 801px; height: 215px" width="801" | ||
|- | |- | ||
! | |||
! Type of protective relay | |||
! Overload<br>protection | |||
! colspan="3" | Short-circuit protection | |||
|- | |- | ||
| Domestic<br>breakers <br>IEC 60898 | |||
| Thermal- magnetic | |||
| Ir = In | |||
| Low setting <br>type B <br>3 In ≤ Im ≤ 5 In | | Low setting <br>type B <br>3 In ≤ Im ≤ 5 In | ||
| Standard setting <br>type C <br>5 In ≤ Im ≤ 10 In | | Standard setting <br>type C <br>5 In ≤ Im ≤ 10 In | ||
| High setting circuit<br>type D<br>10 In ≤ Im ≤ 20 In<sup>(2)</sup> | | High setting circuit<br>type D<br>10 In ≤ Im ≤ 20 In<sup>(2)</sup> | ||
|- | |- | ||
| Modular <br>industrial<sup>(3)</sup> <br>circuit-breakers | |||
| Thermal- magnetic | |||
| Ir = In <br>fixed | |||
| Low setting<br>type B or Z<br>3.2 In ≤ fixed ≤ 4.8 In | | Low setting<br>type B or Z<br>3.2 In ≤ fixed ≤ 4.8 In | ||
| Standard setting<br>type C<br>7 In ≤ fixed ≤ 10 In | | Standard setting<br>type C<br>7 In ≤ fixed ≤ 10 In | ||
| High setting<br>type D or K<br>10 In ≤ fixed ≤ 14 In | | High setting<br>type D or K<br>10 In ≤ fixed ≤ 14 In | ||
|- | |- | ||
| | | rowspan="5" | Industrial<sup>(3)</sup><br>circuit-breakers<br>IEC 60947-2 | ||
| | | rowspan="3" | Thermal- magnetic | ||
| Ir = In fixed | | Ir = In fixed | ||
| | | colspan="3" rowspan="2" | Fixed: Im = 7 to 10 In | ||
|- | |- | ||
| | | rowspan="2" | Adjustable:<br>0.7 In ≤ Ir ≤ In | ||
|- | |- | ||
| colspan="3" | Adjustable:<br> - Low setting : 2 to 5 In <br> - Standard setting: 5 to 10 In | | colspan="3" | Adjustable:<br> - Low setting : 2 to 5 In <br> - Standard setting: 5 to 10 In | ||
|- | |- | ||
| | | rowspan="2" | Electronic | ||
| | | rowspan="2" | Long delay <br>0.4 In ≤ Ir ≤ In | ||
| colspan="3" rowspan="2" | Short-delay, adjustable 1.5 Ir ≤ Im ≤ 10 Ir<br>Instantaneous (I) fixed I = 12 to 15 In | | colspan="3" rowspan="2" | Short-delay, adjustable 1.5 Ir ≤ Im ≤ 10 Ir<br>Instantaneous (I) fixed I = 12 to 15 In | ||
|} | |} | ||
Line 114: | Line 114: | ||
[[ | [[File:FigH32.jpg|none]] | ||
'''''Fig. H32:''' Performance curve of a circuit-breaker thermal-magnetic protective scheme'' | '''''Fig. H32:''' Performance curve of a circuit-breaker thermal-magnetic protective scheme'' | ||
Line 120: | Line 120: | ||
[[ | [[File:FigH33.jpg|none]] | ||
Ir: Overload (thermal or long-delay) relay trip-current setting<br>Im: Short-circuit (magnetic or short-delay) relay trip-current setting<br>Ii: Short-circuit instantaneous relay trip-current setting.<br>Icu: Breaking capacity | Ir: Overload (thermal or long-delay) relay trip-current setting<br>Im: Short-circuit (magnetic or short-delay) relay trip-current setting<br>Ii: Short-circuit instantaneous relay trip-current setting.<br>Icu: Breaking capacity | ||
Line 131: | Line 131: | ||
A circuit-breaker is suitable for isolating a circuit if it fulfills all the conditions prescribed for a disconnector (at its rated voltage) in the relevant standard. In such a case it is referred to as a circuit-breaker-disconnector and marked on its front face with the symbol | A circuit-breaker is suitable for isolating a circuit if it fulfills all the conditions prescribed for a disconnector (at its rated voltage) in the relevant standard. In such a case it is referred to as a circuit-breaker-disconnector and marked on its front face with the symbol | ||
[[ | [[File:Disjoncteur.jpg|none]] | ||
All Acti 9, Compact NSX and Masterpact LV switchgear of Schneider Electric ranges are in this category. | All Acti 9, Compact NSX and Masterpact LV switchgear of Schneider Electric ranges are in this category. | ||
Line 138: | Line 138: | ||
== Rated short-circuit breaking capacity (Icu or Icn) == | == Rated short-circuit breaking capacity (Icu or Icn) == | ||
{| | {{Highlightbox| | ||
The short-circuit current-breaking performance of a LV circuit-breaker is related (approximately) to the cos φ of the fault-current loop. Standard values for this relationship have been established in some standards | |||
}} | |||
The short-circuit current-breaking rating of a CB is the highest (prospective) value of current that the CB is capable of breaking without being damaged. The value of current quoted in the standards is the rms value of the AC component of the fault current, i.e. the DC transient component (which is always present in the worst possible case of short-circuit) is assumed to be zero for calculating the standardized value. This rated value (Icu) for industrial CBs and (Icn) for domestic-type CBs is normally given in kA rms. | The short-circuit current-breaking rating of a CB is the highest (prospective) value of current that the CB is capable of breaking without being damaged. The value of current quoted in the standards is the rms value of the AC component of the fault current, i.e. the DC transient component (which is always present in the worst possible case of short-circuit) is assumed to be zero for calculating the standardized value. This rated value (Icu) for industrial CBs and (Icn) for domestic-type CBs is normally given in kA rms. | ||
Line 150: | Line 149: | ||
*Operating sequences, comprising a succession of operations, i.e. closing and opening on short-circuit | *Operating sequences, comprising a succession of operations, i.e. closing and opening on short-circuit | ||
*Current and voltage phase displacement. When the current is in phase with the supply voltage ( | *Current and voltage phase displacement. When the current is in phase with the supply voltage (cosφ for the circuit = 1), interruption of the current is easier than that at any other power factor. Breaking a current at low lagging values of cosφ is considerably more difficult to achieve; a zero power-factor circuit being (theoretically) the most onerous case. | ||
In practice, all power-system short-circuit fault currents are (more or less) at lagging power factors, and standards are based on values commonly considered to be representative of the majority of power systems. In general, the greater the level of fault current (at a given voltage), the lower the power factor of the fault-current loop, for example, close to generators or large transformers. | In practice, all power-system short-circuit fault currents are (more or less) at lagging power factors, and standards are based on values commonly considered to be representative of the majority of power systems. In general, the greater the level of fault current (at a given voltage), the lower the power factor of the fault-current loop, for example, close to generators or large transformers. | ||
Line 162: | Line 161: | ||
- The correct operation of the overload protection have not been impaired by the test. | - The correct operation of the overload protection have not been impaired by the test. | ||
{| | {| class="wikitable" width="200" | ||
|- | |- | ||
! Icu | |||
! cosφ | |||
|- | |- | ||
| 6 kA < Icu ≤ 10 kA | | 6 kA < Icu ≤ 10 kA | ||
Line 180: | Line 179: | ||
|} | |} | ||
'''''Fig. H34:''' Icu related to power factor ( | '''''Fig. H34:''' Icu related to power factor (cosφ) of fault-current circuit (IEC 60947-2)'' | ||
Revision as of 13:10, 15 November 2013
The fundamental characteristics of a circuit-breaker are:
- Its rated voltage Ue
- Its rated current In
- Its tripping-current-level adjustment ranges for overload protection (Ir [1] or Irth [1] ) and for short-circuit protection (Im) [1]
- Its short-circuit current breaking rating (Icu for industrial CBs; Icn for domestic-type CBs).
Rated operational voltage (Ue)
This is the voltage at which the circuit-breaker has been designed to operate, in normal (undisturbed) conditions.
Other values of voltage are also assigned to the circuit-breaker, corresponding to disturbed conditions.
Rated current (In)
This is the maximum value of current that a circuit-breaker, fitted with a specified overcurrent tripping relay, can carry indefinitely at an ambient temperature stated by the manufacturer, without exceeding the specified temperature limits of the current carrying parts.
Example
A circuit-breaker rated at In = 125 A for an ambient temperature of 40°C will be equipped with a suitably calibrated overcurrent tripping relay (set at 125 A). The same circuit-breaker can be used at higher values of ambient temperature however, if suitably “derated”. Thus, the circuit-breaker in an ambient temperature of 50°C could carry only 117 A indefinitely, or again, only 109 A at 60°C, while complying with the specified temperature limit.
Derating a circuit-breaker is achieved therefore, by reducing the trip-current setting of its overload relay, and marking the CB accordingly. The use of an electronic-type of tripping unit, designed to withstand high temperatures, allows circuit-breakers (derated as described) to operate at 60°C (or even at 70°C) ambient.
Note: In for circuit-breakers (in IEC 60947-2) is equal to Iu for switchgear generally, Iu being the rated uninterrupted current.
Frame-size rating
A circuit-breaker which can be fitted with overcurrent tripping units of different current level-setting ranges, is assigned a rating which corresponds to the highest current-level-setting tripping unit that can be fitted.
Example
A Compact NSX630N circuit-breaker can be equipped with 11 electronic trip units from 150 A to 630 A. The size of the circuit-breaker is 630A.
Overload relay trip-current setting (Irth or Ir)
Apart from small circuit-breakers which are very easily replaced, industrial circuit-breakers are equipped with removable, i.e. exchangeable, overcurrent-trip relays. Moreover, in order to adapt a circuit-breaker to the requirements of the circuit it controls, and to avoid the need to install over-sized cables, the trip relays are generally adjustable. The trip-current setting Ir or Irth (both designations are in common use) is the current above which the circuit-breaker will trip. It also represents the maximum current that the circuit-breaker can carry without tripping. That value must be greater than the maximum load current IB, but less than the maximum current permitted in the circuit Iz (see chapter G).
The thermal-trip relays are generally adjustable from 0.7 to 1.0 times In, but when electronic devices are used for this duty, the adjustment range is greater; typically 0.4 to 1 times In.
Example (see Fig. H30)
A NSX630N circuit-breaker equipped with a 400 A Micrologic 6.3E overcurrent trip relay, set at 0.9, will have a trip-current setting:
Ir = 400 x 0.9 = 360 A
Note: For circuit-breakers equipped with non-adjustable overcurrent-trip relays, Ir = In. Example: for iC60N 20 A circuit-breaker,
Ir = In = 20 A.
Fig. H30: Example of a NSX630N circuit-breaker equipped with a Micrologic 6.3E trip unit adjusted to 0.9, to give Ir = 360 A
Short-circuit relay trip-current setting (Im)
Short-circuit tripping relays (instantaneous or slightly time-delayed) are intended to trip the circuit-breaker rapidly on the occurrence of high values of fault current. Their tripping threshold Im is:
- Either fixed by standards for domestic type CBs, e.g. IEC 60898, or,
- Indicated by the manufacturer for industrial type CBs according to related standards, notably IEC 60947-2.
For the latter circuit-breakers there exists a wide variety of tripping devices which allow a user to adapt the protective performance of the circuit-breaker to the particular requirements of a load (see Fig. H31, Fig. H32 and Fig. H33).
Type of protective relay | Overload protection |
Short-circuit protection | |||
---|---|---|---|---|---|
Domestic breakers IEC 60898 |
Thermal- magnetic | Ir = In | Low setting type B 3 In ≤ Im ≤ 5 In |
Standard setting type C 5 In ≤ Im ≤ 10 In |
High setting circuit type D 10 In ≤ Im ≤ 20 In(2) |
Modular industrial(3) circuit-breakers |
Thermal- magnetic | Ir = In fixed |
Low setting type B or Z 3.2 In ≤ fixed ≤ 4.8 In |
Standard setting type C 7 In ≤ fixed ≤ 10 In |
High setting type D or K 10 In ≤ fixed ≤ 14 In |
Industrial(3) circuit-breakers IEC 60947-2 |
Thermal- magnetic | Ir = In fixed | Fixed: Im = 7 to 10 In | ||
Adjustable: 0.7 In ≤ Ir ≤ In | |||||
Adjustable: - Low setting : 2 to 5 In - Standard setting: 5 to 10 In | |||||
Electronic | Long delay 0.4 In ≤ Ir ≤ In |
Short-delay, adjustable 1.5 Ir ≤ Im ≤ 10 Ir Instantaneous (I) fixed I = 12 to 15 In |
(2) 50 In in IEC 60898, which is considered to be unrealistically high by most European manufacturers (Schneider Electric = 10 to 14 In).
(3) For industrial use, IEC standards do not specify values. The above values are given only as being those in common use.
Fig. H31: Tripping-current ranges of overload and short-circuit protective devices for LV circuit-breakers
Fig. H32: Performance curve of a circuit-breaker thermal-magnetic protective scheme
Ir: Overload (thermal or long-delay) relay trip-current setting
Im: Short-circuit (magnetic or short-delay) relay trip-current setting
Ii: Short-circuit instantaneous relay trip-current setting.
Icu: Breaking capacity
Fig. H33: Performance curve of a circuit-breaker electronic protective scheme
Isolating feature
A circuit-breaker is suitable for isolating a circuit if it fulfills all the conditions prescribed for a disconnector (at its rated voltage) in the relevant standard. In such a case it is referred to as a circuit-breaker-disconnector and marked on its front face with the symbol
All Acti 9, Compact NSX and Masterpact LV switchgear of Schneider Electric ranges are in this category.
Rated short-circuit breaking capacity (Icu or Icn)
The short-circuit current-breaking performance of a LV circuit-breaker is related (approximately) to the cos φ of the fault-current loop. Standard values for this relationship have been established in some standards
The short-circuit current-breaking rating of a CB is the highest (prospective) value of current that the CB is capable of breaking without being damaged. The value of current quoted in the standards is the rms value of the AC component of the fault current, i.e. the DC transient component (which is always present in the worst possible case of short-circuit) is assumed to be zero for calculating the standardized value. This rated value (Icu) for industrial CBs and (Icn) for domestic-type CBs is normally given in kA rms.
Icu (rated ultimate s.c. breaking capacity) and Ics (rated service s.c. breaking capacity) are defined in IEC 60947-2 together with a table relating Ics with Icu for different categories of utilization A (instantaneous tripping) and B (time-delayed tripping) as discussed in subclause 4.3.
Tests for proving the rated s.c. breaking capacities of CBs are governed by standards, and include:
- Operating sequences, comprising a succession of operations, i.e. closing and opening on short-circuit
- Current and voltage phase displacement. When the current is in phase with the supply voltage (cosφ for the circuit = 1), interruption of the current is easier than that at any other power factor. Breaking a current at low lagging values of cosφ is considerably more difficult to achieve; a zero power-factor circuit being (theoretically) the most onerous case.
In practice, all power-system short-circuit fault currents are (more or less) at lagging power factors, and standards are based on values commonly considered to be representative of the majority of power systems. In general, the greater the level of fault current (at a given voltage), the lower the power factor of the fault-current loop, for example, close to generators or large transformers.
Figure H34 below extracted from IEC 60947-2 relates standardized values of cos φ to industrial circuit-breakers according to their rated Icu.
- Following an open - time delay - close/open sequence to test the Icu capacity of a CB, further tests are made to ensure that:
- The dielectric withstand capability
- The disconnection (isolation) performance and
- The correct operation of the overload protection have not been impaired by the test.
Icu | cosφ |
---|---|
6 kA < Icu ≤ 10 kA | 0.5 |
10 kA < Icu ≤ 20 kA | 0.3 |
20 kA < Icu ≤ 50 kA | 0.25 |
50 kA < Icu | 0.2 |
Fig. H34: Icu related to power factor (cosφ) of fault-current circuit (IEC 60947-2)
References
- ^ 1 2 3 Current-level setting values which refer to the currentoperated thermal and “instantaneous” magnetic tripping devices for over-load and short-circuit protection.
ru:Основные характеристики автоматического выключателя zh:断路器的基本特性