Home > Sizing and protection of conductors > The neutral conductor > Breaking of the neutral conductor
(Text modified (guide 2015))
(Text updated (guide 2015))
Line 4: Line 4:
[[File:PictoChap7c.jpg|none]]
[[File:PictoChap7c.jpg|none]]
(see '''Fig. G64''')<br>The need to break or not the neutral conductor is related to the protection against indirect contact.<br>'''In TN-C scheme'''<br>The neutral conductor must not be open-circuited under any circumstances since it constitutes a PE as well as a neutral conductor.<br>'''In TT, TN-S and IT schemes<sup>(1)</sup>'''<br>In the event of a fault, the circuit-breaker will open all poles, including the neutral pole, i.e. the circuit-breaker is omnipolar.<br>The action can only be achieved with fuses in an indirect way, in which the operation of one or more fuses triggers a mechanical trip-out of all poles of an associated series-connected load-break switch.
(see '''Fig. G64''')<br>The need to break or not the neutral conductor is related to the protection against indirect contact.<br>'''In TN-C scheme'''<br>The neutral conductor must not be open-circuited under any circumstances since it constitutes a PE as well as a neutral conductor.<br>'''In TT, TN-S and IT schemes<sup>(1)</sup>'''<br>In the event of a fault, the circuit-breaker will open all poles, including the neutral pole, i.e. the circuit-breaker is omnipolar.<br>The action can only be achieved with fuses in an indirect way, in which the operation of one or more fuses triggers a mechanical trip-out of all poles of an associated series-connected load-break switch.
(1) In some coutries the rules applied for TN-S are the same than the rules for TN-C


[[ru:Отключение нейтрального провода]]
[[ru:Отключение нейтрального провода]]
[[zh:中性线的分断]]
[[zh:中性线的分断]]

Revision as of 06:24, 3 December 2014


PictoChap7c.jpg

(see Fig. G64)
The need to break or not the neutral conductor is related to the protection against indirect contact.
In TN-C scheme
The neutral conductor must not be open-circuited under any circumstances since it constitutes a PE as well as a neutral conductor.
In TT, TN-S and IT schemes(1)
In the event of a fault, the circuit-breaker will open all poles, including the neutral pole, i.e. the circuit-breaker is omnipolar.
The action can only be achieved with fuses in an indirect way, in which the operation of one or more fuses triggers a mechanical trip-out of all poles of an associated series-connected load-break switch.


(1) In some coutries the rules applied for TN-S are the same than the rules for TN-C