The architecture design: Difference between revisions
m (1 revision) |
(Text modified (guide 2015)) |
||
Line 1: | Line 1: | ||
{{Menu_MV_and_LV_architecture_selection_guide}} | {{Menu_MV_and_LV_architecture_selection_guide}} | ||
<br> | <br> | ||
The architecture design considered in this document | The architecture design considered in this document starts at the preliminary design stage (see Fig. D3 step1). It generally covers the levels of MV/LV main distribution, LV power distribution, and exceptionally the terminal distribution level. (see Fig. D2). | ||
In buildings all consumers are connected in low voltage. It means that MV distribution consists in: | |||
* connection to utility, | |||
* distribution to MV/LV substation(s), | |||
* MV/LV substation(s) itself. | |||
[[File:FigD02.jpg|none|449x383px]] | [[File:FigD02.jpg|none|449x383px]] | ||
'''''Fig. D2:''' Example of single-line diagram'' | '''''Fig. D2:''' Example of single-line diagram'' | ||
The design of an electrical distribution architecture can be described by a 3-stage process, with iterative possibilities. This process is based on taking account of the installation characteristics and criteria to be satisfied. <br> | The design of an electrical distribution architecture can be described by a 3-stage process, with iterative possibilities. This process is based on taking account of the installation characteristics and criteria to be satisfied. <br> | ||
[[ru:Проектирование архитектуры]] | [[ru:Проектирование архитектуры]] | ||
[[zh:系统设计]] | [[zh:系统设计]] |
Revision as of 09:10, 5 December 2014
The architecture design considered in this document starts at the preliminary design stage (see Fig. D3 step1). It generally covers the levels of MV/LV main distribution, LV power distribution, and exceptionally the terminal distribution level. (see Fig. D2).
In buildings all consumers are connected in low voltage. It means that MV distribution consists in:
- connection to utility,
- distribution to MV/LV substation(s),
- MV/LV substation(s) itself.
Fig. D2: Example of single-line diagram
The design of an electrical distribution architecture can be described by a 3-stage process, with iterative possibilities. This process is based on taking account of the installation characteristics and criteria to be satisfied.